Bryant 581C024--060, 581B036--072 installation instructions Cooling Service Analysis

Page 58

581B,C

Table 43—Cooling Service Analysis

PROBLEM

CAUSE

REMEDY

Compressor and Condenser Fan

Power failure.

Call power company.

Will Not Start.

 

 

Fuse blown or circuit breaker tripped.

Replace fuse or reset circuit breaker.

 

Defective thermostat, contactor, transformer, or

Replace component.

 

control relay.

 

 

Insufficient line voltage.

Determine cause and correct.

 

Incorrect or faulty wiring.

Check wiring diagram and rewire correctly.

 

Thermostat setting too high.

Lower thermostat setting below room tempera-

 

 

ture.

Compressor Will Not Start

Faulty wiring or loose connections in compres-

Check wiring and repair or replace.

But Condenser Fan Runs.

sor circuit.

 

 

Compressor motor burned out, seized, or in-

Determine cause. Replace compressor.

 

ternal overload open.

 

 

Defective run/start capacitor, overload, start

Determine cause and replace.

 

relay.

 

 

One leg of 3-phase power dead.

Replace fuse or reset circuit breaker. Determine

 

 

cause.

Compressor Cycles (Other Than

Refrigerant overcharge or undercharge.

Recover refrigerant, evacuate system, and re-

Normally Satisfying Thermostat).

 

charge to nameplate.

 

Defective compressor.

Replace and determine cause.

 

Insufficient line voltage.

Determine cause and correct.

 

Blocked condenser.

Determine cause and correct.

 

Defective run/start capacitor, overload, or start

Determine cause and replace.

 

relay.

 

 

Defective thermostat.

Replace thermostat.

 

Faulty condenser-fan motor or capacitor.

Replace.

 

Restriction in refrigerant system.

Locate restriction and remove.

Compressor Operates Continuously.

Dirty air filter.

Replace filter.

 

Unit undersized for load.

Decrease load or increase unit size.

 

Thermostat set too low.

Reset thermostat.

 

Low refrigerant charge.

Locate leak, repair, and recharge.

 

Leaking valves in compressor.

Replace compressor.

 

Air in system.

Recover refrigerant, evacuate system, and re-

 

 

charge.

 

Condenser coil dirty or restricted.

Clean coil or remove restriction.

Excessive Head Pressure.

Dirty air filter.

Replace filter.

 

Dirty condenser coil.

Clean coil.

 

Refrigerant overcharged.

Recover excess refrigerant.

 

Air in system.

Recover refrigerant, evacuate system, and re-

 

 

charge.

 

Condenser air restricted or air short-cycling.

Determine cause and correct.

Head Pressure Too Low.

Low refrigerant charge.

Check for leaks, repair, and recharge.

 

Compressor valves leaking.

Replace compressor.

 

Restriction in liquid tube.

Remove restriction.

Excessive Suction Pressure.

High heat load.

Check for source and eliminate.

 

Compressor valves leaking.

Replace compressor.

 

Refrigerant overcharged.

Recover excess refrigerant.

Suction Pressure Too Low.

Dirty air filter.

Replace filter.

 

Low refrigerant charge.

Check for leaks, repair, and recharge.

 

Metering device or low side restricted.

Remove source of restriction.

 

Insufficient evaporator airflow.

Increase air quantity. Check filter and replace if

 

 

necessary.

 

Temperature too low in conditioned area.

Reset thermostat.

 

Outdoor ambient below 25 F.

Install low-ambient kit.

Evaporator Fan Will Not Shut Off.

Time off delay not finished.

Wait for 30-second off delay.

58

Image 58
Contents Installation Instructions Field Fabricate Ductwork Install External Trap for Condensate DrainProvide Unit Support Rig and Place UnitRoof Curb Details Install Flue Hood Install Gas PipingRoof Curb Alignment 581B 036-072 Base Unit Dimensions 581C 024-060 Base Unit Dimensions Heat Anticipator Settings Field Power SupplyField Control Wiring Make Electrical ConnectionsPhysical Data 581B Base Unit 581BUnit Size 581B Physical Data 581C Base Unit 581CUnit Size 581C Power Wiring Connections Electrical Data 581C 581C024---060Electrical Data 581B Perfect Humidity Adaptive Dehumidification System Adjust Factory-Installed OptionsAssembly Manual Outdoor DamperTypical Perfect Humidity t Adaptive Dehumidification System Outdoor-Air Damper With Hood Attached Temperature F Supply Air Temperature SAT SensorSupply Air Sensor Temperature Resistance Values Outdoor Air Lockout SensorEconomi$er IV Sensor Usage Economi$er IV Control ModesOutdoor Dry Bulb Changeover Differential Dry Bulb ControlEconoMi$er IV Wiring Exhaust Set Point Adjustment Minimum Position ControlThermostats Damper MovementDemand Controlled Ventilation DCV Enthalpy Changeover Set Points Dehumidification of Fresh Air with DCV Control Belt Drive MotorsCO2Sensor Standard Settings Belt Drive Motor MountingEvaporator-Fan Motor Data Standard Motor 581B Fan Rpm at Motor Pulley Setting With High-Static MotorAccessory Static Pressure Evaporator-Fan Motor Data High-Static MotorsARI Octavebands Rating Unit Weighted 581B Outdoor Sound Power Total Unit581C Outdoor Sound Power Total Unit ARI Octave Bands Unit Rating1200 Rpm Bhp1100 1300Rpm Bhp Watts 1600 Rpm Bhp WattsWatts Rpm Bhp 1200 1700Rpm Bhp Watts 1500 1642 2333 17042700 Watts Rpm Bhp 18002600 28002700 2800 2900 3000 Bhp Watts RpmBhp 600 Watts Rpm Bhp Watts 900Watts Rpm Bhp 900 1700 1800 1900 2000 Bhp Watts1900 2000 2100 2200 2300 2400 2500 800 350 904 438 999 535 1087 640 1169 753 913 569 913 569 1010 715 Unit Preparation Internal WiringRefrigerant Service Ports Gas PipingCooling Compressor RotationMain Burners Ventilation Continuous Fan Safety ReliefHeating Operating SequenceHot Gas Reheat Mode Subcooling ModeHeating Units With Economi$er Condenser Coil CleaningEvaporator Coil One-Row CoilsHigh Pressure Switch Condenser-Fan AdjustmentEconoMi$er IV Adjustment Loss-of-Charge SwitchLow Charge Cooling Perfect Humidity System ChargingC06142 Flue Gas Passageways 581C 3 TON Charging Chart 581C 5 TON Charging Chart Removal and Replacement of Gas Train See Limit SwitchLED Error Code Description Combustion-Air BlowerReplacement Parts OFM Unit Troubleshooting Economi$er IV TroubleshootingSymptom Cause Remedy Economi$er IV Troubleshooting CompletionLED Error Code Service Analysis LED OFFHeating Service Analysis Problem Cause RemedyCooling Service Analysis EconoMi$er IV Input/Output Logic Inputs OutputsPreliminary Information Catalog No. II581B---C---36---1