Page 21

Chapter 2: Installation

GND

1

GND

2

GND

3

GND

4

Sensor wired to

Sensor wired to

Alert Input 2

Alert Input 3

Figure 2-7. Two Sensors Wired to Adjacent Inputs

NOTE

Do not use sensors, switches, or relays that supply any voltage or current to the Model 1104. Be aware of proximity to other electrical wires or components when placing wires that lead from the sensors to the unit. Avoid running the wires near electrical devices that use high voltage or current, such as motors, heavy machinery, etc. This voltage may be inductive- ly coupled into the sensor wiring and could result in damage to the the Model 1104’s circuitry. Try to place wires at least 6 inches from other electrical wiring or devices.

2.11 Multiple Sensors

The Model 1104 may have more than one sensor connected to the same alert input, as long as the normal condition for each sensor on the same alert input is identical (either all N.O. or all N.C.). However, only one remote temperature sensor can be used on each input.

When wiring several normally closed sensors on one input, they must be connected in series. Connect one lead from the first sensor to the numbered screw of the alert input. Next, take the other lead from the first sensor and connect it to one lead from the next sensor. Continue connecting sensors end-to-end until you have connected all of your sensors. Take the second lead from the last sensor and connect it to the ground screw on the Model 1104. See Figure 2-8. Multiple N.C. sensors are typically magnetic reed switches to monitor the security of windows and doors.

21

Image 21
Contents Model SENSAPHONE, INC Important Safety Instructions Sensaphone Model 1104 User’s Manual PHONETICS, INC FCC RequirementsSensaphone Model 1104 User’s Manual Canadian Department of Communications Statement Sensaphone Model 1104 User’s Manual Viii Technical Support Summary of the Alarm Dial-Out ProcessDial-out Telephone Numbers Unit ID NumberTone or Pulse Dialing Special Dialing Rings Until AnswerEnable/Disable Inputs Input ConfigurationEstablishing High and Low Temperature Limits Temperature ScaleExit Delay High Sound Alarm Enable/DisableAlarm Acknowledgment Status ReportIntroduction Technical Support Operating Environment Installation+ + + RUN Installing the Telephone Line Alert Inputs Sensor Connected to an Alert Input Two Sensors Wired to Adjacent Inputs ~ ~ From the unit completely to avoid damage to the circuitry Disconnecting the Model 1104 for Storage or Seasonal UseSensaphone Model 1104 User’s Manual Local Keypad Quick StartRUN Set Configuration of InputsSet the ID Number StatusNumber Set Dial-Out Telephone NumbersModel 1104 responds Enter low temperature limit Set Temperature LimitsModel 1104 responds Enter high temperature limit Quick Start Alert Condition Action-Response Programmable FeatureCommunications Programming Programming the ID NumberHello, this is telephone number Unit ID Number Interrogating the ID Number Enter number Programming Dial-out Telephone NumbersErasing a Telephone Number Interrogating a Dial-out Telephone NumberPress ENTER. The Model 1104 will say Enter Tone or Pulse Dialing Special Dialing KeysPause Pound # Incorporating a PauseAsterisk CodePressed Incorporating a Pound # or AsteriskPress any unassigned number key from 1 to 4 to represent Special Dialing to a Beeper or Pager Now press Pause once to activate a four second delay. This Interrogating Rings Until Answer Programming Rings Until AnswerUsing the TAD Feature TAD Enable/DisableNo TAD In Use Programming the Listen-in Time Interrogating the Listen-in Time Programming the Call Delay Call DelayInterrogating Call Delay Local Voice Mute Enable/Disable Local Voice Mute10.2 Interrogating Voice Repetitions Programming Voice RepetitionsModel 1104 will recite the number programmed Programming Intercall Time Seconds Interrogating Intercall TimeProgramming Max Calls Interrogating Max Calls Setting the Clock Interrogating for the Current Time Unlocking the Keypad Locking the KeypadUsing the number keys, enter the digits for the code Sensaphone Model 1104 User’s Manual Alarm Programming Status Programming Input ConfigurationVerifying Input Configuration Changing Enabled/Disabled Input StatusVerifying Enabled/Disabled Input Status Immediately follows the number recited for that input Programming Input Recognition TimeRecites the digits as they are pressed Interrogating Input Recognition TimePress the corresponding input key 1 to Programming Temperature Limits for a Selected Input Interrogating High and Low Temperature Limits Disabling Alarm Response to High or Low TemperatureTemperature Calibration Interrogating Temperature Calibration Programming Temperature CalibrationObtaining Current Temperature Enabling/Disabling the AC Power Alarm Model 1104 will recite the digits as they are pressed Programming Power Failure Recognition TimeInterrogating Power Failure Recognition Time Using the number keys, enter a value for sound sensitivity Programming Sound Alarm SensitivityInterrogating Sound Sensitivity Programming High Sound Alarm Recognition TimeChanging Enabled/Disabled High Sound Alarm Exit Delay Acknowledgment Status Report & Remote Access Local AcknowledgmentTouch-Tone Acknowledgment Callback Acknowledgment Example Status Report, No Alarms Example Status Report, Existing Alarms Battery Condition Example Status Report, Disabled InputsRemote Access by Touch-Tone Telephone Battery Condition OK, if over 8.2 VoltsReplace batteries, if below 7.2 Volts Activating Status Report Sensaphone Model 1104 User’s Manual Operation Alarm Detection, Dial-out and AcknowledgmentValid Alarm TemperatureCall Delay Alarm MessageIntercall Time Alarm MessagesVoice Repetitions Call ProgressAcknowledgment Local, On-siteTouch-Tone Fast CodeTAD Enabled Number...the last number it dialedHave a good day Example a Dial-out Telephone Call Appendix a Troubleshooting Solution ProblemCommunications / Dial-out CauseAppendix a Troubleshooting Communications / Dial-out Problem Cause Solution Temperature Monitoring Problem Cause Solution Other Monitoring Problem Cause Solution Sound Level Monitoring Problem Cause Solution101 Appendix a Troubleshooting Use rechargeable nicad batteries Be sure to use alkaline batteries-do notAppendix B Weekly Testing Procedure 104 Part Number Sensor / Switch Appendix C AccessoriesSensaphone Model 1104 User’s Manual 106 Appendix D Returning the Unit for Repair Service DepartmentYear Limited Warranty