Installation Instructions
TABLE OF CONTENTS |
|
| Page |
SAFETY CONSIDERATIONS | . . 1 |
INSTALLATION | . 1 |
Step | . . 2 |
ROOF CURB | . . 2 |
SLAB MOUNT | . . 2 |
ALTERNATE UNIT SUPPORT | . . 2 |
Step | . 2 |
Step | . . 2 |
Step | . . 2 |
POSITIONING | . . 2 |
Step 5 — Install Flue Hood | . . 4 |
Step 6 — Install Gas Piping | . . 4 |
Step 7 — Make Electrical Connections | . . 8 |
FIELD POWER SUPPLY | . . 8 |
FIELD CONTROL WIRING | . . 8 |
HEAT ANTICIPATOR SETTINGS | . . 8 |
Step 8 — Adjust | . 16 |
PERFECT HUMIDITY™ ADAPTIVE |
|
DEHUMIDIFICATION SYSTEM | . 16 |
MANUAL | . 16 |
CONVENIENCE OUTLET | . 16 |
OPTIONAL ECONOMI$ER IV | . 18 |
ECONOMI$ER IV STANDARD SENSORS | . 19 |
ECONOMI$ER IV CONTROL MODES | . 20 |
Step 9 — Adjust | . 25 |
. 41 | |
. 41 | |
SERVICE | . 45 |
TROUBLESHOOTING | . 55 |
. 60 |
SAFETY CONSIDERATIONS
Installation and servicing of
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on
literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Recognize safety information. This is the
. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, turn off main power switch to unit and install lockout tag. Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate.
!WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could cause death and/or property damage.
Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pressures greater than 1/2 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 1/2 psig, it must be replaced before use. When pressure testing
INSTALLATION
Unit is shipped in the vertical discharge configuration. To convert to horizontal discharge application, remove duct opening covers. Using the same screws, install covers on duct openings in basepan of unit with
1