96
Communications / Dial-out:
Sensaphone
Problem
1. The Model 1104 fails to dial out.
Cause
a)The telephone number may be incorrectly programmed.
b)Tone or pulse (the current dialing method) is not compatible with the telephone line on which the Model 1104 is installed.
c)Recognition Time is too long. An alert condition does not remain in effect long enough to become a valid alarm.
Solution
Recheck programming steps.
Refer to Chapter 4, Section 4.2.1.
Switch from the current setting: from tone to pulse, or from pulse to tone.
Refer to Chapter 4, Section 4.3.
Reprogram Recognition Time. Set the Recognition Time to the minimum duration required to create a valid alarm. If possible, test the new setting by deliberately creating an alert condition.
Refer to Chapter 5, Section 5.3.
® Model 1104 User’s Manual
d) Max Calls is set to zero. | Reprogram Max Calls. It is a good idea to set |
| your Max Calls to at least equal the number of |
| |
| Refer to Chapter 4, Section 4.12.1. |