Bryant 581C024--060, 581B036--072 installation instructions Unit Size 581C

Page 12

581B,C

Table 2 — Physical Data 581C (cont)

UNIT SIZE 581C

 

024

036

048

060

FURNACE SECTION

 

 

 

 

 

Rollout Switch Cutout Temp (F)†

 

195

195

195

195

Burner Orifice Diameter (in. ...drill size)**

 

 

 

 

 

Natural Gas —Std

071/072

.113...33

.113...33

.113...33

.113...33

 

114/115

.113...33

.113...33

.113...33

.113...33

 

149/150

.129...30

.129...30

.129...30

 

060N

.102...38

.102...38

.102...38

 

090N

.102...38

.102...38

.102...38

 

120N

.116...32

.116...32

Propane —Alt††

071/072

.089...43

.089...43

.089...43

.089...43

 

114115

.089...43

.089...43

.089...43

.089...43

 

149/150

.102...38

.102...38

.104...39

 

060N

.082...45

.082...45

.082...45

 

090N

.082...45

.082...45

.082...45

Thermostat Heat Anticipator Setting (amps)

120N

.094...42

.094...42

 

 

 

 

 

208/230/460 v

 

 

 

 

 

First Stage

 

.14

.14

.14

.14

Second Stage

 

.14

.14

.14

.14

Gas Input (Btuh)

 

 

 

 

 

First Stage/Second Stage (3---phase units)

072

50,000/ 72,000

50,000/ 72,000

50,000/ 72,000

50,000/ 72,000

 

115

82,000/115,000

82,000/115,000

82,000/115,000

82,000/115,000

 

150

120,000/150,000

120,000/150,000

120,000/150,000

 

071II

—/72,000

—/72,000

—/72,000

 

114II

—/115,000

—/115,000

—/115,000

 

149II

—/150,000

—/150,000

 

060N***

—/ 60,000

—/60,000

—/60,000

 

090N***

—/ 90,000

—/90,000

—/90,000

 

120N***

—/120,000

—/120,000

Efficiency (Steady State) (%)

072

82

82

82

82

 

115

80

81

81

81

 

150

80

80

80

 

071

82

82

82

 

114

80

81

81

 

149

80

80

 

060N

80

80

80

 

090N

80

80

80

 

120N

80

80

Temperature Rise Range

072

15---45

15---45

15---45

15---45

 

115

55---85

35---65

35---65

35---65

 

150

50---80

50---80

50---80

 

071

15---45

15---45

15---45

 

114

55---85

35---65

35---65

 

149

50---80

50---80

 

060N

20---50

20---50

20---50

 

090N

30---60

30---60

30---60

Manifold Pressure (in. wg)

120N

40---70

40---70

 

 

 

 

 

Natural Gas —Std

 

3.5

3.5

3.5

3.5

Propane —Alt††

 

3.5

3.5

3.5

3.5

Maximum Static Pressure (in. wg)

 

1.0

1.0

1.0

1.0

Field Gas Connection Size (in.)

 

1/2

1/2

1/2

1/2

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

Standard Compressor Internal Relief

450

±

50

 

Cutout

428

 

 

Reset (Auto.)

320

 

 

LOSS-OF-CHARGE SWITCH/LOW-PRESSURE

 

 

 

 

(Liquid Line) (psig)

 

 

 

 

Cutout

7

±

3

 

Reset (Auto.)

22

±

5

 

FREEZE PROTECTION THERMOSTAT

 

 

 

 

Opens (F)

30

±

5

 

Closes (F)

45

±

5

 

OUTDOOR-AIR INLET SCREENS

Cleanable. Screen quantity and size varies with option selected.

RETURN-AIR FILTERS

Throwaway

Quantity...Size (in.)

2...16 x 25 x 2

 

 

4...16 x 16 x 2

LEGEND

removed and the units will no longer be classified as Low NOx units.

Bhp — Brake Horsepower

ll Three-phase standard models have heating inputs as shown. Single-phase stan-

 

dard models have one-stage heating with heating input values.

