Sensaphone® Model 1104 User’s Manual
5.6.1Programming Temperature Calibration
1.Press SET.
SET
#
2. Press CALIBRATE.
6
CALIBRATE
3.Press the number (1 to 4) of the selected temperature input to be calibrated.
1 |
CALL |
DELAY |
4 |
MAX CALLS |
2 | 3 |
VOICE | INTERCALL |
REPS | TIME |
4.Enter the number required to offset the current temperature reading so a correct reading is obtained.
•To program a positive offset number (up to +10 degrees), enter the number on the keypad. The Model 1104 recites the digits as they are pressed.
•To program a negative offset number (up to
5.Press ENTER. The Model 1104 responds:“Enter.”
ENTER |
TONE |
PM |
NOTE
If you find that your calibration offset exceeds more than + 5 or
5.6.2Interrogating Temperature Calibration
1.Press WHAT IS.
WHAT
IS
*
2. Press CALIBRATE.
72