Schneider Electric 2.0A Equipment Ground-Fault Trip Functions Testing, Trip Unit Resetting, 27-EN

Page 29

48049-136-05

Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units

Rev. 01, 07/2012

Section 3—Operation

 

 

Equipment Ground-Fault Trip Functions Testing

Paragraph 230-95 (c) of the National Electrical Code requires that all equipment ground-fault protection systems be tested when first installed.

With the circuit breaker closed, test the ground- fault (Micrologic 6.0A trip unit only) trip functions. For instructions on how to close circuit breaker, refer to the circuit breaker installation instructions shipped with the circuit breaker.

1.Press the ground-fault test button (A). Circuit breaker should trip.

2.If circuit breaker does not trip, contact the local field office.

NOTE: Trip unit must be powered to test ground-fault trip function. The trip unit is powered if the circuit breaker is carrying more than 0.20 x In of load current, if the 24 Vdc external power supply is connected or if the Full- Function Test Kit or Hand-Held Test Kit is connected and on.

Figure 38: Test Equipment Ground-Fault Trip Function

06134249

Micro

logic

6.0 A

 

 

100 %

 

 

 

40 %

 

 

 

menu

 

 

A

ENGLISH

Trip Unit Resetting

When the circuit breaker trips, the fault indicator will remain lit until the trip unit is reset.

Press the reset/test button (A) to reset the trip unit after trip.

Do not return circuit breaker to service until cause of trip is determined. For more information, refer to the circuit breaker installation instructions shipped with the circuit breaker.

Trip Unit Status Check

To check trip unit battery and trip indicators, press the test/reset button (A).

All trip indicators (B) will light up

Battery status will be displayed

If no battery status is displayed, there is no battery installed.

The battery bar graph reading is valid after the reset button has been released.

If the battery bar graph shows the battery needs to be changed, use Square D battery catalog number S33593:

lithium battery

1.2AA, 3.6 V, 800 ma/h

For instructions on replacing battery, see Section 6—Battery Replacement.

Figure 39: Reset Trip Unit

A

06133379

Micrologic 6.0 A

NOTE: Trip unit must be powered to test battery. The trip unit is powered if the circuit breaker is carrying more than 0.20 x In of load current, if the 24 Vdc external power supply is connected or if the Full-Function Test Kit or Hand-Held Test Kit is connected and on.

Figure 40: Check Trip Unit Status

 

B

A

 

 

 

 

Charged

06133379

 

 

 

 

 

 

 

A

 

 

 

 

 

Half

-Charged

 

gic .0

 

 

 

 

 

 

 

 

 

 

 

 

 

Change Battery

 

 

 

 

 

 

 

 

 

 

© 1999–2012 Schneider Electric All Rights Reserved

27-EN

Image 29
Contents Conserver pour usage ultérieur Page Retain for future use Micrologic 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip UnitsPlease Note Hazard Categories and Special SymbolsFCC Notice Death or serious injuryTable of Contents List of Registers Rating Plug Removal New Rating Plug InstallationGeneral Information Trip Unit SettingsIntroduction Communications0A Trip Unit Micrologic 2.0A Trip UnitMicrologic 3.0A Trip Unit Micrologic 5.0A Trip Unit Micrologic 6.0A Trip Unit Zone-Selective Interlocking Trips and clears the fault. Circuit breaker 2 does not tripLong-Time Protection Trip Unit SwitchesMicrologic Trip Unit Long-Time Delay Values Short-Time Protection Micrologic Trip Unit Short-Time Delay ValuesInstantaneous Protection Ground-Fault Protection Indicator LightsOverload Indicator Light Micrologic Trip Unit Ground-Fault Pickup ValuesMicrologic Trip Unit Configuration Trip Unit TestingTrip Indicator Lights Control Power15-EN External Power SupplyFunction Specification Ammeter Accessing InformationDisplay Ammeter MeasurementsCurrent Menus Current MenuRev , 07/2012 Ammeter 17-EN18-EN Peak Menu19-EN Switch Settings MenuSwitch settings menu displays Operation Switch Setting AdjustmentExamples Set pickup levelsSet Time Delay Set time delayRev , 07/2012 Operation 21-EN22-EN Set Time DelaysSet time delays ZSI Combinations Zone-Selective Interlocking ZSIUnits 23-ENCommunication Module values Wire circuit breakers for zone-selectiveInterlocking 24-EN25-EN Set communication module valuesTrip Unit Settings Trip Unit Settings CheckTrip Unit Operation Verification ScreenTrip Unit Resetting Equipment Ground-Fault Trip Functions TestingTrip Unit Status Check 27-ENPreparation Trip Unit ReplacementRequired Tools Battery Installation Trip Unit ReplacementRating Plug Removal Trip Unit Removal30-EN Trip Unit InstallationReplacement Circuit Breaker Accessory CoverClose switch cover a 31-EN32-EN Trip Unit Installation CheckTrip Unit Setup Circuit Breaker Reconnection Rating Plug Removal Adjustable Rating Plug ReplacementNew Rating Plug Installation Circuit Breaker Accessory Cover Removal Battery ReplacementBattery Replacement Circuit Breaker Disconnection35-EN Withstand Module ReplacementRev , 07/2012 Battery Replacement List of Registers Appendix A-Register ListRegister List Module Module Name Equation Address Range37-EN Rev , 07/2012 Appendix A-Register ListSchneider Electric