Emerson MINI-MATE2 user manual Installation Considerations, Site Preparation and Installation

Page 20

Site Preparation and Installation

5.0SITE PREPARATION AND INSTALLATION

NOTE

Before installing unit, determine whether any building alterations are required to run piping, wiring and duct work. Carefully follow all unit dimensional drawings and refer to the submittal engineering dimensional drawings of individual units for proper clearances.

5.1Installation Considerations

The evaporator unit is usually mounted above the suspended ceiling in the space to be conditioned. Ducted systems may be located in a different room. Refer to Figure 8 and Figure 9 for possible configurations. The condensing unit may be:

Indoor Air-Cooled Centrifugal Fan Condensing Unit mounted remotely or close coupled to the evaporator in the ceiling space.

Outdoor Air-Cooled Propeller Fan Condensing Unit.

Water/Glycol Cooled Condensing Unit, mounted remotely or close coupled to the evaporator.

Table 3

Application limits, evaporator and chilled water units*

 

 

 

 

 

Input Voltage

Range of Return Air Conditions to Unit

 

 

 

 

 

 

Min

Max

Dry Bulb Temperature

Relative Humidity

 

 

 

 

 

 

-5%

+10%

65°F to 85°F

20% to 80%

 

 

 

(18°C to 29°C)

 

 

*Unit will operate at these conditions but will not control to these extremes.

Table 4 Application limits, indoor and outdoor air-cooled condensing units

Input

 

Entering Dry Bulb Air

Voltage

Condensing

Temperature

 

 

 

 

Min

Max

Units

Min

Max

 

 

 

 

 

-5%

+10%

Outdoor Prop Fan

-30°F (-34°C)

120°F (49°C)

 

 

Condensing Unit

 

 

 

 

Indoor Air-Cooled

-20°F (-29°C)

115°F (46°C)

 

 

Centrifugal

 

 

 

 

Condensing Unit

 

 

Table 5 Application limits, indoor water/glycol cooled condensing units

Input Voltage

Entering Fluid Temperature

 

 

 

 

Min

Max

Min

Max

 

 

 

 

-5%

+10%

65°F (18.3°C) *

115°F (46°C)

*Operation below 65°F (18°C) may result in reduced valve life and fluid noise.

5.1.1Room Preparation

The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the ceiling and walls can be a polyethylene film. Paint on concrete walls and floors should contain either rubber or plastic.

NOTE

The single most important requirement for maintaining environmental control in the conditioned room is the vapor barrier.

Outside or fresh air should be kept to a minimum when tight temperature and humidity control is required. Outside air adds to the cooling, heating, dehumidifying and humidifying loads of the site. Doors should be properly sealed to minimize leaks and should not contain ventilation grilles.

