Emerson MINI-MATE2 user manual Piping Connections, Ducting, General Considerations

Page 33

Site Preparation and Installation

5.5Indoor Air-Cooled Centrifugal Fan Condensing Unit Installation

NOTE

Follow all national and local building, electrical and plumbing codes.

5.5.1Location Considerations

The centrifugal fan air-cooled condensing unit may be located above the dropped ceiling or any remote indoor area. If noise is of concern, the condensing unit should be located away from personnel. Normal operating sound may be objectionable if the condensing unit is placed near quiet work areas.

To mount the unit in the ceiling, refer to 5.4 - Installing the Ceiling Units.

5.5.2Electrical Connections

Refer to 5.4.4 - Electrical Connections for general wiring requirements and cautions. Refer to electrical schematic when making connections. Refer to unit serial tag for full load amp and wire size amp ratings.

Power Connections

The condensing unit requires its own power source and earth ground, with a disconnect switch to isolate the unit for maintenance.

NOTE

Refer to serial tag for full load amp and wire size amp ratings

Control Connections

Field-supplied control wires must be connected between the evaporator and the condensing unit (See Figure 14 and Figure 17) and the electrical schematic on the units for more details.) Four wires are required between the evaporator and condensing unit.

5.5.3Piping Connections

Details for refrigerant loop piping are in 5.4.3 - Piping Connections and Coolant Requirements.

5.5.4Ducting

Fan operation is designed for 3500 CFM (5947 CMH) at 0.5" (0.12kPa) external static pressure.

General Considerations

Use flexible ductwork or nonflammable cloth collars to attach ductwork to the unit and to control vibration transmission to the building. Attach the ductwork to the unit using the flanges provided. Locate the unit and ductwork so that the discharge air does not short circuit to the return air inlet.

Ductwork that runs through a conditioned space or is exposed to areas where condensation may occur must be insulated. Ductwork should be suspended using flexible hangers. Ductwork should not be fastened directly to the building structure.

For multiple unit installations, space the units so that the hot condensing unit exhaust air is not directed toward the air inlet of an adjacent unit.

Considerations for Specific Applications

In applications where the ceiling plenum is used as the heat rejection domain, the discharge air must be directed away from the condensing unit air inlet and a screen must be added to the end of the discharge duct to protect service personnel. Locate the air discharge a minimum of 4 feet from an adjacent wall. Failure to do so may result in reduced air flow and poor system performance.

If the condensing unit draws air from the outside of the building, rain hoods must be installed. Hood intake dimensions should be the same as the condensing unit duct dimensions. In addition, install a triple layer bird screen over rain hood openings to eliminate the possibility of insects, birds, water or debris entering the unit. Avoid directing the hot exhaust air toward adjacent doors or windows.

