Bryant 581B036--072 Dehumidification of Fresh Air with DCV Control, Belt Drive Motors

Page 25

CO2 SENSOR MAX RANGE SETTING

 

6000

 

 

 

 

 

 

(ppm)

5000

 

 

 

 

 

 

 

 

 

 

 

 

 

CONFIGURATION

4000

 

 

 

 

 

800 ppm

 

 

 

 

 

 

3000

 

 

 

 

 

900 ppm

 

 

 

 

 

1000 ppm

 

 

 

 

 

 

2000

 

 

 

 

 

1100 ppm

 

 

 

 

 

 

 

 

 

 

 

 

 

RANGE

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

2

3

4

5

6

7

8

 

DAMPER VOLTAGE FOR MAX VENTILATION RATE

C06039

Fig. 40 ---CO2 Sensor Maximum Range Setting

CO2 Sensor Configuration

Step 9 Adjust Evaporator-Fan Speed

581B,C

The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. (See Table 7.)

Use setting 1 or 2 for Bryant equipment. (See Table 7.)

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to select the preset number. (See Table 7.)

4.Press Enter to lock in the selection.

5.Press Mode to exit and resume normal operation.

The custom settings of the CO2 sensor can be changed anytime after the sensor is energized. Follow the steps below to change the non-standard settings:

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to toggle to the NONSTD menu and press Enter.

4.Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.

5.Press Mode to move through the variables.

6.Press Enter to lock in the selection, then press Mode to continue to the next variable.

Dehumidification of Fresh Air with DCV Control

Information from ASHRAE indicates that the largest humidity load on any zone is the fresh air introduced. For some applications, a device such as an energy recovery unit can be added to reduce the moisture content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling processes are more than adequate to remove the humidity loads for most commercial applications.

If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered.

Adjust evaporator-fan speed to meet jobsite conditions.

Tables 8 and 9 show fan rpm at motor pulley settings. Tables 10 and 14 show maximum amp draw of belt-drive motor. Table 13 shows sound data. Refer to Tables 15-34 for performance data. See Table 11 for accessory static pressure drop. See Fig. 41 for the Perfect Humiditysystem static pressure drops.

Belt Drive Motors

Fan motor pulleys are factory set for speed shown in Table 1 or 2. Check pulley alignment and belt tension prior to start-up.

To change fan speed:

1.Shut off the unit power supply and tag disconnect.

2.Loosen the belt by loosening the fan motor mounting nuts. (See Fig. 42.)

3.Loosen movable pulley flange setscrew. (See Fig. 43.)

4.Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Table 1 or 2.

5.Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 or 2 for speed change for each full turn of pulley flange.)

6.Adjust belt tension and align fan and motor pulleys per guidance below.

NOTE: Once the required flange position is determined for the correct blower rpm, it is recommended (bu not required) that the variable pitch pulley be replaced with a corresponding size fixed sheave pulley.

To align fan and motor pulleys, loosen fan pulley setscrews and slide fan pulley along fan shaft. Make angular alignment by loosening motor from mounting.

Additional motor and fan alignment, as well as angular alignment can be made by loosening the four motor mounting bolts from the mounting plate.

To adjust belt tension:

1.Loosen the two motor mounting nuts as shown in Fig. 42. Some models may have a third mounting nut located on the opposite side of the fan motor mounting plate.

2.Slide motor mounting plate away from fan scroll for proper belt tension (1/2-in. deflection with 8 to 10 lb of force) and tighten mounting nuts.

3.Adjust lock bolt and nut on mounting plate to secure motor in fixed position.

25

Image 25
Contents Installation Instructions Provide Unit Support Install External Trap for Condensate DrainField Fabricate Ductwork Rig and Place UnitRoof Curb Details Install Gas Piping Install Flue HoodRoof Curb Alignment 581B 036-072 Base Unit Dimensions 581C 024-060 Base Unit Dimensions Field Control Wiring Field Power SupplyHeat Anticipator Settings Make Electrical ConnectionsBase Unit 581B Physical Data 581BUnit Size 581B Base Unit 581C Physical Data 581CUnit Size 581C Power Wiring Connections 581C024---060 Electrical Data 581CElectrical Data 581B Assembly Adjust Factory-Installed OptionsPerfect Humidity Adaptive Dehumidification System Manual Outdoor DamperTypical Perfect Humidity t Adaptive Dehumidification System Outdoor-Air Damper With Hood Attached Supply Air Sensor Temperature Resistance Values Supply Air Temperature SAT SensorTemperature F Outdoor Air Lockout SensorOutdoor Dry Bulb Changeover Economi$er IV Control ModesEconomi$er IV Sensor Usage Differential Dry Bulb ControlEconoMi$er IV Wiring Minimum Position Control Exhaust Set Point AdjustmentThermostats Damper MovementDemand Controlled Ventilation DCV Enthalpy Changeover Set Points Belt Drive Motors Dehumidification of Fresh Air with DCV ControlBelt Drive Motor Mounting CO2Sensor Standard SettingsAccessory Static Pressure 581B Fan Rpm at Motor Pulley Setting With High-Static MotorEvaporator-Fan Motor Data Standard Motor Evaporator-Fan Motor Data High-Static Motors581C Outdoor Sound Power Total Unit 581B Outdoor Sound Power Total UnitARI Octavebands Rating Unit Weighted ARI Octave Bands Unit Rating1100 Rpm Bhp1200 1300Rpm Bhp Watts Watts Rpm Bhp 1200 Rpm Bhp Watts1600 17001642 2333 1704 Rpm Bhp Watts 15002600 Watts Rpm Bhp 18002700 28002700 2800 2900 3000 Bhp Watts RpmBhp 600 Watts Rpm Bhp Watts 900Watts Rpm Bhp 900 Bhp Watts 1700 1800 1900 20001900 2000 2100 2200 2300 2400 2500 800 350 904 438 999 535 1087 640 1169 753 913 569 913 569 1010 715 Refrigerant Service Ports Internal WiringUnit Preparation Gas PipingCooling Compressor RotationMain Burners Heating Safety ReliefVentilation Continuous Fan Operating SequenceHot Gas Reheat Mode Subcooling ModeHeating Units With Economi$er Evaporator Coil CleaningCondenser Coil One-Row CoilsEconoMi$er IV Adjustment Condenser-Fan AdjustmentHigh Pressure Switch Loss-of-Charge SwitchPerfect Humidity System Charging Low Charge CoolingC06142 Flue Gas Passageways 581C 3 TON Charging Chart 581C 5 TON Charging Chart LED Error Code Description Limit SwitchRemoval and Replacement of Gas Train See Combustion-Air BlowerReplacement Parts OFM Economi$er IV Troubleshooting Unit TroubleshootingLED Error Code Service Analysis Economi$er IV Troubleshooting CompletionSymptom Cause Remedy LED OFFProblem Cause Remedy Heating Service AnalysisCooling Service Analysis Inputs Outputs EconoMi$er IV Input/Output LogicCatalog No. II581B---C---36---1 Preliminary Information