581B,C
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.: |
| SERIAL NO.: |
| ||
DATE: |
|
| TECHNICIAN: |
|
II.
j VERIFY THAT JOBSITE VOLTAGE AGREES WITH VOLTAGE LISTED ON RATING PLATE j VERIFY THAT ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNIT
j REMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS j VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS j CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
j CHECK GAS PIPING FOR LEAKS
j CHECK THAT RETURN (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE j VERIFY THAT UNIT INSTALLATION IS LEVEL
j CHECK FAN WHEELS AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
j CHECK TO ENSURE THAT ELECTRICAL WIRING IS NOT IN CONTACT WITH REFRIGERANT LINES OR SHARP METAL EDGES
j CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS
III.START-UP
ELECTRICAL
SUPPLY VOLTAGE | |||
COMPRESSOR AMPS | L1 | L2 | L3 |
L1 | L2 | L3 |
TEMPERATURES |
|
|
|
| DB |
| |
| DB | WB | |
COOLING SUPPLY AIR |
| DB |
|
HEATING SUPPLY AIR |
| DB |
|
PRESSURES (Cooling Mode) |
|
|
|
GAS INLET PRESSURE |
| IN.WG |
|
GAS MANIFOLD PRESSURE |
| IN.WG (HIGH FIRE) | |
REFRIGERANT SUCTION |
| PSIG |
|
REFRIGERANT DISCHARGE |
| PSIG |
|
jVERIFY THAT
jVERIFY THAT