Emerson MINI-MATE2 user manual System Testing, Maintenance and Component Operation

Page 61

System Operation, Testing and Maintenance

9.0SYSTEM OPERATION, TESTING AND MAINTENANCE

This section describes system testing, maintenance and replacement procedures. Use copies of the Maintenance Inspection Checklist to record preventive maintenance inspections.

! WARNING

Risk of electric shock. Can cause injury or death.

Open all local and remote electric power disconnect switches before working within the electrical enclosures.

The Liebert microprocessor control does not isolate power from the unit in the Unit Off mode. Some internal components require and receive power even during the Unit Off mode. The line side of the disconnect switch on the front of the unit contains live high voltage. The only way to ensure that there is NO voltage inside the unit is to install and open a remote disconnect switch and check the internal power supply wires with a voltmeter.

9.1System Testing

9.1.1Environmental Control Functions

The performance of all control circuits can be tested by changing the set points, which activates each of the main functions.

9.1.2Cooling

To test the cooling function, set the set point to a temperature of 10°F (5°C) below room temperature. A call for cooling should register and prompt the equipment to begin cooling cycle. (Disregard any temperature alarms). Upon completion of testing, return set point to the desired temperature.

9.1.3Heating

Reheat may be tested by setting the set point 10°F (5°C) above room temperature. A call for heating should register and prompt the equipment to begin heating cycle. (Disregard any temperature alarms). Upon completion of testing, return set point to the desired temperature.

9.1.4Humidification

To check humidification, set the humidity set point at R.H. 10% above the room humidity reading. After a short delay, the canister will fill with water and steam will be produced. Upon completion of testing, return the humidity set point to the desired humidity.

9.1.5Dehumidification

The dehumidification performance can be tested by setting the humidity set point at R.H. 10% below room relative humidity. The compressor should turn on. Upon completion of testing, return humidity set point to the desired humidity.

9.1.6Remote Shutdown

A connection point is provided for remote shutdown devices supplied by the customer. This terminal strip is located on the printed circuit board. (Terminals TB1-4 and TB1-5 are fitted with a jumper when no remote shutdown device is installed).

9.2Maintenance and Component Operation

9.2.1Electric Panel

The electric panel should be inspected on a semi-annual basis for any loose electrical connections.

9.2.2Filters

Filters are usually the most neglected item in an environmental control system. In order to maintain efficient operation, they should be checked monthly and changed as required. ALWAYS TURN POWER OFF BEFORE REPLACING FILTERS.

Filters are replaced by opening the hinged door on the return air filter box.

