Emerson MSP400RH, IP2046IM manual IP2046/IM

Page 34

If the new temperature is incorrect, the edit sequence can be re-started by pressing the blue button again.

If the temperature is correct, press the red button to save the new value to memory and automatically scroll on to the next main menu option:

The next option will be “t.CAL” if the MSP400 is using the Mobrey remote temperature probe MSP-RTP to monitor the air temperature.

If no external temperature probe is connected the next menu option will be “Ld.dEF”. Refer now to Section 4.7.10.

4.7.9 Temperature calibration

Screen display

“t.CAL”

This menu option is only displayed if the MSP400 is using the Mobrey remote temperature probe MSP-RTP to monitor the air temperature.

Remote air temperature measurement is only possible with the Mobrey MSP-RTP. This is a negative temperature co-efficient (NTC) thermistor design.

Due to the effects of cable length and electronic component tolerances the MSP-RTP air temperature measurement could be up to +/- 0.5°C in error.

This menu option allows the user to trim the recorded temperature to match the users own reading.

To edit and fix the temperature :

a)Press the blue button to enter the temperature calibration menu and to display the current value in use. If this is correct, press the red button return to the main menu.

If the temperature is to be calibrated, press the blue button again to allow calibration.

The leading digit of the temperature will now be flashing, indicating it may be changed.

b)Use the green button to edit the value of the leading digit.

c)Once correct, use the blue button to select the next digit and then the green button to edit as before, or the blue button to move to the next digit. Continue this sequence until all digits are correct.

d)Press the blue button a final time to confirm the new value. None of the digits should now be flashing.

If the new temperature is incorrect, the edit sequence can be re-started by pressing the blue button again.

If the temperature is correct, press the red button to save the new value to memory and automatically scroll on to the next main menu option:

4.7.10 Loading factory default values

Screen display

“Ld.dEF”

It may occasionally be necessary to re-set the MSP400 parameters to factory default values, particularly if the user is unsure of data already changed and held in the transmitter.

Note : Re-loading factory defaults will overwrite all parameters and all site entered data will be lost.

To ensure that this operation is not initiated by accident, a specific push button sequence is necessary to load factory defaults.

34

IP2046/IM

Nov 2006

 

Image 34
Contents Mobrey Contents Introduction Pvdf Wetside Installation IP2046/IM IP2046/IM IP2046/IM Do not USE Housing to Tighten Ptfe RL1 Spst IP2046/IM Alarm IP2046/IM IP2046/IM Selecting the units of measurement Screen display 20/4 Ullage Liquid level SPEC. P CYL.F Scale LEUEL@ max Maximum flow entry Screen display IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM Loop IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM Duty Appendix A1 Main Menu ProgrammingSEt20 Appendix A1Appendix A2 Diagnostics Menu LeuelLoop Appendix A3 Commissioning / Loop Test MenuEngineering Menu Appendix A4Appendix B Default Value Listing Main Menu Parameters ProFDefault Value Listing Engineering Parameters DEAdAppendix C Listing of NON-LINEAR Profiles in the MSP400 SPEC.CAppendix D Hart Communications with the MSP400 Table of MSP400 Parameters IP2046/IM IP2046/IM Instruction & maintenance leaflet