Schneider Electric and 6.0A, 3.0A, 2.0A, 5.0A manual Trip Unit Installation Check, 32-EN

Page 34

Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units

48049-136-05

Section 4—Trip Unit Replacement

Rev. 01, 07/2012

 

 

ENGLISH

Trip Unit Installation Check

Secondary Injection Testing

Primary Injection Testing

Check Accessory Operation

Trip Unit Setup

Circuit Breaker Reconnection

Field installation of a trip unit requires secondary injection testing with the Full-Function Test Kit. to ensure that the newly-installed trip unit is functioning properly. The test will require opening and closing the circuit breaker. Follow the procedures outlined in the instruction bulletins shipped with the circuit breaker and the test kit.

1.Make sure the circuit breaker is isolated from all upstream and downstream devices.

2.Perform secondary injection testing as outlined in the instruction bulletin shipped with the test kit. Verify that all applicable trip unit functions are operating properly.

3.Repeat step 2 with the circuit breaker in the open position.

NOTE: The test kit states that the circuit breaker should be closed when performing the test. Do not close the circuit breaker for this step.

4.If any test fails, do not put the circuit breaker into service and contact the local sales office for factory authorization service.

Primary injection testing is recommended to ensure that all trip system connections have been correctly made. Perform primary injection testing per the instructions in the Field Testing and Maintenance Guide, bulletin number 0600IB1201.

1.Installed accessories – Validate the proper operation of all installed accessories. See the corresponding accessory instruction bulletins for operational testing procedures.

2.Zone selective interlocking – If the circuit breaker is part of a ZSI system, follow the zone selective interlocking test procedures as outlined in the Full Function Test Kit instruction bulletin.

3.Communications – If communication modules exist, validate circuit breaker has re-established communications with the supervisor.

1.If an auxiliary power supply is being used for the Micrologic trip unit, reconnect the auxiliary power supply.

2.Reset the trip unit switches to original values, as recorded at the beginning of this section.

Reconnect circuit breaker as directed in the circuit breaker instruction bulletin shipped with the circuit breaker.

32-EN

© 1999–2012 Schneider Electric All Rights Reserved

Image 34
Contents Conserver pour usage ultérieur Page Micrologic 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units Retain for future useFCC Notice Hazard Categories and Special SymbolsPlease Note Death or serious injuryTable of Contents Rating Plug Removal New Rating Plug Installation List of RegistersIntroduction Trip Unit SettingsGeneral Information CommunicationsMicrologic 3.0A Trip Unit Micrologic 2.0A Trip Unit0A Trip Unit Micrologic 5.0A Trip Unit Micrologic 6.0A Trip Unit Trips and clears the fault. Circuit breaker 2 does not trip Zone-Selective InterlockingMicrologic Trip Unit Long-Time Delay Values Trip Unit SwitchesLong-Time Protection Micrologic Trip Unit Short-Time Delay Values Short-Time ProtectionInstantaneous Protection Overload Indicator Light Indicator LightsGround-Fault Protection Micrologic Trip Unit Ground-Fault Pickup ValuesTrip Indicator Lights Trip Unit TestingMicrologic Trip Unit Configuration Control PowerFunction Specification External Power Supply15-EN Display Accessing InformationAmmeter Ammeter MeasurementsRev , 07/2012 Ammeter Current MenuCurrent Menus 17-ENPeak Menu 18-ENSwitch settings menu displays Switch Settings Menu19-EN Examples Switch Setting AdjustmentOperation Set pickup levelsRev , 07/2012 Operation Set time delaySet Time Delay 21-ENSet time delays Set Time Delays22-EN Units Zone-Selective Interlocking ZSIZSI Combinations 23-ENInterlocking Wire circuit breakers for zone-selectiveCommunication Module values 24-ENSet communication module values 25-ENTrip Unit Operation Verification Trip Unit Settings CheckTrip Unit Settings ScreenTrip Unit Status Check Equipment Ground-Fault Trip Functions TestingTrip Unit Resetting 27-ENRequired Tools Trip Unit ReplacementPreparation Rating Plug Removal Trip Unit ReplacementBattery Installation Trip Unit RemovalTrip Unit Installation 30-ENClose switch cover a Circuit Breaker Accessory CoverReplacement 31-ENTrip Unit Setup Circuit Breaker Reconnection Trip Unit Installation Check32-EN New Rating Plug Installation Adjustable Rating Plug ReplacementRating Plug Removal Battery Replacement Battery ReplacementCircuit Breaker Accessory Cover Removal Circuit Breaker DisconnectionRev , 07/2012 Battery Replacement Withstand Module Replacement35-EN Register List Appendix A-Register ListList of Registers Module Module Name Equation Address RangeRev , 07/2012 Appendix A-Register List 37-ENSchneider Electric