Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units | |
Rev. 01, 07/2012 | Section |
|
|
| Table 8: | ZSI Combinations |
The number of devices which can be interlocked are shown in Table 8.
| Upstream Device | UnitsTrip#.0xMicrologic | UnitsTripBSeriesMicrologicDSquare | UnitsTripSTR58GerinMerlin | TripUSRCMandUSRCPioneerFederalUnits | |||||
|
|
|
|
|
|
| ||||
| (receives input from RIM) |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| |
| Downstream Device |
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||||
| (sends output to RIM) |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
Micrologic #.0x Trip Units | 15 | R | R | 15 | 15 | R | ||||
|
|
|
|
|
|
|
|
|
| |
Square D Micrologic Series B Trip Units | R | 26 | R | R | R | 15 | ||||
|
|
|
|
|
|
|
|
|
| |
Square D | R | R | 7 | R | R | R | ||||
for Equipment Protection | ||||||||||
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| |
Square D | 15 | R | R | 15 | 15 | R | ||||
for Equipment Protection | ||||||||||
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| |
Merlin Gerin STR58 Trip Units | 15 | R | R | 15 | 15 | R | ||||
|
|
|
|
|
|
|
|
|
| |
Merlin Gerin STR53 Trip Units | 15 | R | R | 15 | 15 | R | ||||
|
|
|
|
|
|
|
|
|
| |
Federal Pioneer USRC and USRCM Trip | R | 15 | R | R | R | 15 | ||||
Units |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |
Square D | R | 5 | R | R | R | R | ||||
for Equipment Protection |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
Numerical
ENGLISH
Circuit breaker terminals are shipped with terminals Z3, Z4 and Z5 jumpered to self- restrain the
Figure 33: Jumpered Terminals
UC1
Z5 M1
Z3 Z4
Z1 Z2
Auxiliary Connections
© |
|