Emerson MINI-MATE2 Discharge Pressure, Thermostatic Expansion Valve, Air-Cooled Condensing Units

Page 63

System Operation, Testing and Maintenance

Discharge Pressure

The discharge pressure will vary greatly with load and ambient conditions (Table 23). The high- pressure switch will shut the compressor down at its cut-out setting.

Table 23 Typical discharge pressure

System Design

Discharge Pressure, psig (kPa)

 

 

Air-Cooled

200-300 (1380-2070)

 

 

Water-Cooled 65 to 85°F water

200-250 (1380-1725)

(18 to 29.4°C)

 

Glycol-Cooled

250-350 (1725-2415)

 

 

High-Pressure Cut-Out

400 (2760)

 

 

Thermostatic Expansion Valve

The thermostatic expansion valve keeps the evaporator supplied with enough refrigerant to satisfy load conditions. Proper valve operation can be determined by measuring superheat level. If too little refrigerant is being fed to the evaporator, then the superheat will be high. Conversely, if too much refrigerant is being supplied, then the superheat will be low. The correct superheat setting is between 10 and 15°F (5.6 and 8.3°C).

Air-Cooled Condensing Units

Restricted airflow through the condenser coil will reduce the operating efficiency of the unit. Additionally, it can result in high compressor head pressure and loss of cooling. Using compressed air or commercial coil cleaner, clean the condenser coil of all debris that will inhibit airflow. In winter, do not permit snow to accumulate around the side or underneath the condenser. At the same time check for bent or damaged coil fins and repair as necessary. Check all refrigerant lines and capillaries for vibration and support as necessary. Carefully inspect all refrigerant lines for signs of oil leaks.

Coaxial Condensers (Water/Glycol-Cooled Condensing Units)

Each water- or glycol-cooled condensing unit has a coaxial condenser consisting of an exterior steel tube and an interior copper tube. If the water supply is clean, coaxial condensers do not normally require maintenance or replacement. Should your system begin to operate at high head pressure with reduced capacity and all other causes have been eliminated, the condenser may be obstructed or fouled and should be replaced.

Regulating Valves (Water/Glycol Condensing Units)

The water regulating valve automatically regulate the amount of fluid necessary to remove the heat from the refrigeration system, permitting more fluid to flow when load conditions are high and less fluid to flow when load conditions are low.

The water regulating valve is designed to begin opening at 180 psi (1240 kPa) and to be fully opened at 240 psi (1655 kPa). The valve is factory-set and should not need adjustment.

Glycol Solution Maintenance

It is difficult to establish a specific schedule of inhibitor maintenance since the rate of inhibitor depletion depends upon local water conditions. Analysis of water samples at time of installation and every six (6) months should help to establish a pattern of depletion. A visual inspection of the solution and filter residue is often helpful in judging whether or not active corrosion is occurring. The complexity of problems caused by water requires expert advice from a water treatment specialist plus a regular maintenance program schedule. It is important to note that improper use of water treatment chemicals can cause severe problems.

Proper inhibitor maintenance must be performed in order to prevent corrosion of the glycol system. Consult your glycol manufacturer for proper testing and maintenance procedures. Do not mix products from different manufacturers.

