Emerson MINI-MATE2 Alarms Definitions and Troubleshooting, Custom Alarms, High Head Pressure

Page 58

Alarms

8.0ALARMS

The microprocessor control system will audibly and visually signal all ENABLED Alarms (including two (2) custom alarms). These special alarms can be chosen from the optional alarm list and/or can have their own fully custom text. The custom alarm inputs are contact closures wired from terminal TB1-1 through a normally open contact to either TB1-2 (alarm 1) or TB1-3 (alarm 2). The alarms can be enabled or disabled (refer to 6.0 - Microprocessor Control) and a time delay of 0-255 seconds can be set. The alarms can also be programmed to either sound the alarm & activate the common alarm relay OR to sound the alarm only.

When a new alarm occurs, it is displayed on the screen and the audible alarm is activated. (If communicating with a Liebert Site Product, the alarm is also transmitted.) The message “PRESS ALARM SILENCE” will prompt the operator to silence the alarm. After the alarm is silenced, the display will return to the Normal Status Display. Alarms can be reviewed by selecting the “ACTIVE ALARMS” feature. The alarms can also be silenced through communications with a Liebert Site Product unit.

Many alarms will reset automatically when the alarm condition is no longer represented and only after it has been acknowledged by being “Silenced.” The exceptions are:

1.software alarms, i.e., Loss of Power and Short Cycle alarms will reset automatically 30 seconds after being silenced or acknowledged

2.specific alarms monitoring overload or high pressure switches may require a manual reset depending upon the model

8.1Alarms: Definitions and Troubleshooting

The following list provides a definition and troubleshooting suggestions for each type of alarm. Refer to 11.0 - Troubleshooting for additional details. If you need further assistance, contact your Liebert supplier. THE CUSTOMER MUST SPECIFY ALARM(S) AT THE TIME OF ORDER. OTHER DEVICES AND WIRING MAY BE REQUIRED AT THE FACTORY FOR SOME OF THE ALARMS.

8.1.1Custom Alarms

Custom alarm(s) messages are programmed at the LCD display. The message displayed may be included in a list of provided alarms or it may be customized text (for up to 2 alarms). IF CUSTOMIZED TEXT IS USED, MAINTENANCE PERSONNEL SHOULD BE INFORMED OF THE ALARM FUNCTION AND THE REQUIRED ACTION.

8.1.2High Head Pressure

Compressor head pressure is monitored with a pressure-sensor switch. (One SPDT pressure switch is used) for the compressor in the unit.

If head pressure exceeds 400 psig (2785 kPa), the switch opens the compressor contactor and sends an input signal to the control. The high head pressure condition is acknowledged by pressing the Alarm Silence button on the wall box, which will clear the alarm if the high head pressure condition no longer exists. If the compressor is Off for 1 hour, the control goes into a special cold start mode. In the cold start mode on a call for cooling or dehumidification, the liquid line solenoid valve (LLSV) is energized. If the high pressure switch does NOT trip within 10 seconds, the control returns to normal operation of monitoring the high head pressure switch for three occurrences in a 12 hour period. It is a rolling timer, and after the third high head alarm occurs and is acknowledged by the user, it will lock Off the compressor.

If while in the cold start mode, the high head pressure switch DOES trip within 10 seconds of the activation of the LLSV, the control does not annunciate the alarm. The control will turn Off the LLSV and delay 10 seconds. The control will permit this occurrence two more times or a total of three times. If on the fourth try, the high head pressure switch trips within 10 seconds, the control will annunciate the alarm, turn Off the LLSV, wait for the user to acknowledge the alarm and hold the compressor Off for 3 minutes, the length of the normal short cycle control. The control will permit this occurrence three times. On the third occurrence, the control will lock the compressor Off until the control power is reset.

