Bryant 581C024--060, 581B036--072 installation instructions Unit Size 581B

Page 10

581B,C

Table 1 — Physical Data 581B (cont)

UNIT SIZE 581B

 

 

036

048

060

072

FURNACE SECTION

 

 

 

 

 

 

 

 

 

 

Rollout Switch Cutout Temp (F)†

 

195

195

195

195

Burner Orifice Diameter (in. ...

drill size)**

 

 

 

 

 

 

 

 

 

Natural Gas —Std

 

071/072

.113

...33

.113

...33

.113

...33

.113

...33

 

 

114/115

.113

...33

.113

...33

.113

...33

.113

...33

 

 

149/150

.129

...30

.129

...30

.129

...30

 

 

060N

.102

...38

.102

...38

.102

...38

 

 

090N

.102

...38

.102

...38

.102

...38

 

 

120N

.116

...32

.116

...32

Propane —Alt††

 

071/072

.089

...43

.089

...43

.089

...43

.089

...43

 

 

114115

.089

...43

.089

...43

.089

...43

.089

...43

 

 

149/150

.102

...38

.102

...38

.104

...39

 

 

060N

.082

...45

.082

...45

.082

...45

 

 

090N

.082

...45

.082

...45

.082

...45

Thermostat Heat Anticipator Setting (amps)

120N

.094

...42

.094

...42

 

 

 

 

 

 

 

 

 

208/230/460 v

 

 

 

 

 

 

 

 

 

 

First Stage

 

 

.14

.14

.14

.14

Second Stage

 

 

.14

.14

.14

.14

Gas Input (Btuh)

 

 

 

 

 

 

 

 

 

 

First Stage/Second Stage (3---

phase units)

072

50,000/ 72,000

50,000/ 72,000

50,000/ 72,000

50,000/ 72,000

 

 

115

82,000/115,000

82,000/115,000

82,000/115,000

82,000/115,000

 

 

150

120,000/150,000

120,000/150,000

120,000/150,000

 

 

071II

—/72,000

—/72,000

—/72,000

 

 

114II

—/115,000

—/115,000

—/115,000

 

 

149II

—/150,000

—/150,000

 

 

060N***

—/ 60,000

—/60,000

—/60,000

 

 

090N***

—/ 90,000

—/90,000

—/90,000

 

 

120N***

—/120,000

—/120,000

Efficiency (Steady State) (%)

 

072

82

82

82

82

 

 

115

80

81

81

81

 

 

150

80

80

80

 

 

071

82

82

82

 

 

114

80

81

81

 

 

149

80

80

 

 

060N

80

80

80

 

 

090N

80

80

80

 

 

120N

80

80

Temperature Rise Range

 

072

15---

45

15---

45

15---

45

15---

45

 

 

115

55---

85

35---

65

35---

65

35---

65

 

 

150

50---

80

50---

80

50---

80

 

 

071

15---

45

15---

45

15---

45

 

 

114

55---

85

35---

65

35---

65

 

 

149

50---

80

50---

80

 

 

060N

20---

50

20---

50

20---

50

 

 

090N

30---

60

30---

60

30---

60

Manifold Pressure (in. wg)

 

120N

40---

70

40---

70

 

 

 

 

 

 

 

 

 

 

Natural Gas —Std

 

 

3.5

3.5

3.5

3.5

Propane —Alt††

 

 

3.5

3.5

3.5

3.5

Maximum Static Pressure (in. wg)

 

1.0

1.0

1.0

1.0

Field Gas Connection Size (in.)

 

1/2

1/2

1/2

1/2

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

Standard Compressor Internal Relief

450

±

50

 

Cutout

428

 

 

Reset (Auto.)

320

 

 

LOSS-OF-CHARGE SWITCH/LOW-PRESSURE

 

 

 

 

(Liquid Line) (psig)

 

 

 

 

Cutout

7

±

3

 

Reset (Auto.)

22

±

5

 

FREEZE PROTECTION THERMOSTAT

 

 

 

 

Opens (F)

30

±

5

 

Closes (F)

45

±

5

 

OUTDOOR-AIR INLET SCREENS

Cleanable. Screen quantity and size varies with option selected.

RETURN-AIR FILTERS

Throwaway

...Quantity Size (in.)

