Emerson MINI-MATE2 Setup Operation, Restart Time Delay, 2 C/F Degrees, Humidity Control Method

Page 48

Microprocessor Control

6.9Setup Operation

Selecting Setpoint/Setup from the Main Menu will display the following selections:

RESTART TIME DELAY

C/F DEGREES

HUMIDITY CONTROL METHOD

SHOW DIPSWITCH

CW FLUSH

VALVE TIME

Use the Up and Down arrows to scroll through the submenu. Press Enter to select a particular function.

6.9.1Restart Time Delay

This function delays unit restart after main power is restored to the unit. If several systems are operating, the time delays should be set to different values to cause a sequential start. Delay can be set from 0.1 minutes to 9.9 minutes (6 seconds to 594 seconds). Setting the value to zero (0) will prevent the unit from restarting when power is restored. In this case, the unit must be restarted manually by pressing the “ON/OFF” button on the keypad.

6.9.2C/F Degrees

The control may be selected to show readings and setpoints in either degrees Fahrenheit (°F) or Celsius (°C). To change the value use Enter to select this function, then use the Up and Down arrows to change the value. Press Enter to store the value.

6.9.3Humidity Control Method

The operator may select either relative (direct) or absolute (predictive) humidity control. If “relative” is selected, the RH control is taken directly from the RH sensor. If “absolute” is selected, the RH control is automatically adjusted whenever return air temperature deviates from the desired temperature setpoint (i.e., predictive humidity control). The LCD display will indicate percentage relative humidity for both methods of control. If the “absolute” feature is selected, the adjusted humidity reading will also be shown. When utilizing the predictive humidity control feature, the humidity level is automatically adjusted ~2% RH for each degree difference between the return air temperature and the temperature setpoint.

Unnecessary dehumidification can result when overcooling occurs during a dehumidification cycle. This is due to a higher than normal RH reading caused by overcooling the room (about 2% RH for each degree of overcooling). This drop in temperature extends the dehumidification cycle. Later, when the dehumidification ends and the temperature rises to the setpoint, the RH reading falls. The final RH reading will then be lower than actually desired. If the temperature drop was significant enough, the percentage RH could be low enough to activate the humidifier.

If the absolute humidity control is selected, over-dehumidification may be avoided. When overcooling occurs (i.e., causing an increase in the RH reading) the humidity control program estimates what the RH will be when the dehumidification cycle ends and temperature returns to the setpoint. This allows the dehumidification cycle to end at the proper time. Predictive humidity control can greatly reduce energy consumption by minimizing both compressor/reheat operation. Use the UP or DOWN arrow key to select the desired humidity control method.

6.9.4Show DIP Switch

This function shows the position of the DIP switches, which are located on the control board in the unit; 1 = Switch is “ON” and 0 = Switch is “OFF.” For more information on the DIP switches and their functions, see Table 20.

