Table
System Response — Single Compressor Unit (581C
THERMOSTAT INPUT | ECONOMIZER FUNCTION |
| 581B,C UNIT OPERATION | ||||
|
|
|
|
|
|
|
|
H | Y1 | Y2 | OAT. < Economizer Set Point | Economizer | Comp. 1 | Subcooling Mode | Hot Gas Reheat Mode |
|
|
|
|
|
|
|
|
Off | — | — |
| Normal Operation |
| ||
On | On | On | No | Off | On | Yes | No |
On | On | Off | No | Off | On | Yes | No |
On | On | On | Yes | On | On | Yes | No |
On | On | Off | Yes | On | On | No | Yes |
On | Off | Off | No | Off | On | No | Yes |
NOTE: On a thermostat call for W1, all cooling and dehumidification will be off.
LEGEND
OAT
The net effect of the rooftop when in hot gas reheat mode is to provide nearly all latent capacity removal from the space when sensible loads diminish (when outdoor temperature conditions are moderate). When in hot gas reheat mode, the unit will operate to provide mostly latent capacity and extremely low sensible heat ratio capability.
Similar to the subcooling mode of operation, hot gas reheat mode operates only when the outside air temperature is warmer than 40_F. Below this temperature, a factory installed outside air temperature switch will lockout this mode of operation.
SERVICE
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
When sevicing unit, shut off all electrical power to unit and install lockout tag.
Step 1 —Cleaning
Inspect unit interior at the beginning of heating and cooling season and as operating conditions require.
Evaporator Coil
1.Turn unit power off, tag disconnect. Remove evaporator coil access panel.
2.If economizer or
3.Slide filters out of unit.
4.Clean coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results,
5.Reinstall economizer and filters.
6.Reconnect wiring.
7.Replace access panels.
Condenser Coil
Inspect coil monthly. Clean condenser coil annually, and as required by location and outdoor air conditions.
One-Row Coils
Wash coil with commercial coil cleaner. It is not necessary to remove top panel.
2-Row Coils
Clean coil as follows:
1.Turn off unit power, tag disconnect.
2.Remove top panel screws on condenser end of unit.
3.Remove condenser coil corner post. (See Fig. 47.) To hold top panel open, place coil corner post between top panel and center post. (See Fig. 48.)
C06044
Fig. 47 --- Cleaning Condenser Coil
C06045
Fig. 48 --- Propping Up Top Panel
581B,C
45