Schneider Electric 5.0A, 3.0A, 2.0A manual Adjustable Rating Plug Replacement, Rating Plug Removal

Page 35

48049-136-05

Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units

Rev. 01, 07/2012

Section 5—Adjustable Rating Plug Replacement

 

 

Section 5—Adjustable Rating Plug Replacement

NOTE: To select correct replacement rating plug, see the product catalog.

NOTE: If adjustable rating plug is removed, the circuit breaker will default to a long-time pickup rating of 0.4 x In and a long-time delay at whatever setting was selected before the rating plug was removed.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E or CSA Z462.

This equipment must be installed and serviced only by qualified electrical personnel.

Turn off all power supplying this equipment before working on or inside equipment. Follow instructions shipped with circuit breaker to disconnect and reconnect circuit breaker.

Replace all devices, doors and covers before returning equipment to service.

Failure to follow this instruction will result in death or serious injury.

ENGLISH

Rating Plug Removal

1. Open circuit breaker contacts:

Figure 48: Remove Adjustable Rating Plug

B

C

 

— For Masterpact NT and NW circuit

 

breakers, press the “Push to open”

 

button on the circuit breaker.

 

— For other circuit breakers, move handle

 

to the off (O) position.

2.

Open switch cover (A).

3.

Unscrew adjustable rating plug mounting

 

screw (B).

4.

Remove adjustable rating plug (C).

06133205

06133221

A

long time

tr

4

8

 

12

Ir .7

.8

.9

(s)

 

 

16

 

2

 

 

 

20

.6

 

.95

1

 

 

 

24

 

.98

 

.5

@

6 Ir

.5

x In

1

 

 

 

 

.4

 

 

 

 

 

 

short time

tsd

.4

.4

.3

Isd

4

56

.3

 

 

.2

3

 

 

 

.1

2.5

 

8

.2.1

 

t

0

2

 

10

on

I

 

1.5 x Ir

 

 

 

delay

 

setting

 

 

 

 

 

alarm

 

instantan

eous

I i

4

5

2.5

3

6

 

8

2

 

10

1.5 x In

 

06133222

 

 

 

 

 

 

 

instantane

ous

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I i

4

5

 

 

 

 

 

 

 

short tim

 

.4

.3

3

 

6

 

 

 

 

 

 

 

2.5

 

 

 

 

 

 

 

Isd

4

 

.3

 

 

.2

 

8

 

 

 

 

 

alarm

5

 

 

.1

2

 

10

 

 

 

 

 

 

3

 

6

.2.1

 

 

1.5

x In

long time

(s)tr

 

8

1216

2.5

 

8

2

t

0

 

 

4

2

 

10

on

I

 

 

 

 

Ir

.8

.9

2

 

 

20

1.5

x Ir

delay

 

 

 

.7

 

.95

 

 

 

 

 

 

 

 

 

 

 

.6

 

.98

1

.5

 

24

setting

 

 

 

 

 

 

 

.5

 

1

 

@ 6 Ir

 

 

 

 

 

 

 

 

 

 

.4

x In

 

 

 

 

 

New Rating Plug Installation

1.Inspect mounting area for debris and contamination.

2.Gently push in new adjustable rating plug

(A).

3.Tighten adjustable rating plug mounting screw (B).

4.Set the switches on the trip unit (see Section 3 —Operation).

5.Close switch cover (C).

