Bryant 581C024--060 Economi$er IV Troubleshooting Completion, LED Error Code Service Analysis

Page 56

Economi$er IV Troubleshooting Completion

This procedure is used to return the EconoMi$er IV to operation. No troubleshooting or testing is done by performing the following procedure.

1.Disconnect power at TR and TR1.

2.Set enthalpy potentiometer to previous setting.

3.Set DCV maximum position potentiometer to previous setting.

4.Set minimum position, DCV set point, and exhaust potentiometers to previous settings.

5.Remove 620-ohm resistor from terminals SR and +.

6.Remove 1.2 kilo-ohm checkout resistor from terminals SO and +. If used, reconnect sensor from terminals SO and +.

7.Remove jumper from TR to N.

8.Remove jumper from TR to 1.

9.Remove 5.6 kilo-ohm resistor from T and T1. Reconnect wires at T and T1.

10.Remove jumper from P to P1. Reconnect device at P and P1.

11.Apply power (24 vac) to terminals TR and TR1.

581B,C

Table 39—LED Error Code Service Analysis

SYMPTOM

CAUSE

REMEDY

Hardware Failure.

Loss of power to control module (IGC).

Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and

(LED OFF)

 

transformer. Units without a 24-v circuit breaker have an internal

 

 

overload in the 24-v transformer. If the overload trips, allow

 

 

10 minutes for automatic reset.

Fan ON/OFF Delay Modified

High limit switch opens during heat

Ensure unit is fired on rate and temperature rise is correct.

(LED/FLASH)

exchanger warm-up period before fan-on

 

delay expires.

 

 

Limit switch opens within three minutes

Ensure units’ external static pressure is within application guide-

 

after blower-off delay timing in Heating

lines.

 

mode.

 

Limit Switch Fault.

High temperature limit switch is open.

Check the operation of the indoor (evaporator) fan motor.

(LED 2 Flashes)

 

Ensure that the supply-air temperature rise is in accordance with

 

 

the range on the unit nameplate.

Flame Sense Fault.

The IGC sensed flame that should not be

Reset unit. If problem persists, replace control board.

(LED 3 Flashes)

present.

 

4 Consecutive Limit

Inadequate airflow to unit.

Check operation of indoor (evaporator) fan motor and that supply-air

Switch Faults.

 

temperature rise agrees with range on unit nameplate information.

(LED 4 Flashes)

 

 

Ignition Lockout.

Unit unsuccessfully attempted ignition for

Check ignitor and flame sensor electrode spacing, gaps, etc.

(LED 5 Flashes)

15 minutes.

Ensure that flame sense and ignition wires are properly

 

 

terminated. Verify that unit is obtaining proper amount of gas.

Induced-Draft Motor Fault.

IGC does not sense that induced-draft

Check for proper voltage. If motor is operating, check the

(LED 6 Flashes)

motor is operating.

speed sensor plug/IGC Terminal J2 connection. Proper

 

 

connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black.

Rollout Switch Fault.

Rollout switch has opened.

Rollout switch will automatically reset, but IGC will continue to

(LED 7 Flashes)

 

lock out unit. Check gas valve operation. Ensure that induced-

 

 

draft blower wheel is properly secured to motor shaft.

 

 

Reset unit at unit disconnect.

Internal Control Fault.

Microprocessor has sensed an error in the

If error code is not cleared by resetting unit power, replace the IGC.

(LED 8 Flashes)

software or hardware.

 

Temporary Software

Electrical interference is impeding the IGC

Reset 24-v to control board or turn thermostat off and then on. Fault

Lockout

software.

will automatically reset itself in one hour.

(LED 9 Flashes)

 

 

!CAUTION

COMPONENT DAMAGE HAZARD

Failure to follow this caution may result in component damage.

If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that may be present before handling new control board. The IGC is sensitive to static electricity and may be damaged if the necessary precautions are not taken.

LEGEND

IGC --- Integrated Gas Unit Controller

LED --- Light---Emitting Diode

IMPORTANT: Refer to heating troubleshooting for additional heating section troubleshooting information.

56

Image 56
Contents Installation Instructions Install External Trap for Condensate Drain Provide Unit SupportField Fabricate Ductwork Rig and Place UnitRoof Curb Details Install Flue Hood Install Gas PipingRoof Curb Alignment 581B 036-072 Base Unit Dimensions 581C 024-060 Base Unit Dimensions Field Power Supply Field Control WiringHeat Anticipator Settings Make Electrical ConnectionsPhysical Data 581B Base Unit 581BUnit Size 581B Physical Data 581C Base Unit 581CUnit Size 581C Power Wiring Connections Electrical Data 581C 581C024---060Electrical Data 581B Adjust Factory-Installed Options AssemblyPerfect Humidity Adaptive Dehumidification System Manual Outdoor DamperTypical Perfect Humidity t Adaptive Dehumidification System Outdoor-Air Damper With Hood Attached Supply Air Temperature SAT Sensor Supply Air Sensor Temperature Resistance ValuesTemperature F Outdoor Air Lockout SensorEconomi$er IV Control Modes Outdoor Dry Bulb ChangeoverEconomi$er IV Sensor Usage Differential Dry Bulb ControlEconoMi$er IV Wiring Exhaust Set Point Adjustment Minimum Position ControlDemand Controlled Ventilation DCV Damper MovementThermostats Enthalpy Changeover Set Points Dehumidification of Fresh Air with DCV Control Belt Drive MotorsCO2Sensor Standard Settings Belt Drive Motor Mounting581B Fan Rpm at Motor Pulley Setting With High-Static Motor Accessory Static PressureEvaporator-Fan Motor Data Standard Motor Evaporator-Fan Motor Data High-Static Motors581B Outdoor Sound Power Total Unit 581C Outdoor Sound Power Total UnitARI Octavebands Rating Unit Weighted ARI Octave Bands Unit RatingRpm Bhp 11001200 1300Rpm Bhp Watts Rpm Bhp Watts Watts Rpm Bhp 12001600 1700Rpm Bhp Watts 1500 1642 2333 1704Watts Rpm Bhp 1800 26002700 2800Bhp 600 Bhp Watts Rpm2700 2800 2900 3000 Watts Rpm Bhp 900 Bhp Watts 900Watts Rpm 1700 1800 1900 2000 Bhp Watts1900 2000 2100 2200 2300 2400 2500 800 350 904 438 999 535 1087 640 1169 753 913 569 913 569 1010 715 Internal Wiring Refrigerant Service PortsUnit Preparation Gas PipingMain Burners Compressor RotationCooling Safety Relief HeatingVentilation Continuous Fan Operating SequenceHeating Units With Economi$er Subcooling ModeHot Gas Reheat Mode Cleaning Evaporator CoilCondenser Coil One-Row CoilsCondenser-Fan Adjustment EconoMi$er IV AdjustmentHigh Pressure Switch Loss-of-Charge SwitchLow Charge Cooling Perfect Humidity System ChargingC06142 Flue Gas Passageways 581C 3 TON Charging Chart 581C 5 TON Charging Chart Limit Switch LED Error Code DescriptionRemoval and Replacement of Gas Train See Combustion-Air BlowerReplacement Parts OFM Unit Troubleshooting Economi$er IV TroubleshootingEconomi$er IV Troubleshooting Completion LED Error Code Service AnalysisSymptom Cause Remedy LED OFFHeating Service Analysis Problem Cause RemedyCooling Service Analysis EconoMi$er IV Input/Output Logic Inputs OutputsPreliminary Information Catalog No. II581B---C---36---1