When paralleling machines in order to combine their outputs, all units must be operated in the
SIMULTANEOUS WELDING AND AUXIL- IARY POWER LOADS
It must be noted that the above auxiliary power ratings are with no welding load.
Simultaneous welding and power loads are specified in table B.4.
AUXILIARY POWER OPERATION
Start the engine and set the IDLER control switch to the desired operating mode. Full power is available regardless of the welding control settings, if no weld- ing current is being drawn.
The auxiliary power of the AIR VANTAGE® 500 con- sists of two 15Amp 240VAC single phase receptacles.
The auxiliary power receptacles should only be used with three wire grounded type plugs or approved dou- ble insulated tools with two wire plugs.
The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle.
TABLE B.4 AIR VANTAGE® 500 SIMULTANEOUS WELDING AND POWER LOADS
WELD AMPS 0 100 200 250 300 400 500
PLUS
1PHASE
WATTS AMPS
7,200 30
7,200 30
7,200 30
7,200 30
7,200 30
5,600 | 23 |
0 | 0 |
TABLE B.5
AIR VANTAGE® 500 CUMMINS Extension Cord Length Recommendations (Use the shortest length extension cord possible sized per the following table.)
Current | Voltage | Load | Maximum Allowable Cord Length in ft. (m) for Conductor Size | |
(Amps) | (Volts) | (Watts) | 14AWG 2.52mm | 12AWG 4.02mm 10AWG 6.02mm 8AWG 10.02mm 6AWG 16.02mm 4AWG 25.02mm |
15 | 240 | 3600 | 60 | (18) | 75 | (23) | 150 | 46 | 225 | (69) | 350 | 107 | 600 | (183) |
Conductor size is based on maximum 2.0% voltage drop.
AIR VANTAGE® 500 CUMMINS