Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units Section 4—Trip Unit Replacement

48049-136-05 Rev. 01, 07/2012

ENGLISH

Trip Unit Installation

1.Inspect trip unit connector pins and surfaces. If there is any damage, misaligned pins, or contamination, stop installation and contact the local sales office for factory authorized service.

2.Inspect trip unit mounting base on the circuit breaker. Clear any debris from area and check that all accessory wiring is properly routed for the trip unit being installed. If there is any damage or contamination, stop installation and contact the local sales office for factory authorized service.

3.For Masterpact NW circuit breaker only: Manually depress trip unit interlock (A) and hold it in place during steps 4–6 below.

4.Align guide rail (B) on bottom of trip unit with guide rail slot (C) on trip unit mounting base in circuit breaker and gently slide the trip unit in until it stops.

NOTE: The Masterpact NT and NW trip unit mounting bases are shock mounted and therefore can flex slightly.

Figure 45: Install Trip Unit

Masterpact NW Circuit Breaker

06135453

A

06135451

C

B

NOTICE

HAZARD OF EQUIPMENT DAMAGE

Check installation of trip unit to assure proper connections and seating.

Failure to follow this instruction can result in equipment damage or improper circuit breaker tripping.

30-EN

© 1999–2012 Schneider Electric All Rights Reserved

Image 32
Contents Conserver pour usage ultérieur Page Micrologic 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units Retain for future useHazard Categories and Special Symbols Please NoteFCC Notice Death or serious injuryTable of Contents Rating Plug Removal New Rating Plug Installation List of RegistersTrip Unit Settings General InformationIntroduction Communications0A Trip Unit Micrologic 2.0A Trip UnitMicrologic 3.0A Trip Unit Micrologic 5.0A Trip Unit Micrologic 6.0A Trip Unit Trips and clears the fault. Circuit breaker 2 does not trip Zone-Selective InterlockingLong-Time Protection Trip Unit SwitchesMicrologic Trip Unit Long-Time Delay Values Micrologic Trip Unit Short-Time Delay Values Short-Time ProtectionInstantaneous Protection Indicator Lights Ground-Fault ProtectionOverload Indicator Light Micrologic Trip Unit Ground-Fault Pickup ValuesTrip Unit Testing Micrologic Trip Unit ConfigurationTrip Indicator Lights Control Power15-EN External Power SupplyFunction Specification Accessing Information AmmeterDisplay Ammeter MeasurementsCurrent Menu Current MenusRev , 07/2012 Ammeter 17-ENPeak Menu 18-EN19-EN Switch Settings MenuSwitch settings menu displays Switch Setting Adjustment OperationExamples Set pickup levelsSet time delay Set Time DelayRev , 07/2012 Operation 21-EN22-EN Set Time DelaysSet time delays Zone-Selective Interlocking ZSI ZSI CombinationsUnits 23-ENWire circuit breakers for zone-selective Communication Module valuesInterlocking 24-ENSet communication module values 25-ENTrip Unit Settings Check Trip Unit SettingsTrip Unit Operation Verification ScreenEquipment Ground-Fault Trip Functions Testing Trip Unit ResettingTrip Unit Status Check 27-ENPreparation Trip Unit ReplacementRequired Tools Trip Unit Replacement Battery InstallationRating Plug Removal Trip Unit RemovalTrip Unit Installation 30-ENCircuit Breaker Accessory Cover ReplacementClose switch cover a 31-EN32-EN Trip Unit Installation CheckTrip Unit Setup Circuit Breaker Reconnection Rating Plug Removal Adjustable Rating Plug ReplacementNew Rating Plug Installation Battery Replacement Circuit Breaker Accessory Cover RemovalBattery Replacement Circuit Breaker Disconnection35-EN Withstand Module ReplacementRev , 07/2012 Battery Replacement Appendix A-Register List List of RegistersRegister List Module Module Name Equation Address RangeRev , 07/2012 Appendix A-Register List 37-ENSchneider Electric