4 | Sequence Of Operation |
|
|
4-1 Staging
1.The system uses a PID control algorithm to regulate the chilled water temperature. As the required control effort increases or decreases, the system compressors are infinitely unloaded or turned on/off to keep the temperature at the specified
2.Compressor
4-2 Alarms
If a fault occurs, that compressor or circuit is deactivated. The load will automatically shift to any other compressors that are currently
4-3 Lead-Lag Compressors
The system automatically rotates the compressor order to generate a Lead/Lag rotation. Any time a compressor is faulted or manually taken
Once the fault is cleared or manually put
4-4 Lead-Lag Pumps
The system automatically rotates the pump order to generate a Lead/Lag rotation. Any time a pump is faulted or manually taken
Page 28 of 77 | SCW Series Central Chilling Stations |