Emerson MINI-MATE2 user manual Recommended refrigerant line sizes, Copper Pipe

Page 25

Site Preparation and Installation

Chilled Water Piping—On chilled water units install manual service shut-off valves at the supply and return lines of each unit. These shut-off valves are used for routine service or emergency isolation of the unit.

Chilled water supply and return lines must be insulated. Insulating them will prevent condensation of the water supply and return lines to the unit.

The minimum recommended water temperature is 42°F (5.5°C). Connection sizes are 1-1/8" (28.6mm) OD copper.

Water/Glycol Piping—Water- and glycol-cooled systems require coolant loop connections as specified in the condensing unit installation instructions.

Refrigerant R-407CPiping—All split systems require two refrigerant lines (an insulated copper suction line and a copper liquid line) between the evaporator and the condensing unit.

! WARNING

Risk of explosive discharge of high pressure refrigerant. Can cause serious injury. Relieve refrigerant system pressure before working with piping/connections.

Two possible methods exist for installing the copper suction and liquid lines.

Close coupling the units together using the quick connects. (See Figure 15).

Using an optional sweat adapter kit and hard piping between the two units.

All refrigeration piping should be installed with high temperature brazed joints. Prevailing good refrigeration practices should be employed for piping supports, leak testing, evacuation, dehydration and charging of the refrigeration circuits. The refrigeration piping should be isolated from the building by the use of vibration isolating supports. To prevent tube damage when sealing openings in walls and to reduce vibration transmission, use a soft flexible material to pack around the tubes.

When installing remote condensing units above the evaporator, the suction gas line should be trapped at the evaporator. This trap will retain refrigerant oil in the off cycle. When the unit starts, oil in the trap is carried up the vertical riser and returns to the compressor.

Table 8 Recommended refrigerant line sizes

Equivalent Pipe

 

Liquid

Suction

 

 

 

 

 

 

 

Length, ft (m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50 (15)

 

 

 

1/2"

 

1-1/8"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100 (30.5)

 

 

 

5/8"

 

1-1/8"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150 (45.7)

 

 

 

5/8"

 

1-3/8"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction line and liquid line sizing based on < 3 psi pressure drop in each and suction line refrigerant

 

 

velocities >1000FPM (5.1m/s) for proper oil return.

 

 

 

 

 

 

Table 9

Equivalent lengths for various pipe fittings, ft (m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Copper Pipe

 

 

90 Degree

 

90 Degree

45 Degree

 

Gate

 

Globe

Angle

OD, in.

 

 

Elbow Copper

 

Elbow Cast

Elbow

Tee

Valve

 

Valve

Valve

1/2

 

 

 

0.8 (0.24)

 

 

1.3 (0.39)

0.4 (0.12)

2.5 (0.76)

0.26 (0.07)

 

7.0 (2.13)

4.0 (1.21)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5/8

 

 

 

0.9 (0.27)

 

 

1.4 (0.42)

0.5 (0.15)

2.5 (0.76)

0.28 (0.08)

 

9.5 (2.89)

5.0 (1.52)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

 

 

 

1.0 (0.3)

 

 

1.5 (0.45)

0.6 (0.18)

2.5 (0.76)

0.3 (0.09)

 

12.0 (3.65)

6.5 (1.98)

 

 

 

 

 

 

 

 

 

 

 

 

 

7/8

 

 

 

1.45 (0.44)

 

1.8 (0.54)

0.8 (0.24)

3.6 (1.09)

0.36 (0.1)

 

17.2 (5.24)

9.5 (2.89)

 

 

 

 

 

 

 

 

 

 

 

 

 

1-1/8

 

 

 

1.85 (0.56)

 

2.2 (0.67)

1.0 (0.3)

4.6 (1.4)

0.48 (0.14)

 

22.5 (6.85)

12.0 (3.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-3/8

 

 

 

2.4 (0.73)

 

 

2.9 (0.88)

1.3 (0.39)

6.4 (1.95)

0.65 (0.19)

 

32.0 (9.75)

16.0 (4.87)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-5/8

 

 

 

2.9 (0.88)

 

 

3.5 (1.06)

1.6 (0.48)

7.2 (2.19)

0.72 (0.21)

 

36.0 (10.97)

19.5 (5.94)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant trap = Four times equivalent length of pipe per this table

