Schneider Electric 5.0A, 3.0A, 2.0A, and 6.0A manual Zone-Selective Interlocking

Page 11

48049-136-05

Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units

Rev. 01, 07/2012

Section 1—General Information

 

 

Zone-Selective Interlocking

Short-time and ground-fault protection can be interlocked to provide zone-selective interlocking.

Control wiring links several trip units in the distribution network and in the event of a fault, a trip unit will obey the set delay time only if receiving a signal from a downstream trip unit.

If the trip unit does not receive a signal, tripping will be instantaneous (with no intentional delay).

The fault is cleared instantaneously by the nearest upstream circuit breaker.

Thermal stresses (I2t) in the network are minimized without any effect on the correct time delay coordination of the installation.

Figure 6 shows circuit breakers 1 and 2 zone- selective interlocked.

A fault at A is seen by circuit breakers 1 and

2.Circuit breaker 2 trips instantaneously and also informs circuit breaker 1 to obey set delay times. Thus, circuit breaker 2 trips and clears the fault. Circuit breaker 1 does not trip.

A fault at B is seen by circuit breaker 1. Circuit breaker 1 trips instantaneously since it did not receive a signal from the downstream circuit breaker 2. Circuit breaker

1trips and clears the fault. Circuit breaker 2 does not trip.

NOTE: Use I2t off with ZSI for proper coordination. Using I2t on with ZSI is not recommended as the delay in the upstream device receiving a restraint signal could result in the trip unit tripping in a time shorter than the published trip curve.

NOTE: Setting short-time delay (tsd) or ground-fault delay (tg) to the 0 setting will eliminate selectivity for that circuit breaker.

Figure 6: Zone-Selective Interlocking

06133376

1 B

2 A

ENGLISH

© 1999–2012 Schneider Electric All Rights Reserved

9-EN

Image 11
Contents Conserver pour usage ultérieur Page Retain for future use Micrologic 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip UnitsDeath or serious injury Hazard Categories and Special SymbolsPlease Note FCC NoticeTable of Contents List of Registers Rating Plug Removal New Rating Plug InstallationCommunications Trip Unit SettingsGeneral Information Introduction0A Trip Unit Micrologic 2.0A Trip UnitMicrologic 3.0A Trip Unit Micrologic 5.0A Trip Unit Micrologic 6.0A Trip Unit Zone-Selective Interlocking Trips and clears the fault. Circuit breaker 2 does not tripLong-Time Protection Trip Unit SwitchesMicrologic Trip Unit Long-Time Delay Values Short-Time Protection Micrologic Trip Unit Short-Time Delay ValuesInstantaneous Protection Micrologic Trip Unit Ground-Fault Pickup Values Indicator LightsGround-Fault Protection Overload Indicator LightControl Power Trip Unit TestingMicrologic Trip Unit Configuration Trip Indicator Lights15-EN External Power SupplyFunction Specification Ammeter Measurements Accessing InformationAmmeter Display17-EN Current MenuCurrent Menus Rev , 07/2012 Ammeter18-EN Peak Menu19-EN Switch Settings MenuSwitch settings menu displays Set pickup levels Switch Setting AdjustmentOperation Examples21-EN Set time delaySet Time Delay Rev , 07/2012 Operation22-EN Set Time DelaysSet time delays 23-EN Zone-Selective Interlocking ZSIZSI Combinations Units24-EN Wire circuit breakers for zone-selectiveCommunication Module values Interlocking25-EN Set communication module valuesScreen Trip Unit Settings CheckTrip Unit Settings Trip Unit Operation Verification27-EN Equipment Ground-Fault Trip Functions TestingTrip Unit Resetting Trip Unit Status CheckPreparation Trip Unit ReplacementRequired Tools Trip Unit Removal Trip Unit ReplacementBattery Installation Rating Plug Removal30-EN Trip Unit Installation31-EN Circuit Breaker Accessory CoverReplacement Close switch cover a32-EN Trip Unit Installation CheckTrip Unit Setup Circuit Breaker Reconnection Rating Plug Removal Adjustable Rating Plug ReplacementNew Rating Plug Installation Circuit Breaker Disconnection Battery ReplacementCircuit Breaker Accessory Cover Removal Battery Replacement35-EN Withstand Module ReplacementRev , 07/2012 Battery Replacement Module Module Name Equation Address Range Appendix A-Register ListList of Registers Register List37-EN Rev , 07/2012 Appendix A-Register ListSchneider Electric