Liebert® Mini-Mate2

14

Image 20
Contents Liebert Mini-Mate2 Page Table of Contents Microprocessor Control System Performance Microprocessor ControlsAlarms System OPERATION, Testing and MaintenanceTables Important Safety Instructions Liebert Mini-Mate2 Product Model Information Air-cooled systems-indoor centrifugal condensing unitsPFH 0 67 a a L System configurations-60 Hz System configurations-50 HzIntroduction Standard FEATURES-5 TON Systems Evaporator Section-Split SystemCondensing Unit Section-Split System Chilled Water UnitsOther Standard Control Features System ControlsSwitches and Motors ReheatHumidifier SensorsFree-Cooling Optional Configurations-Prop Fan Condensing UnitsOptional Configurations-Water/Glycol Condensing Units Optional Configurations-Chilled Water Units SHIP-LOOSE ACCESSORIES-FIELD-INSTALLED Ship-Loose Accessories-Field-Installed Room Preparation Installation ConsiderationsSite Preparation and Installation Location Considerations Air-cooled systemsCeiling Unit Weights Unit weightsCooling Drycooler Cooling UnitsInstalling the Ceiling Units Close Coupled InstallationsEquipment Inspection Upon Receipt Evaporator Air Distribution Filter BoxConnections for Ducted Systems Piping Connections and Coolant Requirements Drain LineHumidifier Water Supply Line Evaporator external static pressureRecommended refrigerant line sizes Equivalent lengths for various pipe fittings, ft mEquivalent Pipe Liquid Suction Length, ft m Copper PipeVertical fall below evaporator Pipe length and condenser elevation relative to evaporatorVertical rise above evaporator/maximum Total refrigerant = Units and Lines Quick Connect FittingsRefrigerant charge Line charges refrigerant per 100 ft m of Type L copper tubeDPN000218 Threaded rod and hardware kit installation Electrical ConnectionsPower Connections Control ConnectionsEvaporator unit electrical connections Close coupled installation Piping Connections DuctingGeneral Considerations Considerations for Specific ApplicationsAIR-COOLED Dimensional Data AIR Cooled AIR-COOLED Model # 60Hz 50Hz Outdoor Air-Cooled Condensing Unit InstallationWeight, lb kg Rev Regulating Valve Water/Glycol Piping ConsiderationsCondensing Unit Fluid Requirements WATER/GLYCOL Dimensional Data WATER/GLYCOL DPN000214 Hot Water Reheat Coil Optional free-cooling coil 3-way valve on water/glycol unitsChecklist for Completed Installation Feature Overview Microprocessor ControlMain Menu Menu SetpointsActive Alarms StatusTime DateSetup Operation Restart Time DelayShow DIP Switch 2 C/F DegreesChange Passwords Setup functions, default values and allowable rangesFunction Default Range Calibrate SensorsAlarm Enable Alarm Time DelayCommon Alarm Enable Alarm default time delaysCustom Alarms Standard Custom Alarm MessagesCustom Text LCD Display ContrastRun Diagnostics Available On Rev 1.001.0 and higher Equipment Options SwitchesEquipment switch settings unit control board Switch settings wall box boardTest Outputs Test Control BoardControl menu Control board-inside evaporator Wall box boardSystem Performance Microprocessor Controls Temperature ControlHumidity Control Communications Load Control FeaturesHumidification Operation Alarms Definitions and Troubleshooting AlarmsCustom Alarms High Head PressureTemperature Humidifier Problem AlarmHigh Water Alarm Air-Cooled SystemsOptional/Custom Alarms System OPERATION, Testing and Maintenance System TestingMaintenance and Component Operation Blower System Air DistributionBlower Removal Refrigeration SystemGlycol Solution Maintenance Discharge PressureThermostatic Expansion Valve Air-Cooled Condensing UnitsHot Gas Bypass Hot gas bypassReplacement Procedures Compressor ReplacementMechanical Failure Electrical FailureReplace a Failed Compressor Steam Generating Humidifier-Operation Procedures Humidifier Circuit Board Adjustments Humidifier control board DIP switch settingsReplacing the Humidifier Canister AmpsMaintenance Inspection Checklist Troubleshooting TroubleshootingSymptom Possible Cause Check Or Remedy Cooling cycle too Display ProblemShort Display freezesNe t Ppor t Is tTwor k Care

MINI-MATE2 specifications

The Emerson MINI-MATE2 is a cutting-edge temperature and pressure monitoring device specifically designed for the needs of the refrigeration and HVAC industries. Known for its reliability and user-friendly interface, this compact unit serves as a key tool for technicians and facility managers looking to optimize system performance while ensuring compliance with safety standards.

One of the main features of the MINI-MATE2 is its advanced digital display, which allows users to easily monitor and interpret temperature and pressure readings in real-time. Its highly responsive sensors ensure accurate data collection, vital for maintaining optimal operating conditions. Moreover, the device supports a wide range of refrigerants, making it versatile for different applications, from walk-in coolers to commercial refrigeration systems.

The MINI-MATE2 utilizes state-of-the-art technology to enhance efficiency and performance. Equipped with Bluetooth connectivity, it allows for wireless communication with mobile devices, enabling technicians to track readings and receive alerts remotely. This feature not only improves convenience but also helps in quick decision-making, ensuring timely interventions when anomalies are detected.

Another significant characteristic is its robust construction. Built to withstand harsh environments, the MINI-MATE2 features a durable casing that protects it from physical impacts and environmental factors. This resilience ensures longevity, making it a cost-effective investment for any facility.

In addition, the MINI-MATE2 is designed with user-friendliness in mind. Its intuitive interface means that even technicians with limited experience can easily navigate its functionalities. Quick setup and straightforward operation allow for rapid adoption and extensive use in a variety of settings.

Finally, the MINI-MATE2 also includes built-in data logging capabilities. Users can record historical data for analysis and reporting purposes, which is essential for performing trend analysis and identifying potential issues before they escalate. By providing a comprehensive overview of system performance, the MINI-MATE2 empowers users to make informed decisions that can lead to improved energy efficiency and reduced operational costs.

Overall, the Emerson MINI-MATE2 is an indispensable tool for modern refrigeration and HVAC applications, combining cutting-edge technology, user-friendly design, and essential features to support efficient system management.