Emerson MINI-MATE2 user manual Change Passwords, Calibrate Sensors, Function Default Range

Page 49

Microprocessor Control

6.9.5Valve Time (for Systems With a Modulating Chilled Water Valve)

This function shows the full valve travel time of the modulating valve on a chilled water system. This is the time it takes for the valve to travel from full closed to full open. It is programmable from 50 to 250 seconds; factory default time is 165 seconds and should not be changed. The full valve travel time is used by the control to determine the appropriate valve position. For example, if the valve travel time is 165 seconds and 50% cooling is being called for, the valve will open for 83 seconds to achieve 50% open.

6.9.6CW Flush (for Systems with a Modulating Chilled Water Valve)

This function shows the interval time at which the system will perform a modulating chilled water valve system flush cycle. The factory default is 24 (hours) and is programmable from 0 (hours) which signifies to never flush, to 99 (hours) which signifies to flush after every 99 hours of valve non-use. If the valve is called on by the control to open within the programmed interval time, the timer will be reset to 0. The flush cycle is active even when the fan is turned off, but power is applied to the unit. When the interval timer reaches the programmed time, the valve will be opened for 3 minutes to flush any contaminants that may have collected in the system.

Table 18 Setup functions, default values and allowable ranges

Function

Default

Range

 

 

 

Restart Time

0.1

0 to 9.9 min

Delay

 

(0 = manual restart)

C/F Degrees

°F

°C or °F

 

 

 

Humidity Control

Rel

Relative or Absolute

 

 

 

Valve Time

165

50 to 250 seconds

 

 

 

CW Flush

24

0 to 99 hours

 

 

 

6.10Change Passwords

The display will prompt the operator to enter a three digit password when attempting to make changes. The system includes two (2) passwords, one for setpoints and one for setup. The system allows the password to be changed by first entering the default password set at the factory (1-2-3) for setpoints and (3-2-1) for setup. The password function provides system security so that only authorized personnel are allowed to make changes to the system. (If unauthorized changes are being made, the passwords may be compromised and new ones should be selected). The password function can be disabled by setting DIP switch 8 in the wall box to OFF, then resetting power to the unit.

6.11Calibrate Sensors

The temperature and humidity sensors can be calibrated by selecting the CALIBRATE SENSORS menu item. The temperature sensor can be calibrated ±5°F, while the humidity sensor can be calibrated ±10% RH. When calibrating the humidity sensor, the value shown will always be % RH, even though absolute humidity control may be selected. If absolute humidity control is selected, the Normal Status Display will display the adjusted reading. This reading may not agree with the relative humidity reading displayed while in calibration.

If the sensors are subject to frequent wide temperature and humidity swings, it may be necessary to shorten the cycling by increasing the sensor time delay. If the sensors are located too close to the air discharge, they will likely experience rapid swings in measurement. Another method in reducing compressor cycling is to increase the temperature and/or humidity sensitivity.

