Adcom A720, A723 manual Chapter

Page 19

CHAPTER 3

Maintaining and servicing the RTU

19

If you have verified that the battery needs to be replaced, follow these steps to do so:

1.Open the lid by unscrewing the four screws in the corner of the addIT RTU.

2.Gently remove the lid (the battery is fixed on the lid and is connected to the electronics board by means of a connector).

3.Remove the battery’s plug from the PCB connector.

4.Remove the battery pack from the lid (it is taped to the lid) and replace it with a new one (obtainable from Adcon).

5.Insert the battery plug into the PCB connector.

6.Mount the lid back, taking care that the rubber gasket sealing the box is not out of place.

WARNING Be sure to mount the rubber gasket properly, so that the unit’s IP65 environmental protection is not affected.

7.Screw the four screws back in, applying a moderate force.

Image 19
Contents ADC N ADC N Contents Contents What are addIT devices? IntroductionInstallation issues Italics ConventionsChapter Opening the packages Using the Base StationInstalling the receiver Installing the base stationAddIT Power Supply Installing the power supplyConfiguring the software Replacing the fuseUsing the RTU Shows an addIT RTU Installing the RTUShows what a typical RTU field installation looks like More about the LED tool Maintaining and servicing the RTU RTU batteryConfiguring an addIT RTU in the addVANTAGE software Changing the battery Chapter Chapter Performing Advanced Functions Receiver connector Understanding connectorsDevice series Pins on an I/O Connector Top View RTU connectorsConfiguring the devices AddIT RTU Power Connector Top ViewSerial communication protocol General format of a commandGeneral format of an answer Series 1 devices Using terminal commandsSET Ownid nnnn SET Slot 3600 SET OwnidSET PMP bl bh SET PMP 63SET Freq 467112500 SET Freq freq stepSET Rssi value SET Rssi Querying the actual configuration parametersCmds Series 2 and 3 devicesFreq 433925000 25000 FreqFreq 433925000 FreqSlot PMP SST PMP 65 72193 cm 193 CM 1Repl DEVDEL Repl 5667DEL Dn cs Data 5666 12/12/1998Data b1 b2 b3 ... bn Dd mm yyyy hh mm ss si ft d1 d2 ... dn dd mm yyyyFrame 38 description Frame 39 description Data 6367 30/4/1999Imme DataRoute Info FdevTemp = internalTem p 146 900 Info 255 0 18/4/1999 21511 1.3 0 0 0 91Anlg Code Description Parameters Returns Sampling methods are defined by three bits, as follows Return result depends on the control byte see table. However A720B and A723, but see also the comments in Remote on Performing Advanced Functions Command Code Definitions Port 193 RX 6789 Port 7/5/1999 183422193 TX 15190 B 6789 B#234 BA #7851 BAVER 2.0 Blst 30/8/2001 160341VER VER 1.3Notifications Real time clock Returned errors listCommand line interpreter Device descriptors and storage handlerNotifications Chapter Parameter Min Typ Max Unit Appendix. SpecificationsTransmitter all measurements made on a 50 Ω resistive load Chapter Chapter Index INFO, 41 OWNID, 26 PMP PMP What a base station contains Xmit Credits Credits and ColophonColophon