Sensaphone® Model 1104 User’s Manual

GND

1

GND

2

GND

3

GND

4

~ ~

~ ~

Multiple normally-closed sensors wired in series (example using Input 2)

Alert condition occurs when a switch is opened

Figure 2-8. Multiple Normally Closed Sensors

To wire several normally open sensors to one alert input, connect them in parallel. To do this, take one lead from each sensor and attach it to the numbered terminal. Then, take the second lead from each sensor and attach each to the corresponding ground screw. Refer to Figure 2-9.

GND

1

GND

2

GND

3

GND

4

Alert condition occurs when a normally open switch closes.

Figure 2-9. Multiple Normally Open Sensors

2.12 Outdoor Wiring

When wiring sensors outdoors, DO NOT allow exposed wires to run freely in open air; under such conditions, the Model 1104 is susceptible to serious damage during a lightning storm.

Depending upon the distance outdoor wiring must travel, consideration should be given to the use of shielded wire inside a metal conduit. Both shield and conduit should be connected to an earth ground. This prevents stray voltage from entering the unit.

22

Image 22
Contents Model SENSAPHONE, INC Important Safety Instructions Sensaphone Model 1104 User’s Manual FCC Requirements PHONETICS, INCSensaphone Model 1104 User’s Manual Canadian Department of Communications Statement Sensaphone Model 1104 User’s Manual Viii Summary of the Alarm Dial-Out Process Technical SupportTone or Pulse Dialing Special Dialing Unit ID NumberDial-out Telephone Numbers Rings Until AnswerEstablishing High and Low Temperature Limits Input ConfigurationEnable/Disable Inputs Temperature ScaleAlarm Acknowledgment High Sound Alarm Enable/DisableExit Delay Status ReportIntroduction Technical Support Installation Operating Environment+ + + RUN Installing the Telephone Line Alert Inputs Sensor Connected to an Alert Input Two Sensors Wired to Adjacent Inputs ~ ~ Disconnecting the Model 1104 for Storage or Seasonal Use From the unit completely to avoid damage to the circuitrySensaphone Model 1104 User’s Manual Quick Start Local KeypadSet Configuration of Inputs RUNStatus Set the ID NumberSet Dial-Out Telephone Numbers NumberSet Temperature Limits Model 1104 responds Enter low temperature limitModel 1104 responds Enter high temperature limit Quick Start Action-Response Programmable Feature Alert ConditionProgramming the ID Number Communications ProgrammingHello, this is telephone number Unit ID Number Interrogating the ID Number Programming Dial-out Telephone Numbers Enter numberInterrogating a Dial-out Telephone Number Erasing a Telephone NumberPress ENTER. The Model 1104 will say Enter Special Dialing Keys Tone or Pulse DialingPause Asterisk Incorporating a PausePound # CodeIncorporating a Pound # or Asterisk PressedPress any unassigned number key from 1 to 4 to represent Special Dialing to a Beeper or Pager Now press Pause once to activate a four second delay. This Programming Rings Until Answer Interrogating Rings Until AnswerTAD Enable/Disable Using the TAD FeatureNo TAD In Use Programming the Listen-in Time Interrogating the Listen-in Time Call Delay Programming the Call DelayInterrogating Call Delay Enable/Disable Local Voice Mute Local Voice MuteProgramming Voice Repetitions 10.2 Interrogating Voice RepetitionsModel 1104 will recite the number programmed Programming Intercall Time Interrogating Intercall Time SecondsProgramming Max Calls Interrogating Max Calls Setting the Clock Interrogating for the Current Time Locking the Keypad Unlocking the KeypadUsing the number keys, enter the digits for the code Sensaphone Model 1104 User’s Manual Alarm Programming Programming Input Configuration StatusChanging Enabled/Disabled Input Status Verifying Input ConfigurationVerifying Enabled/Disabled Input Status Programming Input Recognition Time Immediately follows the number recited for that inputInterrogating Input Recognition Time Recites the digits as they are pressedPress the corresponding input key 1 to Programming Temperature Limits for a Selected Input Disabling Alarm Response to High or Low Temperature Interrogating High and Low Temperature LimitsTemperature Calibration Programming Temperature Calibration Interrogating Temperature CalibrationObtaining Current Temperature Enabling/Disabling the AC Power Alarm Programming Power Failure Recognition Time Model 1104 will recite the digits as they are pressedInterrogating Power Failure Recognition Time Programming Sound Alarm Sensitivity Using the number keys, enter a value for sound sensitivityProgramming High Sound Alarm Recognition Time Interrogating Sound SensitivityChanging Enabled/Disabled High Sound Alarm Exit Delay Local Acknowledgment Acknowledgment Status Report & Remote AccessTouch-Tone Acknowledgment Callback Acknowledgment Example Status Report, No Alarms Example Status Report, Existing Alarms Example Status Report, Disabled Inputs Battery ConditionBattery Condition OK, if over 8.2 Volts Remote Access by Touch-Tone TelephoneReplace batteries, if below 7.2 Volts Activating Status Report Sensaphone Model 1104 User’s Manual Alarm Detection, Dial-out and Acknowledgment OperationCall Delay TemperatureValid Alarm Alarm MessageVoice Repetitions Alarm MessagesIntercall Time Call ProgressTouch-Tone Local, On-siteAcknowledgment Fast CodeNumber...the last number it dialed TAD EnabledHave a good day Example a Dial-out Telephone Call Appendix a Troubleshooting Communications / Dial-out ProblemSolution CauseAppendix a Troubleshooting Communications / Dial-out Problem Cause Solution Temperature Monitoring Problem Cause Solution Sound Level Monitoring Problem Cause Solution Other Monitoring Problem Cause Solution101 Appendix a Troubleshooting Be sure to use alkaline batteries-do not Use rechargeable nicad batteriesAppendix B Weekly Testing Procedure 104 Appendix C Accessories Part Number Sensor / SwitchSensaphone Model 1104 User’s Manual 106 Service Department Appendix D Returning the Unit for RepairYear Limited Warranty