43

Liebert® Mini-Mate2

Image 49
Contents Liebert Mini-Mate2 Page Table of Contents System Performance Microprocessor Controls Microprocessor ControlSystem OPERATION, Testing and Maintenance AlarmsTables Important Safety Instructions Liebert Mini-Mate2 Air-cooled systems-indoor centrifugal condensing units Product Model InformationPFH 0 67 a a L System configurations-50 Hz System configurations-60 HzIntroduction Evaporator Section-Split System Standard FEATURES-5 TON SystemsCondensing Unit Section-Split System Chilled Water UnitsSystem Controls Other Standard Control FeaturesReheat Switches and MotorsHumidifier SensorsOptional Configurations-Water/Glycol Condensing Units Optional Configurations-Prop Fan Condensing UnitsFree-Cooling Optional Configurations-Chilled Water Units SHIP-LOOSE ACCESSORIES-FIELD-INSTALLED Ship-Loose Accessories-Field-Installed Site Preparation and Installation Installation ConsiderationsRoom Preparation Air-cooled systems Location ConsiderationsUnit weights Ceiling Unit WeightsCooling Drycooler Cooling UnitsClose Coupled Installations Installing the Ceiling UnitsEquipment Inspection Upon Receipt Evaporator Air Distribution Filter BoxPiping Connections and Coolant Requirements Drain Line Connections for Ducted SystemsHumidifier Water Supply Line Evaporator external static pressureEquivalent lengths for various pipe fittings, ft m Recommended refrigerant line sizesEquivalent Pipe Liquid Suction Length, ft m Copper PipeVertical rise above evaporator/maximum Pipe length and condenser elevation relative to evaporatorVertical fall below evaporator Quick Connect Fittings Total refrigerant = Units and LinesRefrigerant charge Line charges refrigerant per 100 ft m of Type L copper tubeDPN000218 Electrical Connections Threaded rod and hardware kit installationControl Connections Power ConnectionsEvaporator unit electrical connections Close coupled installation Ducting Piping ConnectionsGeneral Considerations Considerations for Specific ApplicationsAIR-COOLED Dimensional Data AIR Cooled AIR-COOLED Weight, lb kg Outdoor Air-Cooled Condensing Unit InstallationModel # 60Hz 50Hz Rev Condensing Unit Fluid Requirements Water/Glycol Piping ConsiderationsRegulating Valve WATER/GLYCOL Dimensional Data WATER/GLYCOL DPN000214 Optional free-cooling coil 3-way valve on water/glycol units Hot Water Reheat CoilChecklist for Completed Installation Microprocessor Control Feature OverviewSetpoints Main Menu MenuStatus Active AlarmsTime DateRestart Time Delay Setup OperationShow DIP Switch 2 C/F DegreesSetup functions, default values and allowable ranges Change PasswordsFunction Default Range Calibrate SensorsAlarm Time Delay Alarm EnableCommon Alarm Enable Alarm default time delaysStandard Custom Alarm Messages Custom AlarmsCustom Text LCD Display ContrastEquipment Options Switches Run Diagnostics Available On Rev 1.001.0 and higherEquipment switch settings unit control board Switch settings wall box boardTest Control Board Test OutputsControl menu Wall box board Control board-inside evaporatorHumidity Control Temperature ControlSystem Performance Microprocessor Controls Humidification Operation Load Control FeaturesCommunications Alarms Alarms Definitions and TroubleshootingCustom Alarms High Head PressureHumidifier Problem Alarm TemperatureHigh Water Alarm Air-Cooled SystemsOptional/Custom Alarms Maintenance and Component Operation System TestingSystem OPERATION, Testing and Maintenance Air Distribution Blower SystemBlower Removal Refrigeration SystemDischarge Pressure Glycol Solution MaintenanceThermostatic Expansion Valve Air-Cooled Condensing UnitsHot gas bypass Hot Gas BypassCompressor Replacement Replacement ProceduresMechanical Failure Electrical FailureReplace a Failed Compressor Steam Generating Humidifier-Operation Procedures Humidifier control board DIP switch settings Humidifier Circuit Board AdjustmentsReplacing the Humidifier Canister AmpsMaintenance Inspection Checklist Troubleshooting TroubleshootingDisplay Problem Symptom Possible Cause Check Or Remedy Cooling cycle tooShort Display freezesPpor t Is t Ne tTwor k Care

MINI-MATE2 specifications

The Emerson MINI-MATE2 is a cutting-edge temperature and pressure monitoring device specifically designed for the needs of the refrigeration and HVAC industries. Known for its reliability and user-friendly interface, this compact unit serves as a key tool for technicians and facility managers looking to optimize system performance while ensuring compliance with safety standards.

One of the main features of the MINI-MATE2 is its advanced digital display, which allows users to easily monitor and interpret temperature and pressure readings in real-time. Its highly responsive sensors ensure accurate data collection, vital for maintaining optimal operating conditions. Moreover, the device supports a wide range of refrigerants, making it versatile for different applications, from walk-in coolers to commercial refrigeration systems.

The MINI-MATE2 utilizes state-of-the-art technology to enhance efficiency and performance. Equipped with Bluetooth connectivity, it allows for wireless communication with mobile devices, enabling technicians to track readings and receive alerts remotely. This feature not only improves convenience but also helps in quick decision-making, ensuring timely interventions when anomalies are detected.

Another significant characteristic is its robust construction. Built to withstand harsh environments, the MINI-MATE2 features a durable casing that protects it from physical impacts and environmental factors. This resilience ensures longevity, making it a cost-effective investment for any facility.

In addition, the MINI-MATE2 is designed with user-friendliness in mind. Its intuitive interface means that even technicians with limited experience can easily navigate its functionalities. Quick setup and straightforward operation allow for rapid adoption and extensive use in a variety of settings.

Finally, the MINI-MATE2 also includes built-in data logging capabilities. Users can record historical data for analysis and reporting purposes, which is essential for performing trend analysis and identifying potential issues before they escalate. By providing a comprehensive overview of system performance, the MINI-MATE2 empowers users to make informed decisions that can lead to improved energy efficiency and reduced operational costs.

Overall, the Emerson MINI-MATE2 is an indispensable tool for modern refrigeration and HVAC applications, combining cutting-edge technology, user-friendly design, and essential features to support efficient system management.