Liebert® Mini-Mate2

52

Image 58
Contents Liebert Mini-Mate2 Page Table of Contents Microprocessor Control System Performance Microprocessor ControlsAlarms System OPERATION, Testing and MaintenanceTables Important Safety Instructions Liebert Mini-Mate2 Product Model Information Air-cooled systems-indoor centrifugal condensing unitsPFH 0 67 a a L System configurations-60 Hz System configurations-50 HzIntroduction Condensing Unit Section-Split System Standard FEATURES-5 TON SystemsEvaporator Section-Split System Chilled Water UnitsOther Standard Control Features System ControlsHumidifier Switches and MotorsReheat SensorsOptional Configurations-Water/Glycol Condensing Units Optional Configurations-Prop Fan Condensing UnitsFree-Cooling Optional Configurations-Chilled Water Units SHIP-LOOSE ACCESSORIES-FIELD-INSTALLED Ship-Loose Accessories-Field-Installed Site Preparation and Installation Installation ConsiderationsRoom Preparation Location Considerations Air-cooled systemsCooling Drycooler Ceiling Unit WeightsUnit weights Cooling UnitsEquipment Inspection Upon Receipt Installing the Ceiling UnitsClose Coupled Installations Evaporator Air Distribution Filter BoxHumidifier Water Supply Line Connections for Ducted SystemsPiping Connections and Coolant Requirements Drain Line Evaporator external static pressureEquivalent Pipe Liquid Suction Length, ft m Recommended refrigerant line sizesEquivalent lengths for various pipe fittings, ft m Copper PipeVertical rise above evaporator/maximum Pipe length and condenser elevation relative to evaporatorVertical fall below evaporator Refrigerant charge Total refrigerant = Units and LinesQuick Connect Fittings Line charges refrigerant per 100 ft m of Type L copper tubeDPN000218 Threaded rod and hardware kit installation Electrical ConnectionsPower Connections Control ConnectionsEvaporator unit electrical connections Close coupled installation General Considerations Piping ConnectionsDucting Considerations for Specific ApplicationsAIR-COOLED Dimensional Data AIR Cooled AIR-COOLED Weight, lb kg Outdoor Air-Cooled Condensing Unit InstallationModel # 60Hz 50Hz Rev Condensing Unit Fluid Requirements Water/Glycol Piping ConsiderationsRegulating Valve WATER/GLYCOL Dimensional Data WATER/GLYCOL DPN000214 Hot Water Reheat Coil Optional free-cooling coil 3-way valve on water/glycol unitsChecklist for Completed Installation Feature Overview Microprocessor ControlMain Menu Menu SetpointsTime Active AlarmsStatus DateShow DIP Switch Setup OperationRestart Time Delay 2 C/F DegreesFunction Default Range Change PasswordsSetup functions, default values and allowable ranges Calibrate SensorsCommon Alarm Enable Alarm EnableAlarm Time Delay Alarm default time delaysCustom Text Custom AlarmsStandard Custom Alarm Messages LCD Display ContrastEquipment switch settings unit control board Run Diagnostics Available On Rev 1.001.0 and higherEquipment Options Switches Switch settings wall box boardTest Outputs Test Control BoardControl menu Control board-inside evaporator Wall box boardHumidity Control Temperature ControlSystem Performance Microprocessor Controls Humidification Operation Load Control FeaturesCommunications Custom Alarms Alarms Definitions and TroubleshootingAlarms High Head PressureHigh Water Alarm TemperatureHumidifier Problem Alarm Air-Cooled SystemsOptional/Custom Alarms Maintenance and Component Operation System TestingSystem OPERATION, Testing and Maintenance Blower Removal Blower SystemAir Distribution Refrigeration SystemThermostatic Expansion Valve Glycol Solution MaintenanceDischarge Pressure Air-Cooled Condensing UnitsHot Gas Bypass Hot gas bypassMechanical Failure Replacement ProceduresCompressor Replacement Electrical FailureReplace a Failed Compressor Steam Generating Humidifier-Operation Procedures Replacing the Humidifier Canister Humidifier Circuit Board AdjustmentsHumidifier control board DIP switch settings AmpsMaintenance Inspection Checklist Troubleshooting TroubleshootingShort Symptom Possible Cause Check Or Remedy Cooling cycle tooDisplay Problem Display freezesTwor k Ne tPpor t Is t Care

MINI-MATE2 specifications

The Emerson MINI-MATE2 is a cutting-edge temperature and pressure monitoring device specifically designed for the needs of the refrigeration and HVAC industries. Known for its reliability and user-friendly interface, this compact unit serves as a key tool for technicians and facility managers looking to optimize system performance while ensuring compliance with safety standards.

One of the main features of the MINI-MATE2 is its advanced digital display, which allows users to easily monitor and interpret temperature and pressure readings in real-time. Its highly responsive sensors ensure accurate data collection, vital for maintaining optimal operating conditions. Moreover, the device supports a wide range of refrigerants, making it versatile for different applications, from walk-in coolers to commercial refrigeration systems.

The MINI-MATE2 utilizes state-of-the-art technology to enhance efficiency and performance. Equipped with Bluetooth connectivity, it allows for wireless communication with mobile devices, enabling technicians to track readings and receive alerts remotely. This feature not only improves convenience but also helps in quick decision-making, ensuring timely interventions when anomalies are detected.

Another significant characteristic is its robust construction. Built to withstand harsh environments, the MINI-MATE2 features a durable casing that protects it from physical impacts and environmental factors. This resilience ensures longevity, making it a cost-effective investment for any facility.

In addition, the MINI-MATE2 is designed with user-friendliness in mind. Its intuitive interface means that even technicians with limited experience can easily navigate its functionalities. Quick setup and straightforward operation allow for rapid adoption and extensive use in a variety of settings.

Finally, the MINI-MATE2 also includes built-in data logging capabilities. Users can record historical data for analysis and reporting purposes, which is essential for performing trend analysis and identifying potential issues before they escalate. By providing a comprehensive overview of system performance, the MINI-MATE2 empowers users to make informed decisions that can lead to improved energy efficiency and reduced operational costs.

Overall, the Emerson MINI-MATE2 is an indispensable tool for modern refrigeration and HVAC applications, combining cutting-edge technology, user-friendly design, and essential features to support efficient system management.