Schneider Electric and 6.0A, 3.0A, 2.0A, 5.0A Appendix A-Register List, List of Registers, 36-EN

Page 38

Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units

48049-136-05

Appendix A—Register List

Rev. 01, 07/2012

 

 

Appendix A—Register List

ENGLISH

List of Registers

The quantities are listed in alphabetical order according to the SMS topic name.

NOTE: A system scan rate of 500 ms or greater is recommended to minimize communications timeout issues.

This is an abbreviated list of registers. For a complete list of registers, contact your local sales office.

To access available registers, the following address scheme applies.

Module

Module Name

Equation

Address Range

 

 

 

 

BCM

Circuit Breaker Communication Module

--

1–47

 

 

 

 

CCM

Cradle Communication Module

BCM + 50

51–97

 

 

 

 

PM

Protection Module (Internal to trip unit)

BCM + 100

101–147

 

 

 

 

MM

Meter Module (Internal to trip unit)

BCM + 200

201–247

 

 

 

 

Table 10:

Register List

 

 

 

 

 

 

 

 

 

 

 

 

 

SMS Topic Name

User Description

Number of

Register*

Module*

Units

Scale/Bitmask

Registers*

 

 

 

 

 

 

 

810DBrkrStatus

 

Circuit Breaker Status

1

661

BCM

 

Bit 0; ON = closed, OFF = open

810DBrkrTripStat

Circuit Breaker Trip Unit Status

1

661

BCM

 

Bit 2; ON = tripped, OFF = not tripped

 

 

 

 

 

 

 

 

BCM_SN

 

BCM Serial Number

4

516

BCM

 

ASCII text

 

 

 

 

 

 

 

Bit 8 = disconnected

BkrPos

 

Circuit Breaker Position

1

661

CCM

 

Bit 9 = connected

 

 

 

 

 

 

 

Bit 10 = test position

 

 

 

 

 

 

 

 

DT_3Regs

 

Device Clock Date/Time

3

679

BCM

 

3-register date/time format

EnableCloseBkr

 

Remote Closing Enabled

1

669

BCM

 

Bit 2; ON = enabled, OFF = not enabled

 

 

 

 

 

 

 

 

EnableOpenBkr

 

Remote Opening Enabled

1

669

BCM

 

Bit 1; ON = enabled, OFF = not enabled

EnableRemCtrl

 

Remote Control Enabled

1

669

BCM

 

Bit 3; ON = auto (enabled),

 

 

OFF = manual (not enabled)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IA

 

Current A

1

8821

PM

A

Unity

IA_PCT

 

Current A % Load

1

8837

PM

%

Unity

 

 

 

 

 

 

 

 

IB

 

Current B

1

8822

PM

A

Unity

IB_PCT

 

Current B % Load

1

8838

PM

%

Unity

 

 

 

 

 

 

 

 

IC

 

Current C

1

8823

PM

A

Unity

IC_PCT

 

Current C % Load

1

8839

PM

%

Unity

 

 

 

 

 

 

 

 

IG

 

Current G

1

8825

PM

A

Unity

IG_PCT

 

Current G % Load

1

8841

PM

%

Unity

 

 

 

 

 

 

 

 

IG_PCT_VIGI

 

Current G (VIGI) % Load

1

8842

PM

%

Hundredths

IG_VIGI

 

Current G (VIGI)

1

8826

PM

A

Thousandths

 

 

 

 

 

 

 

 

IMax

 

Current Max Present

1

8820

PM

A

Unity

IN

 

Current N

1

8824

PM

A

Unity

 

 

 

 

 

 

 

 

IN_PCT

 

Current N % Load

1

8840

PM

%

Unity

LDPUValue

 

Long Delay Pickup Value

2

8756

PM

A

Modulo 10,000 format**

MaxIA

 

Max Current A

1

8827

PM

A

Unity

MaxIB

 

Max Current B

1

8828

PM

A

Unity

 

 

 

 

 

 

 

 

MaxIC

 

Max Current C

1

8829

PM

A

Unity

MaxIG

 

Max Current G

1

8831

PM

A

Unity

 

 

 

 

 

 

 

 

MaxIG_VIGI

 

Max Current G (VIGI)

1

8832

PM

A

Thousandths

MaxIN

 

Max Current N

1

8830

PM

A

Unity

 

 

 

 

 

 

 

 

NominalCurrent

 

Circuit Breaker Nominal Current

1

8750

PM

A

Unity

ReadyToClose

 

Circuit Breaker Ready to Close

1

661

BCM

 

Bit 5; ON = yes, OFF = no

 

 

 

 

 

 

 

 

Continued on next page

36-EN

© 1999–2012 Schneider Electric All Rights Reserved

Image 38
Contents Conserver pour usage ultérieur Page Micrologic 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units Retain for future useFCC Notice Hazard Categories and Special SymbolsPlease Note Death or serious injuryTable of Contents Rating Plug Removal New Rating Plug Installation List of RegistersIntroduction Trip Unit SettingsGeneral Information Communications0A Trip Unit Micrologic 2.0A Trip UnitMicrologic 3.0A Trip Unit Micrologic 5.0A Trip Unit Micrologic 6.0A Trip Unit Trips and clears the fault. Circuit breaker 2 does not trip Zone-Selective InterlockingLong-Time Protection Trip Unit SwitchesMicrologic Trip Unit Long-Time Delay Values Micrologic Trip Unit Short-Time Delay Values Short-Time ProtectionInstantaneous Protection Overload Indicator Light Indicator LightsGround-Fault Protection Micrologic Trip Unit Ground-Fault Pickup ValuesTrip Indicator Lights Trip Unit TestingMicrologic Trip Unit Configuration Control Power15-EN External Power SupplyFunction Specification Display Accessing InformationAmmeter Ammeter MeasurementsRev , 07/2012 Ammeter Current MenuCurrent Menus 17-ENPeak Menu 18-EN19-EN Switch Settings MenuSwitch settings menu displays Examples Switch Setting AdjustmentOperation Set pickup levelsRev , 07/2012 Operation Set time delaySet Time Delay 21-EN22-EN Set Time DelaysSet time delays Units Zone-Selective Interlocking ZSIZSI Combinations 23-ENInterlocking Wire circuit breakers for zone-selectiveCommunication Module values 24-ENSet communication module values 25-ENTrip Unit Operation Verification Trip Unit Settings CheckTrip Unit Settings ScreenTrip Unit Status Check Equipment Ground-Fault Trip Functions TestingTrip Unit Resetting 27-ENPreparation Trip Unit ReplacementRequired Tools Rating Plug Removal Trip Unit ReplacementBattery Installation Trip Unit RemovalTrip Unit Installation 30-ENClose switch cover a Circuit Breaker Accessory CoverReplacement 31-EN32-EN Trip Unit Installation CheckTrip Unit Setup Circuit Breaker Reconnection Rating Plug Removal Adjustable Rating Plug ReplacementNew Rating Plug Installation Battery Replacement Battery ReplacementCircuit Breaker Accessory Cover Removal Circuit Breaker Disconnection35-EN Withstand Module ReplacementRev , 07/2012 Battery Replacement Register List Appendix A-Register ListList of Registers Module Module Name Equation Address RangeRev , 07/2012 Appendix A-Register List 37-ENSchneider Electric