Microprocessor Control

Equipment Options Switches

Equipment options are selected and enabled using DIP switches 1 through 7. These are located on the control board near TB1. These switches are factory-set and should not require any user changes. The setting and function of the switches can be individually read on the LCD display.

NOTE

In order to update the dip switch settings, power must be cycled off, then on, from the unit disconnect switch.

Table 20 Equipment switch settings (unit control board)

Switch

OFF Position

ON Position

 

 

 

1

Compressor

Chilled Water

 

 

 

2

Standard Reheat

SCR Reheat

 

 

 

3

No Modulating Valve

Modulating CW Valve

 

 

 

4

Not Used

Not Used

 

 

 

5

Enable Reheat

Disable Reheat

 

 

 

6

Enable Humidifier

Disable Humidifier

 

 

 

7

Enable Dehumidifier

Disable Dehumidifier

 

 

 

8

Electric Reheat

Gas Reheat

 

 

 

Table 21 Switch settings (wall box board)

Switch

OFF Position

ON Position

 

 

 

1

Disable Beeper

Enable Beeper

 

 

 

2

Not Used

Not Used

 

 

 

3

Not Used

Not Used

 

 

 

4

Not Used

Not Used

 

 

 

5

Not Used

Not Used

 

 

 

6

Not Used

Not Used

 

 

 

7

Disable Setback

Enable Setback

 

 

 

8

Enable Password

Disable Password

 

 

 

6.17Run Diagnostics (Available On Rev 1.001.0 and higher)

By selecting Run Diagnostics, maintenance personnel can check system inputs, outputs and conduct a test of the microcontroller circuit board from the wall box control. A review of the system inputs and the microcontroller test can be done without interrupting normal operation.

Show Inputs

With the unit on and the fan running, the input states may be displayed for the following devices:

High Water Alarm: Normally off unless High Water Alarm is active.

High Head Pressure Alarm: Normally off unless High head Pressure alarm is active.

Custom alarm #1: Normally off unless this special customer selectable alarm is active.

Custom alarm #2: Normally off unless this special customer selectable alarm is active.

Power: Normally on unless unit is turned off through the wall box or any of the following optional

devices: High Temperature Sensor, Smoke Sensor, High Water Alarm or Remote Shutdown

