Chapter 5: Alarm Programming
3.Press the number key corresponding to the selected temperature input.
1 |
CALL |
DELAY |
4 |
MAX CALLS |
2 | 3 |
VOICE | INTERCALL |
REPS | TIME |
5.5 Temperature Scale
Temperature inputs may be set in either Fahrenheit or Celsius degrees. The default temperature scale is Fahrenheit. To change to Celsius:
1. Press SENSOR ON/OFF.
SENSOR
ON/OFF
2. Press TEMP. The Model 1104 responds: “Off,” indicating |
Celsius scale has replaced Fahrenheit scale. |
TEMP |
F° / C° |
3. To return to Fahrenheit scale, repeat the key sequence. The |
Model 1104 responds: “On,” indicating Fahrenheit scale is in |
effect. |
NOTE
When switching from Fahrenheit to Celsius, or vice versa, the change applies to all inputs configured to read temperature. When switching temperature scales it is important to reset high and low temperature lim- its on all temperature inputs. Refer to Section 5.4.1 to reset temperature limits.
5.6 Temperature Calibration
To compensate for minor variances in sensor accuracy, an offset may be programmed for each temperature input. The amount of offset is measured in degrees Fahrenheit or degrees Celsius.
Adjustments are possible within a range from
71