Return to Section TOC
Return to Section TOC
Return to Section TOC
Return to Master TOC
Return to Master TOC
Return to Master TOC
INSTALLATION | ||||||
|
|
| ||||
|
|
|
|
| ||
AUXILIARY POWER |
|
| 120 V GFCI DUPLEX RECEPTACLES | |||
|
|
|
| A GFCI (Ground Fault Circuit Interrupter) electrical | ||
|
|
|
| |||
| CAUTION |
| receptacle is a device to protect against electric shock | |||
|
|
|
| should a piece of defective equipment connected to it | ||
Do not connect any plugs that connect to the | develop a ground fault. If this situation should occur, | |||||
the GFCI will trip, removing voltage from the output of | ||||||
power receptacles in parallel. | ||||||
the receptacle. If a GFCI receptacle is tripped see the | ||||||
MAINTENANCE section for | detailed information on | |||||
Start the engine and set the “IDLER” control switch to | ||||||
testing and resetting it. A GFCI receptacle should be | ||||||
the “High Idle” mode. Set | the “CONTROL” to 10. | |||||
properly tested at least once every month. | ||||||
Voltage is now correct at the receptacles for auxiliary | ||||||
|
| |||||
power. This must be done | before a tripped GFCI | The 120V auxiliary power receptacles should only be | ||||
receptacle can be reset properly. See the MAINTE- | ||||||
used with three wire grounded type plugs or approved | ||||||
NANCE section for more detailed information on test- | ||||||
double insulated tools with two wire plugs. | ||||||
ing and resetting the GFCI receptacle. | ||||||
|
| |||||
The RANGER® 3 PHASE can provide both three | The current rating of any plug used with the system | |||||
must be at least equal to the current load through the | ||||||
phase and single phase power, up to 11,500 watts of | ||||||
associated receptacle. |
| |||||
480 volts AC, three phase 60Hz power for peak use, |
| |||||
|
| |||||
and up to 10,500 watts of 480 volts AC, three phase | 480 VOLT 3 PHASE RECEPTACLE WITH GROUND | |||||
60Hz power for continuous use, up to 10,500 watts of | ||||||
|
| |||||
120/240 volts AC, single phase 60Hz power for peak | The 480 volt receptacle can supply 12.6 amps of 3 | |||||
use, and up to 9,500 watts of 120/240 volt AC, single | ||||||
phase power, or up to 15 amps of single phase power. | ||||||
phase 60Hz power for continuous use. The front of the | ||||||
A NEMA | ||||||
machine includes four receptacles for connecting the | ||||||
cle. The ground (GND) connection is connected to the | ||||||
AC power plugs; one 20 amp 480 volt 3 phase NEMA | ||||||
machine frame, it is NOT the neutral of the three phase | ||||||
receptacle, one 50 amp 120/240 volt NEMA | ||||||
connection, and should under no circumstances be | ||||||
receptacle and two 20 amp 120 volt NEMA | ||||||
connected to the neutral of any 3 phase load. Do not | ||||||
receptacles. Output voltage | is within | |||||
connect 480V 3 phase to | single phase premises | |||||
loads up to rated capacity. Do not use 3 phase power | ||||||
wiring. |
| |||||
and single phase power simultaneously. All auxiliary |
| |||||
|
| |||||
power is protected by cuircuit breakers. | If 480 volt single phase load is to be run, the X lead | |||||
|
|
|
| |||
120/240 VOLT DUAL VOLTAGE RECEPTACLE | must be one of the leads in the circuit in order for the | |||||
automatic idle to function. Using a NEMA plug L16- | ||||||
|
|
|
| |||
The 120/240 volt receptacle can supply up to 40 amps | 20P, connect either X and Y or X and Z to the recepta- | |||||
cle, as well as the machine ground. See Figure A.2. | ||||||
of 240 volt power to a two wire circuit, up to 40 amps | ||||||
|
| |||||
of 120 volts power from each side of a three wire cir- | NOTE: Use of | |||||
cuit (up to 80 amps total). Do not connect the 120 volt | ||||||
ed while welding. |
| |||||
circuits in parallel. Current sensing for the automatic |
| |||||
|
| |||||
idle feature is only in one leg of the three wire circuit as |
|
| ||||
shown in Figure A.1. |
|
|
|
| ||
| FIGURE A.1 | FIGURE A.2 |
Return to Section TOC
Return to Master TOC
GND
120 V
120 V*
*Current Sensing for Automatic Idle. (Receptacle viewed from front of Machine)
Y
480 V
X | Z |
240 V
GND
(FOR ALL SINGLE AND THREE PHASE LOADS)