27

Liebert® Mini-Mate2

Image 33
Contents Liebert Mini-Mate2 Page Table of Contents System Performance Microprocessor Controls Microprocessor ControlSystem OPERATION, Testing and Maintenance AlarmsTables Important Safety Instructions Liebert Mini-Mate2 Air-cooled systems-indoor centrifugal condensing units Product Model InformationPFH 0 67 a a L System configurations-50 Hz System configurations-60 HzIntroduction Evaporator Section-Split System Standard FEATURES-5 TON SystemsCondensing Unit Section-Split System Chilled Water UnitsSystem Controls Other Standard Control FeaturesReheat Switches and MotorsHumidifier SensorsOptional Configurations-Prop Fan Condensing Units Optional Configurations-Water/Glycol Condensing UnitsFree-Cooling Optional Configurations-Chilled Water Units SHIP-LOOSE ACCESSORIES-FIELD-INSTALLED Ship-Loose Accessories-Field-Installed Installation Considerations Site Preparation and InstallationRoom Preparation Air-cooled systems Location ConsiderationsUnit weights Ceiling Unit WeightsCooling Drycooler Cooling UnitsClose Coupled Installations Installing the Ceiling UnitsEquipment Inspection Upon Receipt Evaporator Air Distribution Filter BoxPiping Connections and Coolant Requirements Drain Line Connections for Ducted SystemsHumidifier Water Supply Line Evaporator external static pressureEquivalent lengths for various pipe fittings, ft m Recommended refrigerant line sizesEquivalent Pipe Liquid Suction Length, ft m Copper PipePipe length and condenser elevation relative to evaporator Vertical rise above evaporator/maximumVertical fall below evaporator Quick Connect Fittings Total refrigerant = Units and LinesRefrigerant charge Line charges refrigerant per 100 ft m of Type L copper tubeDPN000218 Electrical Connections Threaded rod and hardware kit installationControl Connections Power ConnectionsEvaporator unit electrical connections Close coupled installation Ducting Piping ConnectionsGeneral Considerations Considerations for Specific ApplicationsAIR-COOLED Dimensional Data AIR Cooled AIR-COOLED Outdoor Air-Cooled Condensing Unit Installation Weight, lb kgModel # 60Hz 50Hz Rev Water/Glycol Piping Considerations Condensing Unit Fluid RequirementsRegulating Valve WATER/GLYCOL Dimensional Data WATER/GLYCOL DPN000214 Optional free-cooling coil 3-way valve on water/glycol units Hot Water Reheat CoilChecklist for Completed Installation Microprocessor Control Feature OverviewSetpoints Main Menu MenuStatus Active AlarmsTime DateRestart Time Delay Setup OperationShow DIP Switch 2 C/F DegreesSetup functions, default values and allowable ranges Change PasswordsFunction Default Range Calibrate SensorsAlarm Time Delay Alarm EnableCommon Alarm Enable Alarm default time delaysStandard Custom Alarm Messages Custom AlarmsCustom Text LCD Display ContrastEquipment Options Switches Run Diagnostics Available On Rev 1.001.0 and higherEquipment switch settings unit control board Switch settings wall box boardTest Control Board Test OutputsControl menu Wall box board Control board-inside evaporatorTemperature Control Humidity ControlSystem Performance Microprocessor Controls Load Control Features Humidification OperationCommunications Alarms Alarms Definitions and TroubleshootingCustom Alarms High Head PressureHumidifier Problem Alarm TemperatureHigh Water Alarm Air-Cooled SystemsOptional/Custom Alarms System Testing Maintenance and Component OperationSystem OPERATION, Testing and Maintenance Air Distribution Blower SystemBlower Removal Refrigeration SystemDischarge Pressure Glycol Solution MaintenanceThermostatic Expansion Valve Air-Cooled Condensing UnitsHot gas bypass Hot Gas BypassCompressor Replacement Replacement ProceduresMechanical Failure Electrical FailureReplace a Failed Compressor Steam Generating Humidifier-Operation Procedures Humidifier control board DIP switch settings Humidifier Circuit Board AdjustmentsReplacing the Humidifier Canister AmpsMaintenance Inspection Checklist Troubleshooting TroubleshootingDisplay Problem Symptom Possible Cause Check Or Remedy Cooling cycle tooShort Display freezesPpor t Is t Ne tTwor k Care

MINI-MATE2 specifications

The Emerson MINI-MATE2 is a cutting-edge temperature and pressure monitoring device specifically designed for the needs of the refrigeration and HVAC industries. Known for its reliability and user-friendly interface, this compact unit serves as a key tool for technicians and facility managers looking to optimize system performance while ensuring compliance with safety standards.

One of the main features of the MINI-MATE2 is its advanced digital display, which allows users to easily monitor and interpret temperature and pressure readings in real-time. Its highly responsive sensors ensure accurate data collection, vital for maintaining optimal operating conditions. Moreover, the device supports a wide range of refrigerants, making it versatile for different applications, from walk-in coolers to commercial refrigeration systems.

The MINI-MATE2 utilizes state-of-the-art technology to enhance efficiency and performance. Equipped with Bluetooth connectivity, it allows for wireless communication with mobile devices, enabling technicians to track readings and receive alerts remotely. This feature not only improves convenience but also helps in quick decision-making, ensuring timely interventions when anomalies are detected.

Another significant characteristic is its robust construction. Built to withstand harsh environments, the MINI-MATE2 features a durable casing that protects it from physical impacts and environmental factors. This resilience ensures longevity, making it a cost-effective investment for any facility.

In addition, the MINI-MATE2 is designed with user-friendliness in mind. Its intuitive interface means that even technicians with limited experience can easily navigate its functionalities. Quick setup and straightforward operation allow for rapid adoption and extensive use in a variety of settings.

Finally, the MINI-MATE2 also includes built-in data logging capabilities. Users can record historical data for analysis and reporting purposes, which is essential for performing trend analysis and identifying potential issues before they escalate. By providing a comprehensive overview of system performance, the MINI-MATE2 empowers users to make informed decisions that can lead to improved energy efficiency and reduced operational costs.

Overall, the Emerson MINI-MATE2 is an indispensable tool for modern refrigeration and HVAC applications, combining cutting-edge technology, user-friendly design, and essential features to support efficient system management.