Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units | |
Rev. 01, 07/2012 | Section |
|
|
Set communication module values:
1.Press and release scroll button to sequence addresses (1 through 47). When the correct address number is reached, enter the value by pressing and holding scroll button until the display stops flashing.
Baud rate screen will appear after address has been entered.
2.Press and release scroll button to sequence baud rates (4.8k, 9.6k or 19.2k). When the desired baud rate appears, enter the value by pressing and holding scroll button until the display stops flashing.
Parity screen will appear after baud rate has been entered.
3.Press and release scroll button to sequence parities (E [even] or n [none]). When the desired parity appears, enter the value by pressing and holding scroll button until the display stops flashing.
Languages screen will appear after parity has been entered.
4.Press and release scroll button to scroll through languages (French [Fr], US English [En US], UK English [En], German [d], Spanish [SP] or Italian [It]). When the desired language appears, enter the value by pressing and holding scroll button until the display stops flashing.
Ammeter display will return to the default screen after language is entered.
After the communication module values have been set, ammeter will automatically return to the current (i.e., default) menu.
After setting circuit breaker communication module values, drawout circuit breakers must have the cradle communication module, if available, activated. For drawout circuit breakers, refer to the cradle communication module instructions to complete setup.
Figure 36: Set Communication Module Values
| Communications Address |
| Baud Rate |
06134248 | 06133703 | 06134248 | 06133704 |
| Baud Rate |
| Parity |
06134248 | 06133704 | 06134248 | 06133705 |
| Parity |
| Language |
06134248 | 06133705 | 06134248 | 06134888 |
| Language |
|
|
06134248 | 06134888 | 06134248 |
|
ENGLISH
© |
|