Bryant 581C024--060 Lubrication, Condenser-Fan Adjustment, EconoMi$er IV Adjustment, Freeze-Stat

Page 46

581B,C

C06046

Fig. 49 ---Separating Coil Sections

4.Remove screws securing coil to compressor plate and compressor access panel.

5.Remove fastener holding coil sections together at return end of condenser coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. (See Fig. 49.)

6.Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.

7.Secure inner and outer coil rows together with a field-supplied fastener.

8.Reposition the outer coil section and remove the coil corner post from between the top panel and center post.

Reinstall the coil corner post and replace all screws.

Condensate Drain

Check and clean each year at the start of the cooling season. In winter, keep the drain dry or protect it against freeze-up.

Filters

Clean or replace at the start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be the same dimensions as the original filters.

Outdoor-Air Inlet Screens

Clean the screens with steam or hot water and a mild detergent. Do not use disposable filters in place of screens.

Step 2 Lubrication

Compressor

The compressor is charged with the correct amount of oil at the factory.

Fan Motor Bearings

Fan motor bearings are permanently lubricated. No further lubrication is required. No lubrication of condenser-fan or evaporator-fan motors is required.

Step 3 Condenser-Fan Adjustment

Shut off unit power supply. Remove condenser-fan assembly (grille, motor, motor cover, and fan) and loosen fan hub setscrews. Adjust fan height as shown in Fig. 50. Tighten setscrews and replace condenser-fan assembly.

 

UNIT

FAN HEIGHT (in.) - A

 

 

024-060 and 072 (208/230 v)

2.75

 

 

072 (460 v)

3.50

 

 

 

 

 

C06138

Fig. 50 ---Condenser-Fan Adjustment

Step 4 EconoMi$er IV Adjustment

Refer to Optional EconoMi$er IV section.

Step 5 Evaporator Fan Belt Inspection

Check condition of evaporator belt or tension during heating and cooling inspections or as conditions require. Replace belt or adjust as necessary.

Step 6 High Pressure Switch

The high-pressure switch contains a Schrader core depressor, and is located on the compressor hot gas line. This switch opens at 428 psig and closes at 320 psig. No adjustments are necessary.

Step 7 Loss-of-Charge Switch

The loss-of-charge switch contains a Schrader core depressor, and is located on the compressor liquid line. This switch opens at 7 psig and closes at 22 psig. No adjustments are necessary.

Step 8 Freeze-Stat

The freeze-stat is a bimetal temperature-sensing switch that is located on the “hair-pin” end of the evaporator coil. The switch protects the evaporator coil from freeze-up due to lack of airflow. The switch opens at 30_F and closes at 45_F. No adjustments are necessary.

Step 9 Refrigerant Charge

Amount of refrigerant charge is listed on unit nameplate (also refer to Table 1). Refer to HVAC Servicing Procedures literature available at your local distributor and the following procedures.

Unit panels must be in place when unit is operating during charging procedure. Unit must operate a minimum of 10 minutes before checking or adjusting refrigerant charge.

An accurate superheat, thermocouple-type or thermistor-type thermometer, and a gauge manifold are required when using the superheat charging method for evaluating the unit charge. Do not use mercury or small dial-type thermometers because they are not adequate for this type of measurement.

No Charge

Use standard evacuating techniques. After evacuating system to 500 microns, weigh in the specified amount of refrigerant. (Refer to Table 1 or 2 and unit information plate.)

46

Image 46
Contents Installation Instructions Field Fabricate Ductwork Install External Trap for Condensate DrainProvide Unit Support Rig and Place UnitRoof Curb Details Install Flue Hood Install Gas PipingRoof Curb Alignment 581B 036-072 Base Unit Dimensions 581C 024-060 Base Unit Dimensions Heat Anticipator Settings Field Power SupplyField Control Wiring Make Electrical ConnectionsPhysical Data 581B Base Unit 581BUnit Size 581B Physical Data 581C Base Unit 581CUnit Size 581C Power Wiring Connections Electrical Data 581C 581C024---060Electrical Data 581B Perfect Humidity Adaptive Dehumidification System Adjust Factory-Installed OptionsAssembly Manual Outdoor DamperTypical Perfect Humidity t Adaptive Dehumidification System Outdoor-Air Damper With Hood Attached Temperature F Supply Air Temperature SAT SensorSupply Air Sensor Temperature Resistance Values Outdoor Air Lockout SensorEconomi$er IV Sensor Usage Economi$er IV Control ModesOutdoor Dry Bulb Changeover Differential Dry Bulb ControlEconoMi$er IV Wiring Exhaust Set Point Adjustment Minimum Position ControlThermostats Damper MovementDemand Controlled Ventilation DCV Enthalpy Changeover Set Points Dehumidification of Fresh Air with DCV Control Belt Drive MotorsCO2Sensor Standard Settings Belt Drive Motor MountingEvaporator-Fan Motor Data Standard Motor 581B Fan Rpm at Motor Pulley Setting With High-Static MotorAccessory Static Pressure Evaporator-Fan Motor Data High-Static MotorsARI Octavebands Rating Unit Weighted 581B Outdoor Sound Power Total Unit581C Outdoor Sound Power Total Unit ARI Octave Bands Unit Rating1200 Rpm Bhp1100 1300Rpm Bhp Watts 1600 Rpm Bhp WattsWatts Rpm Bhp 1200 1700Rpm Bhp Watts 1500 1642 2333 17042700 Watts Rpm Bhp 18002600 28002700 2800 2900 3000 Bhp Watts RpmBhp 600 Watts Rpm Bhp Watts 900Watts Rpm Bhp 900 1700 1800 1900 2000 Bhp Watts1900 2000 2100 2200 2300 2400 2500 800 350 904 438 999 535 1087 640 1169 753 913 569 913 569 1010 715 Unit Preparation Internal WiringRefrigerant Service Ports Gas PipingCooling Compressor RotationMain Burners Ventilation Continuous Fan Safety ReliefHeating Operating SequenceHot Gas Reheat Mode Subcooling ModeHeating Units With Economi$er Condenser Coil CleaningEvaporator Coil One-Row CoilsHigh Pressure Switch Condenser-Fan AdjustmentEconoMi$er IV Adjustment Loss-of-Charge SwitchLow Charge Cooling Perfect Humidity System ChargingC06142 Flue Gas Passageways 581C 3 TON Charging Chart 581C 5 TON Charging Chart Removal and Replacement of Gas Train See Limit SwitchLED Error Code Description Combustion-Air BlowerReplacement Parts OFM Unit Troubleshooting Economi$er IV TroubleshootingSymptom Cause Remedy Economi$er IV Troubleshooting CompletionLED Error Code Service Analysis LED OFFHeating Service Analysis Problem Cause RemedyCooling Service Analysis EconoMi$er IV Input/Output Logic Inputs OutputsPreliminary Information Catalog No. II581B---C---36---1