Liebert® Mini-Mate2

46

Image 52
Contents Liebert Mini-Mate2 Page Table of Contents Microprocessor Control System Performance Microprocessor ControlsAlarms System OPERATION, Testing and MaintenanceTables Important Safety Instructions Liebert Mini-Mate2 Product Model Information Air-cooled systems-indoor centrifugal condensing unitsPFH 0 67 a a L System configurations-60 Hz System configurations-50 HzIntroduction Standard FEATURES-5 TON Systems Evaporator Section-Split SystemCondensing Unit Section-Split System Chilled Water UnitsOther Standard Control Features System ControlsSwitches and Motors ReheatHumidifier SensorsOptional Configurations-Water/Glycol Condensing Units Optional Configurations-Prop Fan Condensing UnitsFree-Cooling Optional Configurations-Chilled Water Units SHIP-LOOSE ACCESSORIES-FIELD-INSTALLED Ship-Loose Accessories-Field-Installed Site Preparation and Installation Installation ConsiderationsRoom Preparation Location Considerations Air-cooled systemsCeiling Unit Weights Unit weightsCooling Drycooler Cooling UnitsInstalling the Ceiling Units Close Coupled InstallationsEquipment Inspection Upon Receipt Evaporator Air Distribution Filter BoxConnections for Ducted Systems Piping Connections and Coolant Requirements Drain LineHumidifier Water Supply Line Evaporator external static pressureRecommended refrigerant line sizes Equivalent lengths for various pipe fittings, ft mEquivalent Pipe Liquid Suction Length, ft m Copper PipeVertical rise above evaporator/maximum Pipe length and condenser elevation relative to evaporatorVertical fall below evaporator Total refrigerant = Units and Lines Quick Connect FittingsRefrigerant charge Line charges refrigerant per 100 ft m of Type L copper tubeDPN000218 Threaded rod and hardware kit installation Electrical ConnectionsPower Connections Control ConnectionsEvaporator unit electrical connections Close coupled installation Piping Connections DuctingGeneral Considerations Considerations for Specific ApplicationsAIR-COOLED Dimensional Data AIR Cooled AIR-COOLED Weight, lb kg Outdoor Air-Cooled Condensing Unit InstallationModel # 60Hz 50Hz Rev Condensing Unit Fluid Requirements Water/Glycol Piping ConsiderationsRegulating Valve WATER/GLYCOL Dimensional Data WATER/GLYCOL DPN000214 Hot Water Reheat Coil Optional free-cooling coil 3-way valve on water/glycol unitsChecklist for Completed Installation Feature Overview Microprocessor ControlMain Menu Menu SetpointsActive Alarms StatusTime DateSetup Operation Restart Time DelayShow DIP Switch 2 C/F DegreesChange Passwords Setup functions, default values and allowable rangesFunction Default Range Calibrate SensorsAlarm Enable Alarm Time DelayCommon Alarm Enable Alarm default time delaysCustom Alarms Standard Custom Alarm MessagesCustom Text LCD Display ContrastRun Diagnostics Available On Rev 1.001.0 and higher Equipment Options SwitchesEquipment switch settings unit control board Switch settings wall box boardTest Outputs Test Control BoardControl menu Control board-inside evaporator Wall box boardHumidity Control Temperature ControlSystem Performance Microprocessor Controls Humidification Operation Load Control FeaturesCommunications Alarms Definitions and Troubleshooting AlarmsCustom Alarms High Head PressureTemperature Humidifier Problem AlarmHigh Water Alarm Air-Cooled SystemsOptional/Custom Alarms Maintenance and Component Operation System TestingSystem OPERATION, Testing and Maintenance Blower System Air DistributionBlower Removal Refrigeration SystemGlycol Solution Maintenance Discharge PressureThermostatic Expansion Valve Air-Cooled Condensing UnitsHot Gas Bypass Hot gas bypassReplacement Procedures Compressor ReplacementMechanical Failure Electrical FailureReplace a Failed Compressor Steam Generating Humidifier-Operation Procedures Humidifier Circuit Board Adjustments Humidifier control board DIP switch settingsReplacing the Humidifier Canister AmpsMaintenance Inspection Checklist Troubleshooting TroubleshootingSymptom Possible Cause Check Or Remedy Cooling cycle too Display ProblemShort Display freezesNe t Ppor t Is tTwor k Care

MINI-MATE2 specifications

The Emerson MINI-MATE2 is a cutting-edge temperature and pressure monitoring device specifically designed for the needs of the refrigeration and HVAC industries. Known for its reliability and user-friendly interface, this compact unit serves as a key tool for technicians and facility managers looking to optimize system performance while ensuring compliance with safety standards.

One of the main features of the MINI-MATE2 is its advanced digital display, which allows users to easily monitor and interpret temperature and pressure readings in real-time. Its highly responsive sensors ensure accurate data collection, vital for maintaining optimal operating conditions. Moreover, the device supports a wide range of refrigerants, making it versatile for different applications, from walk-in coolers to commercial refrigeration systems.

The MINI-MATE2 utilizes state-of-the-art technology to enhance efficiency and performance. Equipped with Bluetooth connectivity, it allows for wireless communication with mobile devices, enabling technicians to track readings and receive alerts remotely. This feature not only improves convenience but also helps in quick decision-making, ensuring timely interventions when anomalies are detected.

Another significant characteristic is its robust construction. Built to withstand harsh environments, the MINI-MATE2 features a durable casing that protects it from physical impacts and environmental factors. This resilience ensures longevity, making it a cost-effective investment for any facility.

In addition, the MINI-MATE2 is designed with user-friendliness in mind. Its intuitive interface means that even technicians with limited experience can easily navigate its functionalities. Quick setup and straightforward operation allow for rapid adoption and extensive use in a variety of settings.

Finally, the MINI-MATE2 also includes built-in data logging capabilities. Users can record historical data for analysis and reporting purposes, which is essential for performing trend analysis and identifying potential issues before they escalate. By providing a comprehensive overview of system performance, the MINI-MATE2 empowers users to make informed decisions that can lead to improved energy efficiency and reduced operational costs.

Overall, the Emerson MINI-MATE2 is an indispensable tool for modern refrigeration and HVAC applications, combining cutting-edge technology, user-friendly design, and essential features to support efficient system management.