4.0 Commissioning, programming and operation

The MSP400 operates from a menu of parameters, each held in a specific memory location within the instrument. The memory locations may be pictured as a matrix, and the user navigates to each parameter to programme the instrument using and steps.

Refer now to the Main Menu structure shown in Appendix A

The MSP400 leaves the factory pre-programmed with a value in each parameter location such that , when the power is first applied, the instrument will give a sensible reading. A list of default values is given in the parameter listing in Appendix B.

The MSP400 is HART enabled, allowing remote communications with the instrument.

The instrument can therefore be either programmed using a suitable HART compatible master, or may be programmed locally using the push buttons provided inside the instrument. For details of local programming, continue reading this section. For details of HART communications, refer to Appendix D.

4.1 Display and push buttons.

D

 

 

Alarm

L

 

 

Fault

C

 

 

 

F

gal/m 3/hrft 3 /hringal/s @max

 

 

Button Colour :

Green

Blue

Red

The main display allows display of up to 5 characters, which in the normal run mode will be the measurement, termed the Primary Variable (PV) of the instrument, or in the programming mode will be data to assist in programming.

To the left of the main display are 4 arrow icons, only one of which will be illuminated at any one time to indicate the duty chosen by the user.

To the right of the main display are 2 arrow icons which indicate the status of the transmitter relays. When illuminated, they indicate that the relay contact is closed.

Under the main display is a text string which allows display of the units of measurement. The instrument will illuminate only those characters applicable to the units of measurement chosen.

To the right of the text string is an echo received icon made up of 3 arc segments which continuously indicate the strength of the echo received (minimum, average and good)

13

IP2046/IM

Nov 2006

 

Image 13
Contents Mobrey Contents Introduction Pvdf Wetside Installation IP2046/IM IP2046/IM IP2046/IM Do not USE Housing to Tighten Ptfe RL1 Spst IP2046/IM Alarm IP2046/IM IP2046/IM Selecting the units of measurement Screen display 20/4 Ullage Liquid level SPEC. P CYL.F Scale LEUEL@ max Maximum flow entry Screen display IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM Loop IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM Appendix A1 Main Menu Programming DutyAppendix A1 SEt20Leuel Appendix A2 Diagnostics MenuAppendix A3 Commissioning / Loop Test Menu LoopAppendix A4 Engineering MenuProF Appendix B Default Value Listing Main Menu ParametersDEAd Default Value Listing Engineering ParametersSPEC.C Appendix C Listing of NON-LINEAR Profiles in the MSP400Appendix D Hart Communications with the MSP400 Table of MSP400 Parameters IP2046/IM IP2046/IM Instruction & maintenance leaflet