Liebert® Mini-Mate2

42

Image 48
Contents Liebert Mini-Mate2 Page Table of Contents Microprocessor Control System Performance Microprocessor ControlsAlarms System OPERATION, Testing and MaintenanceTables Important Safety Instructions Liebert Mini-Mate2 Product Model Information Air-cooled systems-indoor centrifugal condensing unitsPFH 0 67 a a L System configurations-60 Hz System configurations-50 HzIntroduction Standard FEATURES-5 TON Systems Evaporator Section-Split SystemCondensing Unit Section-Split System Chilled Water UnitsOther Standard Control Features System ControlsSwitches and Motors ReheatHumidifier SensorsOptional Configurations-Prop Fan Condensing Units Optional Configurations-Water/Glycol Condensing UnitsFree-Cooling Optional Configurations-Chilled Water Units SHIP-LOOSE ACCESSORIES-FIELD-INSTALLED Ship-Loose Accessories-Field-Installed Installation Considerations Site Preparation and InstallationRoom Preparation Location Considerations Air-cooled systemsCeiling Unit Weights Unit weightsCooling Drycooler Cooling UnitsInstalling the Ceiling Units Close Coupled InstallationsEquipment Inspection Upon Receipt Evaporator Air Distribution Filter BoxConnections for Ducted Systems Piping Connections and Coolant Requirements Drain LineHumidifier Water Supply Line Evaporator external static pressureRecommended refrigerant line sizes Equivalent lengths for various pipe fittings, ft mEquivalent Pipe Liquid Suction Length, ft m Copper PipePipe length and condenser elevation relative to evaporator Vertical rise above evaporator/maximumVertical fall below evaporator Total refrigerant = Units and Lines Quick Connect FittingsRefrigerant charge Line charges refrigerant per 100 ft m of Type L copper tubeDPN000218 Threaded rod and hardware kit installation Electrical ConnectionsPower Connections Control ConnectionsEvaporator unit electrical connections Close coupled installation Piping Connections DuctingGeneral Considerations Considerations for Specific ApplicationsAIR-COOLED Dimensional Data AIR Cooled AIR-COOLED Outdoor Air-Cooled Condensing Unit Installation Weight, lb kgModel # 60Hz 50Hz Rev Water/Glycol Piping Considerations Condensing Unit Fluid RequirementsRegulating Valve WATER/GLYCOL Dimensional Data WATER/GLYCOL DPN000214 Hot Water Reheat Coil Optional free-cooling coil 3-way valve on water/glycol unitsChecklist for Completed Installation Feature Overview Microprocessor ControlMain Menu Menu SetpointsActive Alarms StatusTime DateSetup Operation Restart Time DelayShow DIP Switch 2 C/F DegreesChange Passwords Setup functions, default values and allowable rangesFunction Default Range Calibrate SensorsAlarm Enable Alarm Time DelayCommon Alarm Enable Alarm default time delaysCustom Alarms Standard Custom Alarm MessagesCustom Text LCD Display ContrastRun Diagnostics Available On Rev 1.001.0 and higher Equipment Options SwitchesEquipment switch settings unit control board Switch settings wall box boardTest Outputs Test Control BoardControl menu Control board-inside evaporator Wall box boardTemperature Control Humidity ControlSystem Performance Microprocessor Controls Load Control Features Humidification OperationCommunications Alarms Definitions and Troubleshooting AlarmsCustom Alarms High Head PressureTemperature Humidifier Problem AlarmHigh Water Alarm Air-Cooled SystemsOptional/Custom Alarms System Testing Maintenance and Component OperationSystem OPERATION, Testing and Maintenance Blower System Air DistributionBlower Removal Refrigeration SystemGlycol Solution Maintenance Discharge PressureThermostatic Expansion Valve Air-Cooled Condensing UnitsHot Gas Bypass Hot gas bypassReplacement Procedures Compressor ReplacementMechanical Failure Electrical FailureReplace a Failed Compressor Steam Generating Humidifier-Operation Procedures Humidifier Circuit Board Adjustments Humidifier control board DIP switch settingsReplacing the Humidifier Canister AmpsMaintenance Inspection Checklist Troubleshooting TroubleshootingSymptom Possible Cause Check Or Remedy Cooling cycle too Display ProblemShort Display freezesNe t Ppor t Is tTwor k Care

MINI-MATE2 specifications

The Emerson MINI-MATE2 is a cutting-edge temperature and pressure monitoring device specifically designed for the needs of the refrigeration and HVAC industries. Known for its reliability and user-friendly interface, this compact unit serves as a key tool for technicians and facility managers looking to optimize system performance while ensuring compliance with safety standards.

One of the main features of the MINI-MATE2 is its advanced digital display, which allows users to easily monitor and interpret temperature and pressure readings in real-time. Its highly responsive sensors ensure accurate data collection, vital for maintaining optimal operating conditions. Moreover, the device supports a wide range of refrigerants, making it versatile for different applications, from walk-in coolers to commercial refrigeration systems.

The MINI-MATE2 utilizes state-of-the-art technology to enhance efficiency and performance. Equipped with Bluetooth connectivity, it allows for wireless communication with mobile devices, enabling technicians to track readings and receive alerts remotely. This feature not only improves convenience but also helps in quick decision-making, ensuring timely interventions when anomalies are detected.

Another significant characteristic is its robust construction. Built to withstand harsh environments, the MINI-MATE2 features a durable casing that protects it from physical impacts and environmental factors. This resilience ensures longevity, making it a cost-effective investment for any facility.

In addition, the MINI-MATE2 is designed with user-friendliness in mind. Its intuitive interface means that even technicians with limited experience can easily navigate its functionalities. Quick setup and straightforward operation allow for rapid adoption and extensive use in a variety of settings.

Finally, the MINI-MATE2 also includes built-in data logging capabilities. Users can record historical data for analysis and reporting purposes, which is essential for performing trend analysis and identifying potential issues before they escalate. By providing a comprehensive overview of system performance, the MINI-MATE2 empowers users to make informed decisions that can lead to improved energy efficiency and reduced operational costs.

Overall, the Emerson MINI-MATE2 is an indispensable tool for modern refrigeration and HVAC applications, combining cutting-edge technology, user-friendly design, and essential features to support efficient system management.