Schneider Electric 2.0A, 3.0A Zone-Selective Interlocking ZSI, ZSI Combinations, Units, 23-EN

Page 25

48049-136-05

Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units

Rev. 01, 07/2012

Section 3—Operation

 

 

Zone-Selective Interlocking (ZSI)

Table 8:

ZSI Combinations

The number of devices which can be interlocked are shown in Table 8.

 

Upstream Device

UnitsTrip#.0xMicrologic

UnitsTripBSeriesMicrologicDSquare

RelayFault-Ground100-GCDSquare ProtectionEquipmentfor

RelayFault-Ground200-GCDSquarefor ProtectionEquipment

UnitsTripSTR58GerinMerlin

TripUSRCMandUSRCPioneerFederalUnits

 

 

 

 

 

 

 

 

(receives input from RIM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Downstream Device

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(sends output to RIM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Micrologic #.0x Trip Units

15

R

R

15

15

R

 

 

 

 

 

 

 

 

 

 

Square D Micrologic Series B Trip Units

R

26

R

R

R

15

 

 

 

 

 

 

 

 

 

 

Square D GC-100 Ground-Fault Relay

R

R

7

R

R

R

for Equipment Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Square D GC-200 Ground-Fault Relay

15

R

R

15

15

R

for Equipment Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Merlin Gerin STR58 Trip Units

15

R

R

15

15

R

 

 

 

 

 

 

 

 

 

 

Merlin Gerin STR53 Trip Units

15

R

R

15

15

R

 

 

 

 

 

 

 

 

 

 

Federal Pioneer USRC and USRCM Trip

R

15

R

R

R

15

Units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Square D Add-On Ground Fault Module

R

5

R

R

R

R

for Equipment Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R—RIM module is required to restrain any devices.

Numerical References—Maximum number of upstream circuit breakers which can be restrained without requiring a RIM Module.

ENGLISH

Circuit breaker terminals are shipped with terminals Z3, Z4 and Z5 jumpered to self- restrain the short-time and ground-fault functions. Remove the jumpers when activating zone-selective interlocking.

Figure 33: Jumpered Terminals

UC1

Z5 M1

Z3 Z4

Z1 Z2

Auxiliary Connections

© 1999–2012 Schneider Electric All Rights Reserved

23-EN

Image 25
Contents Conserver pour usage ultérieur Page Retain for future use Micrologic 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip UnitsPlease Note Hazard Categories and Special SymbolsFCC Notice Death or serious injuryTable of Contents List of Registers Rating Plug Removal New Rating Plug InstallationGeneral Information Trip Unit SettingsIntroduction CommunicationsMicrologic 3.0A Trip Unit Micrologic 2.0A Trip Unit0A Trip Unit Micrologic 5.0A Trip Unit Micrologic 6.0A Trip Unit Zone-Selective Interlocking Trips and clears the fault. Circuit breaker 2 does not tripMicrologic Trip Unit Long-Time Delay Values Trip Unit SwitchesLong-Time Protection Short-Time Protection Micrologic Trip Unit Short-Time Delay ValuesInstantaneous Protection Ground-Fault Protection Indicator LightsOverload Indicator Light Micrologic Trip Unit Ground-Fault Pickup ValuesMicrologic Trip Unit Configuration Trip Unit TestingTrip Indicator Lights Control PowerFunction Specification External Power Supply15-EN Ammeter Accessing InformationDisplay Ammeter MeasurementsCurrent Menus Current MenuRev , 07/2012 Ammeter 17-EN18-EN Peak MenuSwitch settings menu displays Switch Settings Menu19-EN Operation Switch Setting AdjustmentExamples Set pickup levelsSet Time Delay Set time delayRev , 07/2012 Operation 21-ENSet time delays Set Time Delays22-EN ZSI Combinations Zone-Selective Interlocking ZSIUnits 23-ENCommunication Module values Wire circuit breakers for zone-selectiveInterlocking 24-EN25-EN Set communication module valuesTrip Unit Settings Trip Unit Settings CheckTrip Unit Operation Verification ScreenTrip Unit Resetting Equipment Ground-Fault Trip Functions TestingTrip Unit Status Check 27-ENRequired Tools Trip Unit ReplacementPreparation Battery Installation Trip Unit ReplacementRating Plug Removal Trip Unit Removal30-EN Trip Unit InstallationReplacement Circuit Breaker Accessory CoverClose switch cover a 31-ENTrip Unit Setup Circuit Breaker Reconnection Trip Unit Installation Check32-EN New Rating Plug Installation Adjustable Rating Plug ReplacementRating Plug Removal Circuit Breaker Accessory Cover Removal Battery ReplacementBattery Replacement Circuit Breaker DisconnectionRev , 07/2012 Battery Replacement Withstand Module Replacement35-EN List of Registers Appendix A-Register ListRegister List Module Module Name Equation Address Range37-EN Rev , 07/2012 Appendix A-Register ListSchneider Electric