57

Liebert® Mini-Mate2

Image 63
Contents Liebert Mini-Mate2 Page Table of Contents System Performance Microprocessor Controls Microprocessor ControlSystem OPERATION, Testing and Maintenance AlarmsTables Important Safety Instructions Liebert Mini-Mate2 Air-cooled systems-indoor centrifugal condensing units Product Model InformationPFH 0 67 a a L System configurations-50 Hz System configurations-60 HzIntroduction Chilled Water Units Standard FEATURES-5 TON SystemsEvaporator Section-Split System Condensing Unit Section-Split SystemSystem Controls Other Standard Control FeaturesSensors Switches and MotorsReheat HumidifierOptional Configurations-Prop Fan Condensing Units Optional Configurations-Water/Glycol Condensing UnitsFree-Cooling Optional Configurations-Chilled Water Units SHIP-LOOSE ACCESSORIES-FIELD-INSTALLED Ship-Loose Accessories-Field-Installed Installation Considerations Site Preparation and InstallationRoom Preparation Air-cooled systems Location ConsiderationsCooling Units Ceiling Unit WeightsUnit weights Cooling DrycoolerEvaporator Air Distribution Filter Box Installing the Ceiling UnitsClose Coupled Installations Equipment Inspection Upon ReceiptEvaporator external static pressure Connections for Ducted SystemsPiping Connections and Coolant Requirements Drain Line Humidifier Water Supply LineCopper Pipe Recommended refrigerant line sizesEquivalent lengths for various pipe fittings, ft m Equivalent Pipe Liquid Suction Length, ft mPipe length and condenser elevation relative to evaporator Vertical rise above evaporator/maximumVertical fall below evaporator Line charges refrigerant per 100 ft m of Type L copper tube Total refrigerant = Units and LinesQuick Connect Fittings Refrigerant chargeDPN000218 Electrical Connections Threaded rod and hardware kit installationControl Connections Power ConnectionsEvaporator unit electrical connections Close coupled installation Considerations for Specific Applications Piping ConnectionsDucting General ConsiderationsAIR-COOLED Dimensional Data AIR Cooled AIR-COOLED Outdoor Air-Cooled Condensing Unit Installation Weight, lb kgModel # 60Hz 50Hz Rev Water/Glycol Piping Considerations Condensing Unit Fluid RequirementsRegulating Valve WATER/GLYCOL Dimensional Data WATER/GLYCOL DPN000214 Optional free-cooling coil 3-way valve on water/glycol units Hot Water Reheat CoilChecklist for Completed Installation Microprocessor Control Feature OverviewSetpoints Main Menu MenuDate Active AlarmsStatus Time2 C/F Degrees Setup OperationRestart Time Delay Show DIP SwitchCalibrate Sensors Change PasswordsSetup functions, default values and allowable ranges Function Default RangeAlarm default time delays Alarm EnableAlarm Time Delay Common Alarm EnableLCD Display Contrast Custom AlarmsStandard Custom Alarm Messages Custom TextSwitch settings wall box board Run Diagnostics Available On Rev 1.001.0 and higherEquipment Options Switches Equipment switch settings unit control boardTest Control Board Test OutputsControl menu Wall box board Control board-inside evaporatorTemperature Control Humidity ControlSystem Performance Microprocessor Controls Load Control Features Humidification OperationCommunications High Head Pressure Alarms Definitions and TroubleshootingAlarms Custom AlarmsAir-Cooled Systems TemperatureHumidifier Problem Alarm High Water AlarmOptional/Custom Alarms System Testing Maintenance and Component OperationSystem OPERATION, Testing and Maintenance Refrigeration System Blower SystemAir Distribution Blower RemovalAir-Cooled Condensing Units Glycol Solution MaintenanceDischarge Pressure Thermostatic Expansion ValveHot gas bypass Hot Gas BypassElectrical Failure Replacement ProceduresCompressor Replacement Mechanical FailureReplace a Failed Compressor Steam Generating Humidifier-Operation Procedures Amps Humidifier Circuit Board AdjustmentsHumidifier control board DIP switch settings Replacing the Humidifier CanisterMaintenance Inspection Checklist Troubleshooting TroubleshootingDisplay freezes Symptom Possible Cause Check Or Remedy Cooling cycle tooDisplay Problem ShortCare Ne tPpor t Is t Twor k

MINI-MATE2 specifications

The Emerson MINI-MATE2 is a cutting-edge temperature and pressure monitoring device specifically designed for the needs of the refrigeration and HVAC industries. Known for its reliability and user-friendly interface, this compact unit serves as a key tool for technicians and facility managers looking to optimize system performance while ensuring compliance with safety standards.

One of the main features of the MINI-MATE2 is its advanced digital display, which allows users to easily monitor and interpret temperature and pressure readings in real-time. Its highly responsive sensors ensure accurate data collection, vital for maintaining optimal operating conditions. Moreover, the device supports a wide range of refrigerants, making it versatile for different applications, from walk-in coolers to commercial refrigeration systems.

The MINI-MATE2 utilizes state-of-the-art technology to enhance efficiency and performance. Equipped with Bluetooth connectivity, it allows for wireless communication with mobile devices, enabling technicians to track readings and receive alerts remotely. This feature not only improves convenience but also helps in quick decision-making, ensuring timely interventions when anomalies are detected.

Another significant characteristic is its robust construction. Built to withstand harsh environments, the MINI-MATE2 features a durable casing that protects it from physical impacts and environmental factors. This resilience ensures longevity, making it a cost-effective investment for any facility.

In addition, the MINI-MATE2 is designed with user-friendliness in mind. Its intuitive interface means that even technicians with limited experience can easily navigate its functionalities. Quick setup and straightforward operation allow for rapid adoption and extensive use in a variety of settings.

Finally, the MINI-MATE2 also includes built-in data logging capabilities. Users can record historical data for analysis and reporting purposes, which is essential for performing trend analysis and identifying potential issues before they escalate. By providing a comprehensive overview of system performance, the MINI-MATE2 empowers users to make informed decisions that can lead to improved energy efficiency and reduced operational costs.

Overall, the Emerson MINI-MATE2 is an indispensable tool for modern refrigeration and HVAC applications, combining cutting-edge technology, user-friendly design, and essential features to support efficient system management.