Bryant 581B036--072, 581C024--060 Cleaning, Evaporator Coil, Condenser Coil, One-Row Coils

Page 45

Table 37—Perfect Humidity Adaptive Dehumidification System Sequence of Operation and

System Response — Single Compressor Unit (581C 024-060, 581B 036-072)

THERMOSTAT INPUT

ECONOMIZER FUNCTION

 

581B,C UNIT OPERATION

 

 

 

 

 

 

 

 

H

Y1

Y2

OAT. < Economizer Set Point

Economizer

Comp. 1

Subcooling Mode

Hot Gas Reheat Mode

 

 

 

 

 

 

 

 

Off

 

Normal Operation

 

On

On

On

No

Off

On

Yes

No

On

On

Off

No

Off

On

Yes

No

On

On

On

Yes

On

On

Yes

No

On

On

Off

Yes

On

On

No

Yes

On

Off

Off

No

Off

On

No

Yes

NOTE: On a thermostat call for W1, all cooling and dehumidification will be off.

LEGEND

OAT --- Outdoor Air Temperature

The net effect of the rooftop when in hot gas reheat mode is to provide nearly all latent capacity removal from the space when sensible loads diminish (when outdoor temperature conditions are moderate). When in hot gas reheat mode, the unit will operate to provide mostly latent capacity and extremely low sensible heat ratio capability.

Similar to the subcooling mode of operation, hot gas reheat mode operates only when the outside air temperature is warmer than 40_F. Below this temperature, a factory installed outside air temperature switch will lockout this mode of operation.

SERVICE

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could cause personal injury or death.

When sevicing unit, shut off all electrical power to unit and install lockout tag.

Step 1 Cleaning

Inspect unit interior at the beginning of heating and cooling season and as operating conditions require.

Evaporator Coil

1.Turn unit power off, tag disconnect. Remove evaporator coil access panel.

2.If economizer or two-position damper is installed, remove economizer by disconnecting Molex plug and removing mounting screws.

3.Slide filters out of unit.

4.Clean coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results, back-flush toward return-air section to remove foreign material. Flush condensate pan after completion.

5.Reinstall economizer and filters.

6.Reconnect wiring.

7.Replace access panels.

Condenser Coil

Inspect coil monthly. Clean condenser coil annually, and as required by location and outdoor air conditions.

One-Row Coils

Wash coil with commercial coil cleaner. It is not necessary to remove top panel.

2-Row Coils

Clean coil as follows:

1.Turn off unit power, tag disconnect.

2.Remove top panel screws on condenser end of unit.

3.Remove condenser coil corner post. (See Fig. 47.) To hold top panel open, place coil corner post between top panel and center post. (See Fig. 48.)

C06044

Fig. 47 ---Cleaning Condenser Coil

C06045

Fig. 48 ---Propping Up Top Panel

581B,C

45

Image 45
Contents Installation Instructions Provide Unit Support Install External Trap for Condensate DrainField Fabricate Ductwork Rig and Place UnitRoof Curb Details Install Gas Piping Install Flue HoodRoof Curb Alignment 581B 036-072 Base Unit Dimensions 581C 024-060 Base Unit Dimensions Field Control Wiring Field Power SupplyHeat Anticipator Settings Make Electrical ConnectionsBase Unit 581B Physical Data 581BUnit Size 581B Base Unit 581C Physical Data 581CUnit Size 581C Power Wiring Connections 581C024---060 Electrical Data 581CElectrical Data 581B Assembly Adjust Factory-Installed OptionsPerfect Humidity Adaptive Dehumidification System Manual Outdoor DamperTypical Perfect Humidity t Adaptive Dehumidification System Outdoor-Air Damper With Hood Attached Supply Air Sensor Temperature Resistance Values Supply Air Temperature SAT SensorTemperature F Outdoor Air Lockout SensorOutdoor Dry Bulb Changeover Economi$er IV Control ModesEconomi$er IV Sensor Usage Differential Dry Bulb ControlEconoMi$er IV Wiring Minimum Position Control Exhaust Set Point AdjustmentDamper Movement ThermostatsDemand Controlled Ventilation DCV Enthalpy Changeover Set Points Belt Drive Motors Dehumidification of Fresh Air with DCV ControlBelt Drive Motor Mounting CO2Sensor Standard SettingsAccessory Static Pressure 581B Fan Rpm at Motor Pulley Setting With High-Static MotorEvaporator-Fan Motor Data Standard Motor Evaporator-Fan Motor Data High-Static Motors581C Outdoor Sound Power Total Unit 581B Outdoor Sound Power Total UnitARI Octavebands Rating Unit Weighted ARI Octave Bands Unit Rating1100 Rpm Bhp1200 1300Rpm Bhp Watts Watts Rpm Bhp 1200 Rpm Bhp Watts1600 17001642 2333 1704 Rpm Bhp Watts 15002600 Watts Rpm Bhp 18002700 2800Bhp Watts Rpm 2700 2800 2900 3000Bhp 600 Bhp Watts 900 Watts RpmWatts Rpm Bhp 900 Bhp Watts 1700 1800 1900 20001900 2000 2100 2200 2300 2400 2500 800 350 904 438 999 535 1087 640 1169 753 913 569 913 569 1010 715 Refrigerant Service Ports Internal WiringUnit Preparation Gas PipingCompressor Rotation CoolingMain Burners Heating Safety ReliefVentilation Continuous Fan Operating SequenceSubcooling Mode Hot Gas Reheat ModeHeating Units With Economi$er Evaporator Coil CleaningCondenser Coil One-Row CoilsEconoMi$er IV Adjustment Condenser-Fan AdjustmentHigh Pressure Switch Loss-of-Charge SwitchPerfect Humidity System Charging Low Charge CoolingC06142 Flue Gas Passageways 581C 3 TON Charging Chart 581C 5 TON Charging Chart LED Error Code Description Limit SwitchRemoval and Replacement of Gas Train See Combustion-Air BlowerReplacement Parts OFM Economi$er IV Troubleshooting Unit TroubleshootingLED Error Code Service Analysis Economi$er IV Troubleshooting CompletionSymptom Cause Remedy LED OFFProblem Cause Remedy Heating Service AnalysisCooling Service Analysis Inputs Outputs EconoMi$er IV Input/Output LogicCatalog No. II581B---C---36---1 Preliminary Information