Chapter 5: Alarm Programming
5.4Establishing High and Low Temperature Limits
High and low temperature limits can be separately programmed for each input configured as temperature. Limits can range from
When temperature limits exceed high or low settings, the Model
1104 will dial out with an alarm message. Default settings are: 10° F for low temperature and 100° F for high temperature.
5.4.1Programming Temperature Limits for a Selected Input
1.Press SET.
SET
#
2. Press TEMP LIMITS.
5
TEMP LIMITS
3.From the number keys, press a number (from 1 to 4) that corresponds to the temperature input being programmed.
1 |
CALL |
DELAY |
4 |
MAX CALLS |
2 | 3 |
VOICE | INTERCALL |
REPS | TIME |
The Model 1104 responds: “Enter low temperature limit.”
4.Using the number keys, enter a value for low temperature limit. The Model 1104 will recite the digits as they are pressed. If a negative number is required, first press PAUSE, then enter the number.
1 |
CALL |
DELAY |
4 |
MAX CALLS |
7 |
RECOGNITION |
TIME |
2 |
VOICE |
REPS |
5 |
TEMP LIMITS |
8 |
CLOCK |
0 |
ID NUMBER |
POWER |
3 |
INTERCALL |
TIME |
6 |
CALIBRATE |
9 |
LISTEN TIME |
SOUND |
5. Press ENTER.
ENTER |
TONE |
PM |
The Model 1104 responds: “Enter high temperature limit.”
6.Using the number keys, enter the value for high temperature limit. The Model 1104 recites the digits as they are pressed.
69