Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units | |
Section | Rev. 01, 07/2012 |
|
|
ENGLISH
Section 3—Operation
Switch Setting Adjustment
1.Open switch cover (A).
2.Adjust the appropriate switches (B) to desired values.
3.Replace switch cover. Use wire seal MICROTUSEAL (C, not provided), if necessary, to provide tamper evidence.
Examples
Circuit breaker is rated 2000 A.
Figure 23: Adjust Switch Settings
06133205 | 06133206 | 06133207 |
A | C |
| |
| B |
Figure 24: Circuit Breaker Rating
06133208
In 2000 A
Micrologic 2.0A Trip Unit
Figure 25: Set Pickup Levels
1. Set pickup levels.
06134251 | long time | ||
Ir | .8 | alarm | |
.7 | .9 | ||
| .6 |
| .95 |
| .5 |
| .98 |
| .4 x In 1 | ||
| instantaneous | ||
| Isd | 4 |
|
| 3 | 5 | |
| 2.5 |
| 6 |
| 2 |
| 8 |
| 1.5 x Ir | 10 | |
| setting |
In = 2000 A
Ir = 0.7 x In = 1400 A
Isd = 2 x Ir = 2800 A
06134245
t
0 Ir | Isd |
| © |