INSTALLATION

A-8

 

 

 

NOTE: The 240 V receptacle has two 120 V circuits, but are of opposite polarities and cannot be paralleled.

All auxiliary power is protected by circuit breakers. The 120V has 20 Amp circuit breakers for each duplex receptacle. The 120/240V Single Phase and the 240V Three-Phases have a 50 Amp 3-pole Circuit Breaker that disconnects both hot leads and all Three Phases simultaneously

STANDbY POWER CONNECTIONS

The VANTAGE® 300 is suitable for temporary, stand- by or emergency power using the engine manufactur- er’s recommended maintenance schedule.

The VANTAGE® 300 can be permanently installed as a standby power unit for 240 VAC, 3 wire, single phase, 40 amp service. Connections must be made by a licensed electrician who can determine how the 120/240 VAC power can be adapted to the particular installation and comply with all applicable electrical codes.

Install the double-pole, double-throw switch between the power company meter and the premis- es disconnect. Switch rating must be the same or greater than the customer’s premises disconnect and service over current protection.

Take necessary steps to assure load is limited to the capacity of the generator by installing a 50 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 50 amperes. Loading above the rated output will reduce output voltage below the allow- able - 10% of rated voltage which may damage appliances or other motor-driven equipment and may result in overheating of the engine and/or alternator windings.

Install a 50 amp, 120/240 VAC plug (NEMA Type 14-50) to the double-pole circuit breaker using No. 6, 4 conductor cable of the desired length. (The 50 amp, 120/240 VAC plug is available in the optional K802R plug kit or as part number T12153-9.)

Plug this cable into the 50 Amp, 120/240 Volt receptacle on the case front.

VANTAGE® 300

Image 16
Contents Safety Depends on You VantageSafety Electric Shock can kill Welding and Cutting Sparks can Cause fire or explosion IiiIvSAFETY Précautions DE SûretéPlease Examine Carton and Equipment For Damage Immediately On-Line Product RegistrationTAbLE of Contents Vii Section DSection E Section FHeight Width Depth Weight AIR Cleaner Engine Idler Muffler Engine ProtectionEmissions Fuel System Governor VantageAuxiliary Power Circuit bREAKER Other Circuit bREAKERS ReceptaclesSafety Precautions VRD Voltage Reduction DeviceLocation and Ventilation StackingTowing Vehicle MountingPRE-OPERATION Engine Service OILFuel Engine Cooling SystemRemote Control Electrical ConnectionsMachine Grounding Welding TerminalsAuxiliary Power Receptacles Welding Output CAbLESTotal COMbINED Length of Electrode and Work CAbLES Duplex Receptacles and Gfci ModulesSTANDbY Power Connections Connection of Vantage 300 to Premises Wiring Connection of Lincoln Electric Wire Feeders Connection of LN-15 to the Vantage Shut the welder offAcross The-Arc Model Control Cable ModelInstallation General Description Weld Mode Selector Switch Figure b.1Ground Stud Wire Feeder Voltmeter SwitchTAbLE b.1 Coolant Temperature GAUGE-A indicator Engine ControlsGlow Plug Push bUTTON Electric Fuel GAUGE- The electric fuelWelder Operation Stopping the EngineTypical Vantage 300 Fuel Consumption TIG Welding Typical Current Ranges 1 for Tungsten ELECTRODES2Downhill Pipe Welding TAbLE b.3Wire WELDING-CV Auxiliary PowerARC Gouging TAbLE b.4TIG Options Wire Feeder OptionsPLASMA CUTTING Routine Maintenance Engine Oil ChangeAIR Cleaner OIL Filter ChangeService Instructions Single- and Two-Stage Engine Air CleanersCooling System Tightening the FAN bELTBLEEDING the Fuel System See Deutz engine manualEngine Adjustment Servicing Optional SparkArrestor Fuel FilterWelder / Generator Maintenance Gfci Module Testing and Resetting ProcedureTROUbLESHOOTING PRObLEMS SymptomsPOSSIbLE Cause Recommended Course of ActionWelding without a control cable Contact your local Lincoln Faulty PC board or welder alterna Field Service Facility Your local Lincoln AuthorizedDiagrams Diagrams Diagrams Diagrams Diagrams Diagrams Diagrams Diagrams Diagrams Diagrams Dimension Print L12573-1Vantage Precaucion Warnung