Schneider Electric 5.0A, 3.0A, 2.0A Trip Unit Replacement, Rating Plug Removal, Trip Unit Removal

Page 31

48049-136-05

Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units

Rev. 01, 07/2012

Section 4—Trip Unit Replacement

 

 

Rating Plug Removal

A small Phillips screwdriver is needed to remove the adjustable rating plug.

Figure 41: Remove Adjustable Rating Plug

B

C

ENGLISH

1.Open switch cover (A).

2.Unscrew adjustable rating plug mounting screw (B).

3.Remove adjustable rating plug (C). Save for installation in replacement trip unit.

06133205

06133221

A

long time

tr

4

8

 

12

Ir .7

.8

.9

(s)

 

 

16

 

2

 

 

 

20

.6

 

.95

1

 

 

 

24

 

.98

 

.5

@

6 Ir

.5

x In

1

 

 

 

 

.4

 

 

 

 

 

 

short time

tsd

.4

.4

.3

Isd

4

56

.3

 

 

.2

3

 

 

 

.1

2.5

 

8

.2.1

 

t

0

2

 

10

on

I

 

1.5 x Ir

 

 

 

delay

 

setting

 

 

 

 

 

alarm

 

instantan

eous

I i

4

5

2.5

3

6

 

8

2

 

10

1.5 x In

 

06133222

 

 

 

 

 

 

 

instantane

ous

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I i

4

5

 

 

 

 

 

 

 

short tim

 

.4

.3

3

 

6

 

 

 

 

 

 

 

2.5

 

 

 

 

 

 

 

Isd

4

 

.3

 

 

.2

 

8

 

 

 

 

 

alarm

5

 

 

.1

2

 

10

 

 

 

 

 

 

3

 

6

.2.1

 

 

1.5

x In

long time

(s)tr

 

8

1216

2.5

 

8

2

t

0

 

 

4

2

 

10

on

I

 

 

 

 

Ir

.8

.9

2

 

 

20

1.5

x Ir

delay

 

 

 

.7

 

.95

 

 

 

 

 

 

 

 

 

 

 

.6

 

.98

1

.5

 

24

setting

 

 

 

 

 

 

 

.5

 

1

 

@ 6 Ir

 

 

 

 

 

 

 

 

 

 

.4

x In

 

 

 

 

 

Trip Unit Removal

1.Remove connector block (A) from top of trip unit, if present.

2.Loosen two trip unit screws (B).

3.Slide out trip unit (C).

Figure 42: Remove Existing Trip Unit

 

A

06134853

06134854

B

C

Trip Unit Replacement

Battery Installation

If a new trip unit is being installed, install the trip unit battery.

Install battery holder with battery (A) in trip unit, observing the correct polarity as indicated on the battery compartment.

NOTE: Battery holder with battery is located under the side flap in the cardboard box the trip unit is shipped in.

Figure 43: Install Battery

A

06133375

LITHIUM BATTERY 3.6V - SL - 550/S SONNENSCHEIN

Press test/reset button (A). All four indicator lights (B) should light. If they do not light, check polarity of battery and retest. If indicator lights still do not light up when test/reset button is pressed, stop installation and contact the local sales office for factory authorized service

Figure 44: Trip Indicator Lights

B A

06133245

Micrologic

.0 A

 

 

© 1999–2012 Schneider Electric All Rights Reserved

29-EN

Image 31
Contents Conserver pour usage ultérieur Page Retain for future use Micrologic 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip UnitsDeath or serious injury Hazard Categories and Special SymbolsPlease Note FCC NoticeTable of Contents List of Registers Rating Plug Removal New Rating Plug InstallationCommunications Trip Unit SettingsGeneral Information IntroductionMicrologic 3.0A Trip Unit Micrologic 2.0A Trip Unit0A Trip Unit Micrologic 5.0A Trip Unit Micrologic 6.0A Trip Unit Zone-Selective Interlocking Trips and clears the fault. Circuit breaker 2 does not tripMicrologic Trip Unit Long-Time Delay Values Trip Unit SwitchesLong-Time Protection Short-Time Protection Micrologic Trip Unit Short-Time Delay ValuesInstantaneous Protection Micrologic Trip Unit Ground-Fault Pickup Values Indicator LightsGround-Fault Protection Overload Indicator LightControl Power Trip Unit TestingMicrologic Trip Unit Configuration Trip Indicator LightsFunction Specification External Power Supply15-EN Ammeter Measurements Accessing InformationAmmeter Display17-EN Current MenuCurrent Menus Rev , 07/2012 Ammeter18-EN Peak MenuSwitch settings menu displays Switch Settings Menu19-EN Set pickup levels Switch Setting AdjustmentOperation Examples21-EN Set time delaySet Time Delay Rev , 07/2012 OperationSet time delays Set Time Delays22-EN 23-EN Zone-Selective Interlocking ZSIZSI Combinations Units24-EN Wire circuit breakers for zone-selectiveCommunication Module values Interlocking25-EN Set communication module valuesScreen Trip Unit Settings CheckTrip Unit Settings Trip Unit Operation Verification27-EN Equipment Ground-Fault Trip Functions TestingTrip Unit Resetting Trip Unit Status CheckRequired Tools Trip Unit ReplacementPreparation Trip Unit Removal Trip Unit ReplacementBattery Installation Rating Plug Removal30-EN Trip Unit Installation31-EN Circuit Breaker Accessory CoverReplacement Close switch cover aTrip Unit Setup Circuit Breaker Reconnection Trip Unit Installation Check32-EN New Rating Plug Installation Adjustable Rating Plug ReplacementRating Plug Removal Circuit Breaker Disconnection Battery ReplacementCircuit Breaker Accessory Cover Removal Battery ReplacementRev , 07/2012 Battery Replacement Withstand Module Replacement35-EN Module Module Name Equation Address Range Appendix A-Register ListList of Registers Register List37-EN Rev , 07/2012 Appendix A-Register ListSchneider Electric