Bryant 581B036--072, 581C024--060 581B Fan Rpm at Motor Pulley Setting With High-Static Motor

Page 27

Table 8—581B and 581C Fan Rpm at Motor Pulley Setting With Standard Motor*

UNIT

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

0

1/

1

11/

2

21/

3

31/

4

41/

5

51/

6

 

 

2

 

2

 

2

 

2

 

2

 

2

 

024

936

906

876

846

816

786

756

726

696

666

639

036

1044

1008

971

935

898

862

826

789

753

716

680

048

1185

1144

1102

1061

1019

978

936

895

853

812

770

060

1460

1425

1389

1354

1318

1283

1248

1212

1177

1141

1106

1070

1035

072

1585

1538

1492

1445

1399

1352

1305

1259

1212

1166

1119

*Approximate fan rpm shown (standard motor/drive).

Table 9—581B Fan Rpm at Motor Pulley Setting With High-Static Motor*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

 

0

1/

1

11/

2

 

21/

3

31/

 

4

41/

5

51/

6

 

 

2

 

2

 

 

2

 

2

 

 

2

 

2

 

036

1455

1423

1392

1360

1328

 

1297

1265

1233

 

1202

1170

1138

1107

1075

048

1455

1423

1392

1360

1328

 

1297

1265

1233

 

1202

1170

1138

1107

1075

060

1685

1589

1557

1525

1493

 

1460

1428

1396

 

1364

1332

1300

072

1685

1589

1557

1525

1493

 

1460

1428

1396

 

1364

1332

1300

*Approximate fan rpm shown (high-static motor/drive).

Table 10—Evaporator-Fan Motor Data — Standard Motor

UNIT

UNIT

MAXIMUM

MAXIMUM

 

MAXIMUM

581B

UNIT VOLTAGE

PHASE

CONTINUOUS BHP*

OPERATING WATTS*

AMP DRAW

581C

 

 

 

 

 

 

 

 

 

 

 

 

024

Single

0.58

580

208/230

2.0

 

Single

1.20

1000

208/230

4.9

036

 

 

 

208/230

4.9

Three

1.20

1000

460

2.2

 

 

 

 

 

575

2.2

 

Single

1.20

1000

208/230

4.9

048

 

 

 

208/230

4.9

Three

1.20

1000

460

2.2

 

 

 

 

 

575

2.2

 

Single

1.30

1455

208/230

7.0

060

 

 

 

208/230

6.7

Three

2.40

2120

460

3.0

 

 

 

 

 

575

3.0

072

 

 

 

208/230

6.7

Three

2.40

2120

460

3.0

 

 

 

 

575

3.0

LEGEND

Bhp — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

581B,C

Table 11—Accessory Static Pressure

 

 

 

 

 

 

 

 

 

 

 

 

COMPONENT

 

 

 

 

CFM

 

 

 

 

 

600

800

1000

1250

1500

1750

2000

2250

2500

2750

3000

 

Vertical EconoMi$er IV

0.010

0.020

0.035

0.045

0.065

0.080

0.120

0.145

0.175

0.220

0.255

Horizontal EconoMi$er IV

0.100

0.125

0.150

0.180

0.225

0.275

Table 12—Evaporator-Fan Motor Data — High-Static Motors

UNIT

UNIT

MAXIMUM

MAXIMUM

UNIT VOLTAGE

MAXIMUM

581B

PHASE

CONTINUOUS BHP*

OPERATING WATTS*

AMP DRAW

 

 

 

 

 

 

 

036

 

 

 

208/230

6.7

Three

2.40

2120

460

3.0

 

 

 

 

575

3.0

048

 

 

 

208/230

6.7

Three

2.40

2120

460

3.0

 

 

 

 

575

3.0

060

 

 

 

208/230

8.6

Three

2.90

2615

460

3.9

 

 

 

 

575

3.9

072

 

 

 

208/230

8.6

Three

2.90

2615

460

3.9

 

 

 

 

575

3.9

LEGEND

Bhp — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

27

Image 27
Contents Installation Instructions Rig and Place Unit Install External Trap for Condensate DrainProvide Unit Support Field Fabricate DuctworkRoof Curb Details Install Gas Piping Install Flue HoodRoof Curb Alignment 581B 036-072 Base Unit Dimensions 581C 024-060 Base Unit Dimensions Make Electrical Connections Field Power SupplyField Control Wiring Heat Anticipator SettingsBase Unit 581B Physical Data 581BUnit Size 581B Base Unit 581C Physical Data 581CUnit Size 581C Power Wiring Connections 581C024---060 Electrical Data 581CElectrical Data 581B Manual Outdoor Damper Adjust Factory-Installed OptionsAssembly Perfect Humidity Adaptive Dehumidification SystemTypical Perfect Humidity t Adaptive Dehumidification System Outdoor-Air Damper With Hood Attached Outdoor Air Lockout Sensor Supply Air Temperature SAT SensorSupply Air Sensor Temperature Resistance Values Temperature FDifferential Dry Bulb Control Economi$er IV Control ModesOutdoor Dry Bulb Changeover Economi$er IV Sensor UsageEconoMi$er IV Wiring Minimum Position Control Exhaust Set Point AdjustmentDamper Movement ThermostatsDemand Controlled Ventilation DCV Enthalpy Changeover Set Points Belt Drive Motors Dehumidification of Fresh Air with DCV ControlBelt Drive Motor Mounting CO2Sensor Standard SettingsEvaporator-Fan Motor Data High-Static Motors 581B Fan Rpm at Motor Pulley Setting With High-Static MotorAccessory Static Pressure Evaporator-Fan Motor Data Standard MotorARI Octave Bands Unit Rating 581B Outdoor Sound Power Total Unit581C Outdoor Sound Power Total Unit ARI Octavebands Rating Unit Weighted1300 Rpm Bhp1100 1200Rpm Bhp Watts 1700 Rpm Bhp WattsWatts Rpm Bhp 1200 16001642 2333 1704 Rpm Bhp Watts 15002800 Watts Rpm Bhp 18002600 2700Bhp Watts Rpm 2700 2800 2900 3000Bhp 600 Bhp Watts 900 Watts RpmWatts Rpm Bhp 900 Bhp Watts 1700 1800 1900 20001900 2000 2100 2200 2300 2400 2500 800 350 904 438 999 535 1087 640 1169 753 913 569 913 569 1010 715 Gas Piping Internal WiringRefrigerant Service Ports Unit PreparationCompressor Rotation CoolingMain Burners Operating Sequence Safety ReliefHeating Ventilation Continuous FanSubcooling Mode Hot Gas Reheat ModeHeating Units With Economi$er One-Row Coils CleaningEvaporator Coil Condenser CoilLoss-of-Charge Switch Condenser-Fan AdjustmentEconoMi$er IV Adjustment High Pressure SwitchPerfect Humidity System Charging Low Charge CoolingC06142 Flue Gas Passageways 581C 3 TON Charging Chart 581C 5 TON Charging Chart Combustion-Air Blower Limit SwitchLED Error Code Description Removal and Replacement of Gas Train SeeReplacement Parts OFM Economi$er IV Troubleshooting Unit TroubleshootingLED OFF Economi$er IV Troubleshooting CompletionLED Error Code Service Analysis Symptom Cause RemedyProblem Cause Remedy Heating Service AnalysisCooling Service Analysis Inputs Outputs EconoMi$er IV Input/Output LogicCatalog No. II581B---C---36---1 Preliminary Information