Lincoln Electric IM10066 manual Muffler Outlet Pipe, Spark Arrestor, AIR Cleaner Inlet Hood

Page 15

A-5

INSTALLATION

A-5

 

 

 

The AIR VANTAGE® 500 (AU) is shipped with the negative battery cable disconnected. Before you oper- ate the machine, make sure the Engine Switch is in the OFF position and attach the disconnected cable securely to the negative (-) battery terminal.

Remove the insulating cap from the negative battery terminal. Replace and tighten negative battery cable terminal. NOTE: This machine is furnished with a wet charged battery; if unused for several months, the bat- tery may require a booster charge. Be sure to use the correct polarity when charging the battery.

MUFFLER OUTLET PIPE

Remove the plastic plug covering the muffler outlet tube. Using the clamp provided secure the outlet pipe to the outlet tube with the pipe positioned such that it will direct the exhaust in the desired position.

SPARK ARRESTOR

Some federal, state or local laws may require that petrol or diesel engines be equipped with exhaust spark arrestors when they are operated in certain locations where unarrested sparks may present a fire hazard. The standard muffler included with this welder has an internal spark arrestor. When required by local regulations, a suitable spark arrestor, must be installed and properly maintained.

CAUTION

An incorrect arrestor may lead to damage to the engine or adversely affect performance.

------------------------------------------------------------------------

AIR CLEANER INLET HOOD

Remove the plastic plug covering the air cleaner inlet. Install the air cleaner inlet hood to the air cleaner.

WELDING TERMINALS

The AIR VANTAGE® 500 (AU) is equipped with a tog- gle switch for selecting "hot" welding terminals when in the "WELD TERMINALS ON" position or "cold" welding terminals when in the "REMOTELY CON- TROLLED" position.

WELDING OUTPUT CAbLES

With the engine off, route the electrode and work cables thru the strain relief bracket provided on the front of the base and connect to the terminals provid- ed. These connections should be checked periodically and tightened if necessary.

Listed in Table A.1 are copper cable sizes recom- mended for the rated current and duty cycle. Lengths stipulated are the distance from the welder to work and back to the welder again. Cable sizes are increased for greater lengths primarily for the purpose of minimizing cable voltage drop.

Table A.1 Combined Length of Electrode and

Work Cables.

TOTAL COMbINED LENGTH OF ELECTRODE AND WORK CAbLES

 

 

 

 

 

 

 

 

 

Cable Length

 

 

Cable Size for

 

 

 

 

 

500 Amps

 

 

 

 

 

 

100% Duty Cycle

 

 

 

0-150 Ft. (0-46 meters)

 

 

3/0 AWG (95mm2)

 

 

 

150-200 Ft. (46-61 meters)

 

 

3/0 AWG (95mm2)

 

 

 

200-250 Ft. (61-76 meters)

 

 

4/0 AWG(120mm2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MACHINE GROUNDING

Because this portable engine driven welder creates its own power, it is not necessary to connect its frame to an earth ground, unless the machine is connected to premises wiring (home, shop, etc.).

To prevent dangerous electric shock, other equipment to which this engine driven welder supplies power must:

WARNING

be grounded to the frame of the welder using a grounded type plug or be double insulated.

Do not ground the machine to a pipe that carries explosive or combustible material.

------------------------------------------------------------------------

When this welder is mounted on a truck or trailer, its frame must be securely connected to the metal frame of the vehicle. When this engine driven welder is con- nected to premises wiring such as that in a home or shop, its frame must be connected to the system earth ground. See further connection instructions in the sec- tion entitled “Standby Power Connections” as well as the article on grounding in the latest National Electrical Code and the local codes.

In general, if the machine is to be grounded, it should be connected with a #8 or larger copper wire to a solid earth ground such as a metal ground stake going into the ground for at least 10 Feet or to the metal frame- work of a building which has been effectively ground- ed.

The National Electric Code lists a number of alternate means of grounding electrical equipment. A machine grounding stud marked with the symbol is provided on the front of the welder.

AIR VANTAGE® 500 (AU)

Image 15
Contents 11656 Safety Depends on YouCalifornia Proposition 65 Warnings SafetyIiSAFETY Iii IiiSAFETYPrécautions DE Sûreté IvSAFETYElectromagnetic Compatibility EMC Methods of Reducing Emissions Mains Supply Vii Please Examine Carton and Equipment For Damage ImmediatelyOn-Line Product Registration TAbLE of Contents TAbLE of Contents Height Width Depth InstallationDuty Cycle Welding Output Volts at Rated Amps Open Circuit VoltageStacking Safety PrecautionsLocation and Ventilation StoringTowing High Temperature OperationLifting High Altitude OperationFuel CAP PRE-OPERATION Engine and COM- Pressor ServiceOIL Fuel USE Diesel Fuel onlyWelding Terminals AIR Cleaner Inlet HoodMuffler Outlet Pipe Spark ArrestorRemote Control Auxiliary Power ReceptaclesSTANDbY Power Connections Control Cable Model Connection of Lincoln ELEC- Tric Wire FeedersConnection of LN-15 to the AIR Vantage 500 AU Across The-Arc ModelShut off welder before making any electrical con- nections Connection of the LN-25 to the AIR Vantage 500 AUGeneral Description OperationControls and Settings Output Control Idler SwitchOIL Pressure Gauge ENGINE PROTECTIONPIN Connector WELD MODE SELECTOR SWITCHWelding Terminals Switch Wire Feeder Voltmeter SwitchAIR Compressor Controls 26 Thru What are VRD and Rocv DEVICES? Welding Power SourcesSafety VRD Operation IndicatorTable b.1 Cummins b3.3 Engine Fuel Consumption Starting TechniqueBREAK-IN Period Typical Fuel ConsumptionWelder Operation Stick Welding ModeCC-STICK Mode Touch Start TIG ModeWire WELDING-CV ARC GougingTable b.3 Typical Current Ranges Plus Auxiliary Power OperationSimultaneous Welding and AUXIL- Iary Power Loads ParallelingK2641-2 Four Wheeled STEERAbLE Yard Trailer AccessoriesOptional Field Installed Accessories TIG OptionsCompressor Maintenance MaintenanceSingle- and Two-StageEngine Air Cleaners Service InstructionsFuel Filters Cooling SystemPreventing Electrical Damage Nameplates / Warning Decals MAIN- Tenance CleaningWelder / Generator MAINTE- Nance StorageTROUbLESHOOTING Cause Recommended Course of Action PRObLEMSSymptoms POSSIbLETROUbLESHOOTING Faulty receptacle Wiring Diagram Diagrams To Work Electrode Cable To Wire Feed Unit Engine Welders / K867 / K775 / LN-7 Connection DiagramDiagrams Diagrams Engine Welders / K867 / LN-8 Connection Diagram Diagrams Diagrams Diagrams Diagrams Diagrams Diagrams Dimension Print AIR Vantage 500 AU Precaucion Warnung