10 | Troubleshooting | |
|
|
|
|
|
|
Problem | Possible Cause | Solution |
| No power. | Check main disconnect, |
| fuses, wiring, and power lead | |
|
| to unit. |
| Wrong voltage supplied to | Voltage must be within plus |
| or minus ten percent (±10%) | |
| unit. | |
| of nameplate rating. | |
|
| |
| Defective On/Off switch. | Replace switch. |
|
| Replace fuse, check |
|
| transformer, check wiring for |
| Control circuit fuse blown. | loose wires, check for shorted |
| coils on contactors and | |
|
| |
Unit does not run. |
| solenoids, check crankcase |
|
| heater. |
| Defective control transformer. | Replace. |
| Flow switch circuit is open. | Check pump for proper |
| rotation. | |
|
| |
| Pump motor off on overload. | Reset and test motor. |
|
| Check that the chiller pump is |
| Unit is off on flow switch or | running. |
| Check that all valves are | |
| pressure switch. | open. |
|
| Check for defective flow |
|
| switch or pressure switch. |
| Freeze control set higher than | Lower freeze control setting |
| temperature of liquid in | to 10°F (6ºC) below the |
| leaving temperature you | |
| system. | |
| want. | |
|
| |
|
| Air cooled units: Check and |
|
| clean air filters. Check |
|
| condenser fans for proper |
Pump runs, |
| rotation. Check for dirty |
| condenser. Check for | |
compressor does not. | High pressure refrigerant | condenser air obstruction. |
| Check for tripped motor | |
| cutout switch contacts open. | overload, blown fuses, or bad |
|
| condenser fan motor. |
|
| Water cooled units: Check for |
|
| water valves turned on. |
|
| Check for dirty condenser. |
|
| Check water flow through |
|
| condenser. |
Page 68 of 77 | SCW Series Central Chilling Stations |