INSTALLATION | ||
|
|
|
2.Take necessary steps to assure load is limited to the capacity of the Commander by installing a 45 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 45 amperes. Loading above the rated output will reduce output voltage below the allowable
3.Install a 50 amp 120/240 VAC plug (NEMA Type 14-
50)to the
4.Plug this cable into the 50 Amp 120/240 Volt recep- tacle on the Commander 400 case front.
Figure A.2 Connection of the Commander 400 to Premises Wiring
240Volt
60 Hz.
Service
240 VOLT
POWER
120 VOLT
COMPANY
120 VOLT
METER
GROUNDED CONDUCTOR
NEUTRAL
BUS
DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
PROTECTION.
|
| 45AMP | |
|
| 240 VOLT | |
|
| DOUBLE | |
50 AMP, 120/240 |
| POLE | |
| CIRCUIT | ||
VOLT PLUG | 240 VOLT | ||
BREAKER | |||
NEMA TYPE |
|
|
GND
N
N
LOAD
PREMISES
DISCONNECT AND
SERVICE
GROUNDOVERCURRENT PROTECTION
50 AMP, 120/240 VOLT
RECEPTACLENOTE: No. 8 COPPER CONDUCTOR CABLE SEE NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
SIZE RECOMMENDATIONS.
COMMANDER 400