55

Liebert® Mini-Mate2

Image 61
Contents Liebert Mini-Mate2 Page Table of Contents System Performance Microprocessor Controls Microprocessor ControlSystem OPERATION, Testing and Maintenance AlarmsTables Important Safety Instructions Liebert Mini-Mate2 Air-cooled systems-indoor centrifugal condensing units Product Model InformationPFH 0 67 a a L System configurations-50 Hz System configurations-60 HzIntroduction Evaporator Section-Split System Standard FEATURES-5 TON SystemsCondensing Unit Section-Split System Chilled Water UnitsSystem Controls Other Standard Control FeaturesReheat Switches and MotorsHumidifier SensorsOptional Configurations-Water/Glycol Condensing Units Optional Configurations-Prop Fan Condensing UnitsFree-Cooling Optional Configurations-Chilled Water Units SHIP-LOOSE ACCESSORIES-FIELD-INSTALLED Ship-Loose Accessories-Field-Installed Site Preparation and Installation Installation ConsiderationsRoom Preparation Air-cooled systems Location ConsiderationsUnit weights Ceiling Unit WeightsCooling Drycooler Cooling UnitsClose Coupled Installations Installing the Ceiling UnitsEquipment Inspection Upon Receipt Evaporator Air Distribution Filter BoxPiping Connections and Coolant Requirements Drain Line Connections for Ducted SystemsHumidifier Water Supply Line Evaporator external static pressureEquivalent lengths for various pipe fittings, ft m Recommended refrigerant line sizesEquivalent Pipe Liquid Suction Length, ft m Copper PipeVertical rise above evaporator/maximum Pipe length and condenser elevation relative to evaporatorVertical fall below evaporator Quick Connect Fittings Total refrigerant = Units and LinesRefrigerant charge Line charges refrigerant per 100 ft m of Type L copper tubeDPN000218 Electrical Connections Threaded rod and hardware kit installationControl Connections Power ConnectionsEvaporator unit electrical connections Close coupled installation Ducting Piping ConnectionsGeneral Considerations Considerations for Specific ApplicationsAIR-COOLED Dimensional Data AIR Cooled AIR-COOLED Weight, lb kg Outdoor Air-Cooled Condensing Unit InstallationModel # 60Hz 50Hz Rev Condensing Unit Fluid Requirements Water/Glycol Piping ConsiderationsRegulating Valve WATER/GLYCOL Dimensional Data WATER/GLYCOL DPN000214 Optional free-cooling coil 3-way valve on water/glycol units Hot Water Reheat CoilChecklist for Completed Installation Microprocessor Control Feature OverviewSetpoints Main Menu MenuStatus Active AlarmsTime DateRestart Time Delay Setup OperationShow DIP Switch 2 C/F DegreesSetup functions, default values and allowable ranges Change PasswordsFunction Default Range Calibrate SensorsAlarm Time Delay Alarm EnableCommon Alarm Enable Alarm default time delaysStandard Custom Alarm Messages Custom AlarmsCustom Text LCD Display ContrastEquipment Options Switches Run Diagnostics Available On Rev 1.001.0 and higherEquipment switch settings unit control board Switch settings wall box boardTest Control Board Test OutputsControl menu Wall box board Control board-inside evaporatorHumidity Control Temperature ControlSystem Performance Microprocessor Controls Humidification Operation Load Control FeaturesCommunications Alarms Alarms Definitions and TroubleshootingCustom Alarms High Head PressureHumidifier Problem Alarm TemperatureHigh Water Alarm Air-Cooled SystemsOptional/Custom Alarms Maintenance and Component Operation System TestingSystem OPERATION, Testing and Maintenance Air Distribution Blower SystemBlower Removal Refrigeration SystemDischarge Pressure Glycol Solution MaintenanceThermostatic Expansion Valve Air-Cooled Condensing UnitsHot gas bypass Hot Gas BypassCompressor Replacement Replacement ProceduresMechanical Failure Electrical FailureReplace a Failed Compressor Steam Generating Humidifier-Operation Procedures Humidifier control board DIP switch settings Humidifier Circuit Board AdjustmentsReplacing the Humidifier Canister AmpsMaintenance Inspection Checklist Troubleshooting TroubleshootingDisplay Problem Symptom Possible Cause Check Or Remedy Cooling cycle tooShort Display freezesPpor t Is t Ne tTwor k Care

MINI-MATE2 specifications

The Emerson MINI-MATE2 is a cutting-edge temperature and pressure monitoring device specifically designed for the needs of the refrigeration and HVAC industries. Known for its reliability and user-friendly interface, this compact unit serves as a key tool for technicians and facility managers looking to optimize system performance while ensuring compliance with safety standards.

One of the main features of the MINI-MATE2 is its advanced digital display, which allows users to easily monitor and interpret temperature and pressure readings in real-time. Its highly responsive sensors ensure accurate data collection, vital for maintaining optimal operating conditions. Moreover, the device supports a wide range of refrigerants, making it versatile for different applications, from walk-in coolers to commercial refrigeration systems.

The MINI-MATE2 utilizes state-of-the-art technology to enhance efficiency and performance. Equipped with Bluetooth connectivity, it allows for wireless communication with mobile devices, enabling technicians to track readings and receive alerts remotely. This feature not only improves convenience but also helps in quick decision-making, ensuring timely interventions when anomalies are detected.

Another significant characteristic is its robust construction. Built to withstand harsh environments, the MINI-MATE2 features a durable casing that protects it from physical impacts and environmental factors. This resilience ensures longevity, making it a cost-effective investment for any facility.

In addition, the MINI-MATE2 is designed with user-friendliness in mind. Its intuitive interface means that even technicians with limited experience can easily navigate its functionalities. Quick setup and straightforward operation allow for rapid adoption and extensive use in a variety of settings.

Finally, the MINI-MATE2 also includes built-in data logging capabilities. Users can record historical data for analysis and reporting purposes, which is essential for performing trend analysis and identifying potential issues before they escalate. By providing a comprehensive overview of system performance, the MINI-MATE2 empowers users to make informed decisions that can lead to improved energy efficiency and reduced operational costs.

Overall, the Emerson MINI-MATE2 is an indispensable tool for modern refrigeration and HVAC applications, combining cutting-edge technology, user-friendly design, and essential features to support efficient system management.