**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000 Btuh

***California compliant three-phase models.

heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh

†††California SCAQMD compliant low NOx models have combustion products that are

Heat input units have 3 burners.

controlled to 40 nanograms per joule or less.

††A propane kit is available as an accessory. Kit may be used at elevations as high as

 

2000 ft. If a propane kit is used with Low NOx units, the Low NOx baffle must be

 

12

Image 12
Contents Installation Instructions Install External Trap for Condensate Drain Provide Unit SupportField Fabricate Ductwork Rig and Place UnitRoof Curb Details Install Flue Hood Install Gas PipingRoof Curb Alignment 581B 036-072 Base Unit Dimensions 581C 024-060 Base Unit Dimensions Field Power Supply Field Control WiringHeat Anticipator Settings Make Electrical ConnectionsPhysical Data 581B Base Unit 581BUnit Size 581B Physical Data 581C Base Unit 581CUnit Size 581C Power Wiring Connections Electrical Data 581C 581C024---060Electrical Data 581B Adjust Factory-Installed Options AssemblyPerfect Humidity Adaptive Dehumidification System Manual Outdoor DamperTypical Perfect Humidity t Adaptive Dehumidification System Outdoor-Air Damper With Hood Attached Supply Air Temperature SAT Sensor Supply Air Sensor Temperature Resistance ValuesTemperature F Outdoor Air Lockout SensorEconomi$er IV Control Modes Outdoor Dry Bulb ChangeoverEconomi$er IV Sensor Usage Differential Dry Bulb ControlEconoMi$er IV Wiring Exhaust Set Point Adjustment Minimum Position ControlDamper Movement ThermostatsDemand Controlled Ventilation DCV Enthalpy Changeover Set Points Dehumidification of Fresh Air with DCV Control Belt Drive MotorsCO2Sensor Standard Settings Belt Drive Motor Mounting581B Fan Rpm at Motor Pulley Setting With High-Static Motor Accessory Static PressureEvaporator-Fan Motor Data Standard Motor Evaporator-Fan Motor Data High-Static Motors581B Outdoor Sound Power Total Unit 581C Outdoor Sound Power Total UnitARI Octavebands Rating Unit Weighted ARI Octave Bands Unit RatingRpm Bhp 11001200 1300Rpm Bhp Watts Rpm Bhp Watts Watts Rpm Bhp 12001600 1700Rpm Bhp Watts 1500 1642 2333 1704Watts Rpm Bhp 1800 26002700 2800Bhp Watts Rpm 2700 2800 2900 3000Bhp 600 Bhp Watts 900 Watts RpmWatts Rpm Bhp 900 1700 1800 1900 2000 Bhp Watts1900 2000 2100 2200 2300 2400 2500 800 350 904 438 999 535 1087 640 1169 753 913 569 913 569 1010 715 Internal Wiring Refrigerant Service PortsUnit Preparation Gas PipingCompressor Rotation CoolingMain Burners Safety Relief HeatingVentilation Continuous Fan Operating SequenceSubcooling Mode Hot Gas Reheat ModeHeating Units With Economi$er Cleaning Evaporator CoilCondenser Coil One-Row CoilsCondenser-Fan Adjustment EconoMi$er IV AdjustmentHigh Pressure Switch Loss-of-Charge SwitchLow Charge Cooling Perfect Humidity System ChargingC06142 Flue Gas Passageways 581C 3 TON Charging Chart 581C 5 TON Charging Chart Limit Switch LED Error Code DescriptionRemoval and Replacement of Gas Train See Combustion-Air BlowerReplacement Parts OFM Unit Troubleshooting Economi$er IV TroubleshootingEconomi$er IV Troubleshooting Completion LED Error Code Service AnalysisSymptom Cause Remedy LED OFFHeating Service Analysis Problem Cause RemedyCooling Service Analysis EconoMi$er IV Input/Output Logic Inputs OutputsPreliminary Information Catalog No. II581B---C---36---1