Bryant 581C024--060 Adjust Factory-Installed Options, Manual Outdoor Damper, Assembly

Page 16

Step 8 Adjust Factory-Installed Options

Perfect HumidityAdaptive Dehumidification

System

Perfect Humidity system operation can be controlled by field installation of a Bryant-approved humidistat. (See Fig. 15.)

NOTE: A light commercial Thermidistatdevice (Fig. 16) can be used instead of the humidistat if desired. The Thermidistat device includes a thermostat and a humidistat. The humidistat is normally used in applications where a temperature sensor is already provided.

581B,C

% RELATIVE HUMIDITY

C06358

Fig. 15 ---Accessory Field-Installed Humidistat

C06359

Fig. 16 ---Light Commercial Thermidistat Device

To install the humidistat:

1.Route humidistat cable through hole provided in unit control box.

2.Some models may be equipped with a raceway built into the corner post located on the left side of control box (See Fig. 14). This raceway provides the required clearance between high-voltage and low voltage wiring. For models without a raceway, ensure to provide the NEC required clearance between the high-voltage and low-voltage wiring.

3.Use a wire nut to connect humidistat cable into low- voltage wiring as shown in Fig. 17.

To install Thermidistat device:

1.Route Thermidistat cable through hole provided in unit control box.

2.Some models may be equipped with a raceway built into the corner post located on the left side of control box (See Fig. 14). This raceway provides the required clearance between high-voltage and low voltage wiring. For models without a raceway, ensure to provide the NEC required clearance between the high-voltage and low-voltage wiring.

3.A field-supplied relay must be installed between the Thermidistat and the Humidi-Mizer circuit (recommended relay: HN61KK324). (See Fig. 18.) The relay coil is connected between the DEHUM output and C (common) of the unit. The relay controls thePerfect Humidity solenoid valve and must be wired between the Perfect Humidity fuse and the low-pressure switch. Refer to the installation instructions included with the Bryant Light Commercial Thermidistat device for more information.

Manual Outdoor Damper

The outdoor-air hood and screen are attached to the basepan at the bottom of the unit for shipping.

Assembly:

1.Determine quantity of ventilation required for building. Record amount for use in Step 8.

2.Remove and save outdoor air opening panel and screws. (See Fig. 19.)

3.Remove evaporator coil access panel. Separate hood and screen from basepan by removing the 4 screws securing them. Save all screws.

4.Replace evaporator coil access panel.

5.Place hood on front of outdoor air opening panel. See Fig. 20 for hood details. Secure top of hood with the 4 screws removed in Step 3. (See Fig. 21.)

6.Remove and save 6 screws (3 on each side) from sides of the manual outdoor-air damper.

7.Align screw holes on hood with screw holes on side of manual outdoor-air damper. (See Fig. 28 and 21.) Secure hood with 6 screws from Step 6.

8.Adjust minimum position setting of the damper blade by adjusting the manual outdoor-air adjustment screws on the front of the damper blade. (See Fig. 19.) Slide blade vertically until it is in the appropriate position determined by Fig. 22. Tighten screws.

9.Remove and save screws currently on sides of hood. Insert screen. Secure screen to hood using the screws. (See Fig. 21.)

Convenience Outlet

An optional convenience outlet provides power for rooftop use. For maintenance personnel safety, the convenience outlet power is off when the unit disconnect is off. Adjacent unit outlets may be used for service tools.

16

Image 16
Contents Installation Instructions Install External Trap for Condensate Drain Provide Unit SupportField Fabricate Ductwork Rig and Place UnitRoof Curb Details Install Flue Hood Install Gas PipingRoof Curb Alignment 581B 036-072 Base Unit Dimensions 581C 024-060 Base Unit Dimensions Field Power Supply Field Control WiringHeat Anticipator Settings Make Electrical ConnectionsPhysical Data 581B Base Unit 581BUnit Size 581B Physical Data 581C Base Unit 581CUnit Size 581C Power Wiring Connections Electrical Data 581C 581C024---060Electrical Data 581B Adjust Factory-Installed Options AssemblyPerfect Humidity Adaptive Dehumidification System Manual Outdoor DamperTypical Perfect Humidity t Adaptive Dehumidification System Outdoor-Air Damper With Hood Attached Supply Air Temperature SAT Sensor Supply Air Sensor Temperature Resistance ValuesTemperature F Outdoor Air Lockout SensorEconomi$er IV Control Modes Outdoor Dry Bulb ChangeoverEconomi$er IV Sensor Usage Differential Dry Bulb ControlEconoMi$er IV Wiring Exhaust Set Point Adjustment Minimum Position ControlThermostats Damper MovementDemand Controlled Ventilation DCV Enthalpy Changeover Set Points Dehumidification of Fresh Air with DCV Control Belt Drive MotorsCO2Sensor Standard Settings Belt Drive Motor Mounting581B Fan Rpm at Motor Pulley Setting With High-Static Motor Accessory Static PressureEvaporator-Fan Motor Data Standard Motor Evaporator-Fan Motor Data High-Static Motors581B Outdoor Sound Power Total Unit 581C Outdoor Sound Power Total UnitARI Octavebands Rating Unit Weighted ARI Octave Bands Unit RatingRpm Bhp 11001200 1300Rpm Bhp Watts Rpm Bhp Watts Watts Rpm Bhp 12001600 1700Rpm Bhp Watts 1500 1642 2333 1704Watts Rpm Bhp 1800 26002700 28002700 2800 2900 3000 Bhp Watts RpmBhp 600 Watts Rpm Bhp Watts 900Watts Rpm Bhp 900 1700 1800 1900 2000 Bhp Watts1900 2000 2100 2200 2300 2400 2500 800 350 904 438 999 535 1087 640 1169 753 913 569 913 569 1010 715 Internal Wiring Refrigerant Service PortsUnit Preparation Gas PipingCooling Compressor RotationMain Burners Safety Relief HeatingVentilation Continuous Fan Operating SequenceHot Gas Reheat Mode Subcooling ModeHeating Units With Economi$er Cleaning Evaporator CoilCondenser Coil One-Row CoilsCondenser-Fan Adjustment EconoMi$er IV AdjustmentHigh Pressure Switch Loss-of-Charge SwitchLow Charge Cooling Perfect Humidity System ChargingC06142 Flue Gas Passageways 581C 3 TON Charging Chart 581C 5 TON Charging Chart Limit Switch LED Error Code DescriptionRemoval and Replacement of Gas Train See Combustion-Air BlowerReplacement Parts OFM Unit Troubleshooting Economi$er IV TroubleshootingEconomi$er IV Troubleshooting Completion LED Error Code Service AnalysisSymptom Cause Remedy LED OFFHeating Service Analysis Problem Cause RemedyCooling Service Analysis EconoMi$er IV Input/Output Logic Inputs OutputsPreliminary Information Catalog No. II581B---C---36---1