Page 10

3.2 Mounting the transmitter above the liquid surface.

A 2” thread is provided to mount the transmitter.

The user should check the thread form, which will be either 2” BSPT (MSP400RH-B28) or 2” NPT (MSP400RH-N28). The thread form is clearly marked on the hexagon of the transducer body.

Note : The MSP400 is designed to be mounted in a non-metallic fitting or flange. The use of metallic fittings or flanges is not recommended.

To help installation, a bracket kit is available from Mobrey. This comprises a Stainless Steel angle bracket and PVC threaded disc which may be used to mount the MSP400 on a gantry or other support over the liquid level. Order part number MSP-BRK2 (BSP) or MSP-BRK3 (NPT). The bracket may be bolted to a suitable cross member above the liquid surface.

Ensure that the transmitter is perpendicular to the liquid surface to maximise the return echo size.

Check that the maximum liquid level will not encroach into the 0.45m blanking zone of the transmitter.

Note : To aid alignment, the echo size / signal strength can be displayed on the MCU900 control unit or on the MSP400RH transmitter display. Refer to section 4 for details.

Use PTFE tape on the screw thread, tighten to hand tight + ¼ turn, using the Hexagon.

When installing on a vessel which has a nozzle or stand-off, and the transducer face does not protrude into the vessel, note the dimensions in the diagram below and always ensure that the nozzle/vessel weld is smooth and free from internal weld beads or other projections.

Use hexagon to tighten to hand tight + ¼ turn

DO NOT USE HOUSING TO TIGHTEN.

PTFE

(Teflon)

Min :

R3,0mm (1/8")

Max : 0,35m (14")

Min 0,15m (6")

10

IP2046/IM

Nov 2006

 

Image 10
Contents Mobrey Contents Introduction Pvdf Wetside Installation IP2046/IM IP2046/IM IP2046/IM Do not USE Housing to Tighten Ptfe RL1 Spst IP2046/IM Alarm IP2046/IM IP2046/IM Selecting the units of measurement Screen display 20/4 Ullage Liquid level SPEC. P CYL.F Scale LEUEL@ max Maximum flow entry Screen display IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM Loop IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM Duty Appendix A1 Main Menu ProgrammingSEt20 Appendix A1Appendix A2 Diagnostics Menu LeuelLoop Appendix A3 Commissioning / Loop Test MenuEngineering Menu Appendix A4Appendix B Default Value Listing Main Menu Parameters ProFDefault Value Listing Engineering Parameters DEAdAppendix C Listing of NON-LINEAR Profiles in the MSP400 SPEC.CAppendix D Hart Communications with the MSP400 Table of MSP400 Parameters IP2046/IM IP2046/IM Instruction & maintenance leaflet