Parameter 36 – Signal Input 2 (S2) Setpoint
When the S2 configuration, parameter 35, is set to one of the jog modes, this parameter defines the jog setpoint in display units. If the drive operating mode is set to Follower Mode, then this parameter is set in RPM units. This allows a follower control to be jogged when the master is stopped.
Parameter 37 – Signal Input 2 (S2) Pulses per Revolution
This is the number of pulses per revolution for the signal input 2 (S2). The drive supports pickups and encoders from 1 to 2048 pulses per revolution.
Parameter 95 – Factory Default Command
When set to a value of 5, the unit will be reset to factory default settings. This can also be achieved by applying power to the unit with both the Enter and Down buttons depressed. The programming jumper must be in the "On" position for this method to function.
Parameter 98 – Save to User Default Area Command
When set to a value of 5, the unit will store all adjustable parameters to the user default area. The user default area is intended to be a location where an end user can store settings specific to their application. Using this, an end user can easily refresh their custom settings in the field if an someone accidentally reconfigures the unit unsuccessfully. Another common use for this area is testing and initial setup. The user can store
Parameter 99 – Restore from User Default Area Command
When set to a value of 1, the unit will restore the all adjustable parameters from the user default area. See parameter 98 for additional information.