...2 16 x 25 x 2

 

 

...4 16 x 16 x 2

LEGEND

Bhp — Brake Horsepower

**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000 Btuh heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh Heat input units have 3 burners.

††A propane kit is available as an accessory. Kit may be used at elevations as high as 2000 ft. If a propane kit is used with Low NOx units, the Low NOx baffle must be removed and the units will no longer be classified as Low NOx units.

ll Three-phase standard models have heating inputs as shown. Single-phase stan- dard models have one-stage heating with heating input values.

***California compliant three-phase models.

†††California SCAQMD compliant low NOx models have combustion products that are controlled to 40 nanograms per joule or less.

10

Image 10
Contents Installation Instructions Field Fabricate Ductwork Install External Trap for Condensate DrainProvide Unit Support Rig and Place UnitRoof Curb Details Install Flue Hood Install Gas PipingRoof Curb Alignment 581B 036-072 Base Unit Dimensions 581C 024-060 Base Unit Dimensions Heat Anticipator Settings Field Power SupplyField Control Wiring Make Electrical ConnectionsPhysical Data 581B Base Unit 581BUnit Size 581B Physical Data 581C Base Unit 581CUnit Size 581C Power Wiring Connections Electrical Data 581C 581C024---060Electrical Data 581B Perfect Humidity Adaptive Dehumidification System Adjust Factory-Installed OptionsAssembly Manual Outdoor DamperTypical Perfect Humidity t Adaptive Dehumidification System Outdoor-Air Damper With Hood Attached Temperature F Supply Air Temperature SAT SensorSupply Air Sensor Temperature Resistance Values Outdoor Air Lockout SensorEconomi$er IV Sensor Usage Economi$er IV Control ModesOutdoor Dry Bulb Changeover Differential Dry Bulb ControlEconoMi$er IV Wiring Exhaust Set Point Adjustment Minimum Position ControlThermostats Damper MovementDemand Controlled Ventilation DCV Enthalpy Changeover Set Points Dehumidification of Fresh Air with DCV Control Belt Drive MotorsCO2Sensor Standard Settings Belt Drive Motor MountingEvaporator-Fan Motor Data Standard Motor 581B Fan Rpm at Motor Pulley Setting With High-Static MotorAccessory Static Pressure Evaporator-Fan Motor Data High-Static MotorsARI Octavebands Rating Unit Weighted 581B Outdoor Sound Power Total Unit581C Outdoor Sound Power Total Unit ARI Octave Bands Unit Rating1200 Rpm Bhp1100 1300Rpm Bhp Watts 1600 Rpm Bhp WattsWatts Rpm Bhp 1200 1700Rpm Bhp Watts 1500 1642 2333 17042700 Watts Rpm Bhp 18002600 28002700 2800 2900 3000 Bhp Watts RpmBhp 600 Watts Rpm Bhp Watts 900Watts Rpm Bhp 900 1700 1800 1900 2000 Bhp Watts1900 2000 2100 2200 2300 2400 2500 800 350 904 438 999 535 1087 640 1169 753 913 569 913 569 1010 715 Unit Preparation Internal WiringRefrigerant Service Ports Gas PipingCooling Compressor RotationMain Burners Ventilation Continuous Fan Safety ReliefHeating Operating SequenceHot Gas Reheat Mode Subcooling ModeHeating Units With Economi$er Condenser Coil CleaningEvaporator Coil One-Row CoilsHigh Pressure Switch Condenser-Fan AdjustmentEconoMi$er IV Adjustment Loss-of-Charge SwitchLow Charge Cooling Perfect Humidity System ChargingC06142 Flue Gas Passageways 581C 3 TON Charging Chart 581C 5 TON Charging Chart Removal and Replacement of Gas Train See Limit SwitchLED Error Code Description Combustion-Air BlowerReplacement Parts OFM Unit Troubleshooting Economi$er IV TroubleshootingSymptom Cause Remedy Economi$er IV Troubleshooting CompletionLED Error Code Service Analysis LED OFFHeating Service Analysis Problem Cause RemedyCooling Service Analysis EconoMi$er IV Input/Output Logic Inputs OutputsPreliminary Information Catalog No. II581B---C---36---1