Emerson MSP400RH, IP2046IM manual Appendix D Hart Communications with the MSP400

Page 44

APPENDIX D

HART COMMUNICATIONS WITH THE MSP400

D 1.0 Overview

The MSP400 ultrasonic level transmitter supports HART communications, which may be used to programme or interrogate the transmitter remotely from any point on the 2 wire loop.

Any HART compatible communication device may be connected across the loop and, if loaded with the Device Description (DD) of the MSP400 transmitter, will have full access to the all of the parameters of the instrument as shown in D 3.0

If the communication device is not loaded with the MSP400 DD, then access to the Universal and some Common Practice commands is possible in accordance with HART convention.

The MSP400 may be used with the Mobrey MCU900 Series of control units. MCU900 will

supply the 24V dc loop power to the MSP400 and provide control functionality using the 4-20mA signal from the transmitter.

The MCU900 control unit has HART communications capability and access to all of the parameters of the MSP400 as shown in D3.0.

The Mobrey PC software “DDConf” is also available, allowing a computer fitted with a HART modem to communicate with and re-programme the MSP400 transmitter. Note : A HART modem is supplied with the DDConf software.

D 2.0 Wiring

Wiring for HART communications is no different to that of 4-20mA instruments, except that the loop must contain a resistance of at least 250 Ohm. This resistance may be achieved by a combination of wiring resistance and any other loop instruments, or may be achieved by the inclusion of a suitable 250 Ohm resistor, usually connected in series in the +24V dc power line at the power supply.

Note, the MSP400 requires a minimum voltage of 12V dc at the terminals for correct operation.

44

IP2046/IM

Nov 2006

 

Image 44
Contents Mobrey Contents Introduction Pvdf Wetside Installation IP2046/IM IP2046/IM IP2046/IM Do not USE Housing to Tighten Ptfe RL1 Spst IP2046/IM Alarm IP2046/IM IP2046/IM Selecting the units of measurement Screen display 20/4 Ullage Liquid level SPEC. P CYL.F Scale LEUEL@ max Maximum flow entry Screen display IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM Loop IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM IP2046/IM Duty Appendix A1 Main Menu ProgrammingSEt20 Appendix A1Appendix A2 Diagnostics Menu LeuelLoop Appendix A3 Commissioning / Loop Test MenuEngineering Menu Appendix A4Appendix B Default Value Listing Main Menu Parameters ProFDefault Value Listing Engineering Parameters DEAdAppendix C Listing of NON-LINEAR Profiles in the MSP400 SPEC.CAppendix D Hart Communications with the MSP400 Table of MSP400 Parameters IP2046/IM IP2046/IM Instruction & maintenance leaflet