Economi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the
Supply Air Temperature (SAT) Sensor
The supply air temperature sensor is a 3k ohm thermistor located at the inlet of the indoor fan. (See Fig. 34.) This sensor is factory installed. The operating range of temperature measurement is 0° to 158_F. See Table 5 for sensor temperature/resistance values.
Table 5—Supply Air Sensor Temperature/
Resistance Values
TEMPERATURE (F) |
| RESISTANCE (ohms) | |||||||||
|
| 200,250 |
| ||||||||
|
| 100,680 |
| ||||||||
|
| 53,010 |
| ||||||||
|
|
| 29,091 |
| |||||||
14 |
|
| 16,590 |
| |||||||
32 |
|
| 9,795 |
|
| ||||||
50 |
|
| 5,970 |
|
| ||||||
68 |
|
| 3,747 |
|
| ||||||
77 |
|
| 3,000 |
|
| ||||||
86 |
|
| 2,416 |
|
| ||||||
104 |
|
| 1,597 |
|
| ||||||
122 |
|
| 1,080 |
|
| ||||||
140 |
|
| 746 |
|
| ||||||
158 |
|
| 525 |
|
| ||||||
176 |
|
| 376 |
|
| ||||||
185 |
|
| 321 |
|
| ||||||
194 |
|
| 274 |
|
| ||||||
212 |
|
| 203 |
|
| ||||||
230 |
|
| 153 |
|
| ||||||
248 |
|
| 116 |
|
| ||||||
257 |
|
| 102 |
|
| ||||||
266 |
|
| 89 |
|
| ||||||
284 |
|
| 70 |
|
| ||||||
302 |
|
| 55 |
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 17 1/4” |
|
|
| |
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DIVIDER
OUTSIDE
AIR
HOOD
CLEANABLE ALUMINUM FILTER
FILTER
BAROMETRIC RELIEF
FILTER CLIP
C06027
Fig. 28 --- Filter Installation
The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.
Outdoor Air Lockout Sensor
The Economi$er IV is equipped with an ambient temperature lockout switch located in the outdoor air stream which is used to lockout the compressors below a 42_F ambient temperature. (See Fig. 23.)
581B,C