19

Liebert® Mini-Mate2

Image 25
Contents Liebert Mini-Mate2 Page Table of Contents System Performance Microprocessor Controls Microprocessor ControlSystem OPERATION, Testing and Maintenance AlarmsTables Important Safety Instructions Liebert Mini-Mate2 Air-cooled systems-indoor centrifugal condensing units Product Model InformationPFH 0 67 a a L System configurations-50 Hz System configurations-60 HzIntroduction Evaporator Section-Split System Standard FEATURES-5 TON SystemsCondensing Unit Section-Split System Chilled Water UnitsSystem Controls Other Standard Control FeaturesReheat Switches and MotorsHumidifier SensorsOptional Configurations-Water/Glycol Condensing Units Optional Configurations-Prop Fan Condensing UnitsFree-Cooling Optional Configurations-Chilled Water Units SHIP-LOOSE ACCESSORIES-FIELD-INSTALLED Ship-Loose Accessories-Field-Installed Site Preparation and Installation Installation ConsiderationsRoom Preparation Air-cooled systems Location ConsiderationsUnit weights Ceiling Unit WeightsCooling Drycooler Cooling UnitsClose Coupled Installations Installing the Ceiling UnitsEquipment Inspection Upon Receipt Evaporator Air Distribution Filter BoxPiping Connections and Coolant Requirements Drain Line Connections for Ducted SystemsHumidifier Water Supply Line Evaporator external static pressureEquivalent lengths for various pipe fittings, ft m Recommended refrigerant line sizesEquivalent Pipe Liquid Suction Length, ft m Copper PipeVertical rise above evaporator/maximum Pipe length and condenser elevation relative to evaporatorVertical fall below evaporator Quick Connect Fittings Total refrigerant = Units and LinesRefrigerant charge Line charges refrigerant per 100 ft m of Type L copper tubeDPN000218 Electrical Connections Threaded rod and hardware kit installationControl Connections Power ConnectionsEvaporator unit electrical connections Close coupled installation Ducting Piping ConnectionsGeneral Considerations Considerations for Specific ApplicationsAIR-COOLED Dimensional Data AIR Cooled AIR-COOLED Weight, lb kg Outdoor Air-Cooled Condensing Unit InstallationModel # 60Hz 50Hz Rev Condensing Unit Fluid Requirements Water/Glycol Piping ConsiderationsRegulating Valve WATER/GLYCOL Dimensional Data WATER/GLYCOL DPN000214 Optional free-cooling coil 3-way valve on water/glycol units Hot Water Reheat CoilChecklist for Completed Installation Microprocessor Control Feature OverviewSetpoints Main Menu MenuStatus Active AlarmsTime DateRestart Time Delay Setup OperationShow DIP Switch 2 C/F DegreesSetup functions, default values and allowable ranges Change PasswordsFunction Default Range Calibrate SensorsAlarm Time Delay Alarm EnableCommon Alarm Enable Alarm default time delaysStandard Custom Alarm Messages Custom AlarmsCustom Text LCD Display ContrastEquipment Options Switches Run Diagnostics Available On Rev 1.001.0 and higherEquipment switch settings unit control board Switch settings wall box boardTest Control Board Test OutputsControl menu Wall box board Control board-inside evaporatorHumidity Control Temperature ControlSystem Performance Microprocessor Controls Humidification Operation Load Control FeaturesCommunications Alarms Alarms Definitions and TroubleshootingCustom Alarms High Head PressureHumidifier Problem Alarm TemperatureHigh Water Alarm Air-Cooled SystemsOptional/Custom Alarms Maintenance and Component Operation System TestingSystem OPERATION, Testing and Maintenance Air Distribution Blower SystemBlower Removal Refrigeration SystemDischarge Pressure Glycol Solution MaintenanceThermostatic Expansion Valve Air-Cooled Condensing UnitsHot gas bypass Hot Gas BypassCompressor Replacement Replacement ProceduresMechanical Failure Electrical FailureReplace a Failed Compressor Steam Generating Humidifier-Operation Procedures Humidifier control board DIP switch settings Humidifier Circuit Board AdjustmentsReplacing the Humidifier Canister AmpsMaintenance Inspection Checklist Troubleshooting TroubleshootingDisplay Problem Symptom Possible Cause Check Or Remedy Cooling cycle tooShort Display freezesPpor t Is t Ne tTwor k Care

MINI-MATE2 specifications

The Emerson MINI-MATE2 is a cutting-edge temperature and pressure monitoring device specifically designed for the needs of the refrigeration and HVAC industries. Known for its reliability and user-friendly interface, this compact unit serves as a key tool for technicians and facility managers looking to optimize system performance while ensuring compliance with safety standards.

One of the main features of the MINI-MATE2 is its advanced digital display, which allows users to easily monitor and interpret temperature and pressure readings in real-time. Its highly responsive sensors ensure accurate data collection, vital for maintaining optimal operating conditions. Moreover, the device supports a wide range of refrigerants, making it versatile for different applications, from walk-in coolers to commercial refrigeration systems.

The MINI-MATE2 utilizes state-of-the-art technology to enhance efficiency and performance. Equipped with Bluetooth connectivity, it allows for wireless communication with mobile devices, enabling technicians to track readings and receive alerts remotely. This feature not only improves convenience but also helps in quick decision-making, ensuring timely interventions when anomalies are detected.

Another significant characteristic is its robust construction. Built to withstand harsh environments, the MINI-MATE2 features a durable casing that protects it from physical impacts and environmental factors. This resilience ensures longevity, making it a cost-effective investment for any facility.

In addition, the MINI-MATE2 is designed with user-friendliness in mind. Its intuitive interface means that even technicians with limited experience can easily navigate its functionalities. Quick setup and straightforward operation allow for rapid adoption and extensive use in a variety of settings.

Finally, the MINI-MATE2 also includes built-in data logging capabilities. Users can record historical data for analysis and reporting purposes, which is essential for performing trend analysis and identifying potential issues before they escalate. By providing a comprehensive overview of system performance, the MINI-MATE2 empowers users to make informed decisions that can lead to improved energy efficiency and reduced operational costs.

Overall, the Emerson MINI-MATE2 is an indispensable tool for modern refrigeration and HVAC applications, combining cutting-edge technology, user-friendly design, and essential features to support efficient system management.