Figure 49: Install New Adjustable Rating Plug

06133223

A

06134244

B

 

 

 

 

 

 

 

alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

long time

tr

4

8

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ir

 

.8

.9

(s)

 

 

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.7

 

2

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.6

 

.95

1

 

 

 

24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.98

 

.5

@

6 Ir

instantan

eous

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.5

x In

1

 

 

 

 

 

 

 

 

 

 

instantaneous

 

 

 

 

 

 

 

.4

 

 

 

 

 

 

I i

4

5

 

 

 

 

 

 

 

 

 

 

 

 

 

short time

tsd

.4

.4

.3.2

2.53

 

 

68

 

 

t time

 

 

I i

4

5

 

 

 

 

 

 

Isd

4

5

.3

 

 

.1

2

 

10

shor

 

tsd

2

2.5

 

8

 

 

 

 

 

 

2.5

 

8

.2.1

I

t

0

 

x In

 

 

Isd

4

56

.3

1

2

 

10

 

 

 

 

 

 

alarm

2

 

10

on

 

 

 

 

 

3

 

1.5 x In

 

 

 

 

 

 

 

1.5

 

delay

 

 

 

 

 

2.5

 

 

.2

0

 

long time

tr

 

8

12

 

x Irg

 

 

 

 

 

 

 

 

 

2

 

8

.1

I2t

 

 

test

Ir

.8

.9

(s)

4

 

16

settin

 

 

 

 

 

 

 

 

 

 

1.5

 

10

on

delay

 

 

 

.7

 

.95

2

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

x Ir

 

 

 

 

 

.6

 

.98

1

 

 

24

 

 

 

 

 

 

 

 

 

 

 

 

setting

 

 

 

 

 

.5

 

1

 

.5

@ 6 Ir

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.4

x In

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

© 1999–2012 Schneider Electric All Rights Reserved

33-EN

Image 35
Contents Conserver pour usage ultérieur Page Retain for future use Micrologic 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip UnitsDeath or serious injury Hazard Categories and Special SymbolsPlease Note FCC NoticeTable of Contents List of Registers Rating Plug Removal New Rating Plug InstallationCommunications Trip Unit SettingsGeneral Information Introduction0A Trip Unit Micrologic 2.0A Trip UnitMicrologic 3.0A Trip Unit Micrologic 5.0A Trip Unit Micrologic 6.0A Trip Unit Zone-Selective Interlocking Trips and clears the fault. Circuit breaker 2 does not tripLong-Time Protection Trip Unit SwitchesMicrologic Trip Unit Long-Time Delay Values Short-Time Protection Micrologic Trip Unit Short-Time Delay ValuesInstantaneous Protection Micrologic Trip Unit Ground-Fault Pickup Values Indicator LightsGround-Fault Protection Overload Indicator LightControl Power Trip Unit TestingMicrologic Trip Unit Configuration Trip Indicator Lights15-EN External Power SupplyFunction Specification Ammeter Measurements Accessing InformationAmmeter Display17-EN Current MenuCurrent Menus Rev , 07/2012 Ammeter18-EN Peak Menu19-EN Switch Settings MenuSwitch settings menu displays Set pickup levels Switch Setting AdjustmentOperation Examples21-EN Set time delaySet Time Delay Rev , 07/2012 Operation22-EN Set Time DelaysSet time delays 23-EN Zone-Selective Interlocking ZSIZSI Combinations Units24-EN Wire circuit breakers for zone-selectiveCommunication Module values Interlocking25-EN Set communication module valuesScreen Trip Unit Settings CheckTrip Unit Settings Trip Unit Operation Verification27-EN Equipment Ground-Fault Trip Functions TestingTrip Unit Resetting Trip Unit Status CheckPreparation Trip Unit ReplacementRequired Tools Trip Unit Removal Trip Unit ReplacementBattery Installation Rating Plug Removal30-EN Trip Unit Installation31-EN Circuit Breaker Accessory CoverReplacement Close switch cover a32-EN Trip Unit Installation CheckTrip Unit Setup Circuit Breaker Reconnection Rating Plug Removal Adjustable Rating Plug ReplacementNew Rating Plug Installation Circuit Breaker Disconnection Battery ReplacementCircuit Breaker Accessory Cover Removal Battery Replacement35-EN Withstand Module ReplacementRev , 07/2012 Battery Replacement Module Module Name Equation Address Range Appendix A-Register ListList of Registers Register List37-EN Rev , 07/2012 Appendix A-Register ListSchneider Electric